hager XEM470 Flow Energy Management Controller Instruction Manual

June 3, 2024
hager

hager logo

flow Energy Management Controller 6LE007863A

XEM470 Flow Energy Management Controller

XEM470
Danger of death by electric shock.
Live components carry potentially fatal voltages.

  • Before starting any installation or maintenance work, switch off the power to the distribution board and secure to prevent itbeing switched on again accidentally.
  • Make sure that the conductors to be connected to the meter are voltage-free.
  • All installation and maintenance work on this unit must be carried out by a trained and authorised electrician.

The Energy Management Controller is supplied with power via outer conductor L1. At least the outer conductor L1 and neutral conductor N need to be connected for the
unit to switch on.

Introduction

flow connects the electrical system to the main producers and consumers of the installation in a modular way. Once installed in the meter cabinet, flow monitors and controls
the electrical energy dynamics in your home in a modular and flexible manner, by measuring and controlling devices like electric storage system, electric vehicles, heating
system and photovoltaic installation. It prevents your domestic electrical supply from being overloaded and optimize the consumption and energy flows.

Documentation

The latest and complete documentation is available on https://hgr.io/r/XEM470

hager XEM470 Flow Energy Management Controller - qr 1https://hgr.io/r/XEM470

Safety instructions

Danger of death by electric shoc

k.

  • Live components carry potentially fatal voltages.
  • Only use the Energy Management Controller in a dry environment and keep it away from liquids.
  • Install the Energy Management Controller only in approved enclosures or distribution boards downstream of the electricity supply company’s meter so that the connections for the outer and neutral conductors are located behind a cover or guard to prevent accidental contact.
  • Before starting any installation or maintenance work, switch off the power to the distribution board and secure to prevent it being switched on again accidentally.
  • Maintain the prescribed minimum distances between the network cable and mains voltage installation components or use suitable insulation.

Avoid damage to or destruction of the Energy Management Controller

  • Do not connect an ISDN cable to the Energy Management Controller’s networkconnection.
  • Damage to or destruction of the EnergyManagement Controller by voltage surgeson the network cable.
  • If network cables are installed outside thebuilding, voltage surges can be caused bylightning strike, for example.
  • If installed outside the building, the networkcable must be protected with suitable overvoltage protection.
  • Protect your solar installation with invertersusing suitable overvoltage protection.
  • Damage to or destruction of the EnergyManagement Controller by improper use.
  • Do not operate the Energy Management Controller outside the specified technical tolerances.
  • The LAN1/2 Ethernet interface of the connected unit must meet the safety extralow voltage requirements.

Technical data

Interfaces LAN (10/100 Mbit) RS485 (half-duplex, max. 115200 baud)
Protection class II
Overvoltage category III
IP IP2X
Connection cross section In line with EN 60204 10-25 mm2′

• Mechanical: 1.5-25 mm (e.g. for connecting external current transformers)
Tightening torque for screw terminals| 2.0 Nm
Weight| 0.3 kg
Dimensions| 88 x 70 x 65 mm
Ambient temperature in operation
with reduced measuring current I,„ < 32 A| -25 °C…+45 °C
-25 °C…+55 °C
Ambient temperature during transportation / storage| -25 °C…+70 °C
Relative humidity (non- condensing)| Up to 75 % as an annual average, up to 95% on up to 30 days/year
Max. altitude during operation| 2000 m above sea level
Degree of polution| 2
Utilisation| Indoor use only
Mains power supply
Starting current| < 25 mA
Supply voltage / frequency| 110 V – *10 % / 60 Hz ± 5% or
230 V – ±10 % / 50 Hz ± 5%
Internal consumption P,,,..| 5.0 W
Measuring current circuit for measurement category III
Limit current I„ / phase| 63 A
Rated voltage| max. 230/400 V –
Frequency range| 50/60 Hz ± 5 %

Operation of the Energy Management Controller at ambient temperature of 55°C
The Energy Management Controller must not be run continuously at ambient temperatures of 55 °C. If such condition can be present, please consider the usage of
Current Transformer and to install the Energy Management Controller in an appropriate environment.
** Danger of death by electric shock or fire Live components carry potentially fatal voltages.
If the ambiant temperature exceed 45°C:**

  • Electrical protection must not exceed 32 A.
  • External current transformers should be used for higher currents.
  • The Energy Management Controller must be connected with cables that are at least 10 mm² in cross section and no less than 1 m long.

Product description

hager XEM470 Flow Energy Management Controller - fig

A Outer conductors, L1, L2, L3 outputs
B(A) RS485 modbus RTU connection
B(B) Not used
C Connection Ethernet LAN1
D Connection Ethernet LAN2
E PWR: Power LED
F APP: Application LED
G NET: Network LED
H BTN: Button (reset)
I Outer conductors, L1, L2, L3 Inputs
J Neutral conductor N

Modbus interface

Note the following points when connecting external devices to the RS485 Modbus RTU interface of the Energy Management
Controller:
Requirement for the cable:

  • Nominal voltage/wire insulation: 300 V RMS
  • Cable cross section: 0.25 … 1.5 mm²
  • Cable type: Rigid or flexible
  • Recommendation: Use AlphaWire standard cable, designation 2466C. Alternatively, a CAT5e cable can also be used.

Requirement for cable installation:

  • In the area for connecting the RS485 Modbus RTU interface on the Energy Management Controller, mechanical means must be provided to ensure that individual wires of the connecting cable are at least 10 mm away from live parts.
  • The connecting cable must be run separately from the mains cables in the distribution board and on the permanent link.
  • The RS485 Modbus RTU interface of the connected unit must meet the safety extra low voltage requirements.

Figure: Enlarged detail of the figure from above WITH connector

Connection diagram for RS485 connector:

Pin Description Color
1 Not used
2 Com. / C/C’ / OVL Brown
3 D1 / B/B’ / (+) Green
4 D0 / A/A’ / (-) Yellow

Maximal modbus cable length = 10 m.

Led statuses

Power LED

Colour| Status| Description
Green| Flashing| Device is starting.
Green| On| Application launched correctly and running.
Orange| Flashing| Application on update.
Orange| On| Application not launched: an Issue appears in application lifecycle; If system doesn’t go back to normal, please take contact with hager support.
Red| On| Application / System Dead: Try to realize an hardware reboot. If system doesn’t go back to normal, please take contact with hager support.
Application LED
Colour| Status| Description
Green| On| Installation is running.
Orange| On| Alert occur, see flow website https://flow.hager.com for detail.
Red| On| Critical error occur, see flow website https://flow.hager.com for detail.
Network LED
Colour| Status| Description
/| Off| No connection during booting or if application is not launched.
Green| On| Internet connected & Cloud connected.
Green| Flashing rapidly| Confirmation the start of the local webserver using the push button (press between 2 and 4 seconds).
Green| Flashing| Local WebServer for Network configuration activated/reachable.
Orange| On| Internet connected & No Cloud connection.
Orange| Flashing| No Internet connection & No Cloud connection.
Red| On| Network issue: conflict on IP, no address got from DHCP server…
Red| Flashing rapidly| Confirmation the start of “network reset to default” using the push button (press more than 4 seconds) – see section 12. Hardware reboot and network settings.

Electrical connection for direct  measurement

It must be ensured by fitting the according protection that the maximum permitted current per phase (63A) is not exceeded.

  1. Install the Energy Management Controller on a DIN rail.
  2. Connect the conductors to the Energy Management Controller. Do not exceed the permitted connection cross section and tightening torque for the screw terminals
    (see section “4. Technical data”):
    • For a three phase power network, connect the outer conductors L1, L2 and L3 and the neutral conductor N to the
    Energy Management Controller as shown in the connection diagram.
    • For a single phase power network, connect the outer conductor L1 and neutral conductor N to the Energy Management Controller as shown in the connection diagram.
    The following figure contains a connection example.
    Check correct allocation of the phases Make sure that the phases are all correctly allocated, otherwise the Energy Management Controller will return incorrect measured values and failed to ensure overload protection
    .In case of combination with a Storage System, please follow the wiring diagram of the system/ storage.

hager XEM470 Flow Energy Management Controller - fig6

Electrical connection for indirect measurement with current transformers

  1. Install the Energy Management Controller on a DIN rail. To do this, hook the XEM470 onto the top edge of the DIN rail and press down until it latches into place.

  2. Connect a current transformer to each outer conductor L1, L2 and L3.
    **** Danger of death by electric shock at the current transformer terminals.
    Due to the type of connection, there is a mains voltage of 230 V present at conductors k/s1 and l/s2. To prevent accidents, put up a notice with this information at this location on site.

  3. Connect a cable for the secondary current measurement to terminals k/s1 and I/s2 on  each current transformer. Do not exceedthe permitted connection cross section for the Energy Management Controller (see section “4. Technical data”).

  4. Connect the connecting cable for the current measurement to the Energy Management Controller and do not exceed the permitted tightening torque for screw
    terminals (see section “4. Technical data”).

  5. Connect the connecting cables for the voltage measurement to the outer conductors L1, L2 and L3.

The following figure contains a connection example.
Figure: Connection for indirect measurement with current transformershager
XEM470 Flow Energy Management Controller - fig8

Designation Explanation
L1, L2, L3 Outer conductor
N Neutral conductor
OUT Meter output, distribution board side
IN Meter input, mains side

Start the web interface

hager XEM470 Flow Energy Management Controller - qrhttps://flow.hager.com

  1. Flash QRCode sticker on the XEM470 front-face to access to its installation or to pair it to one. or
    1. Connect to https://flow.hager.com 
    2. LogIn with yours myhager Pro credentials.
    3. Create or select the installation to add the EMC to this one.

Hardware reboot and network settings

Use a pointed object to press the BTN button: After 2s, the NET LED will first blink green, release now to start the embedded webserver to set up network settings. Once the web server is active, it will be accessible using its IP address and the NET LED will flash slowly in green.
Keep pressing after 4s, then the NET LED will blink in red, release now to go back to factory network settings. A reboot will occur.
Keep pressing after 7s to realize an hardware reboot. all EMC’s LED will switch off, now release.

Fault finding

The PWR LED does not light up.
The Energy Management Controller is not being supplied with power.

  • Make sure that at least the top/outer conductor L1 and the neutral conductor N are connected to the Energy Management Controller.
    The NET LED lights up or flashes orange or red.
    The EMC isn’t connected properly on our cloud.

  • Check the house internet connection

  • Check the ethernet cable connection

  • Check if an error occur on https://flow.hager.com/

  • Restart the EMC

  • The IP configuration isn’t set properly.
    The APP LED flashes orange or red.
    Orange: an alert occur on the installation, see https://flow.hager.com to see the detail. Red: a critical error occur on the installation, see https://flow.hager.com to see the detail.

  • Restart the EMC could solve the issue.

 Environmentally-friendly disposal

Dispose of the Energy Management Controller in accordance with the electronic waste disposal regulations that apply on site.

Open source licenses

This product also contains open source software that was developed by third parties. This relates, in particular, to the GPL and LGPL licenses.
You will find the license text and associated notes on the Energy Management Controller user interface.

Contact

HagerEnergy GmbH
Karlstraße 5
49074 Osnabrück Germany
info@hager.com
www.hager.com 
HagerEnergy GmbH-Karlstraße 5-49074 Osnabrück-GERMANY – www.hager.com
Can be used anywhere in Europe M and Switzerland

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals