Shinko LV-300 Level Switch Instruction Manual

June 3, 2024
Shinko

Shinko-logo

Shinko LV-300 Level Switch

No.LV31JE6 2021.10 To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

Safety Precautions

(Be sure to read these precautions before using our products.)
The safety precautions are classified into categories:

  • “Warning” and “Caution”.
    • Depending on circumstances, procedures indicated by so be sure to follow the directions for usage.
    • Caution may be linked to serious results,
    • Procedures which may lead to dangerous conditions and cause death or serious injury, if not carried out properly.
    • Procedures which may lead to dangerous conditions and cause superficial to medium injury or physical damage or may degrade or damage the product, if not carried out properly.

Warning

  • To prevent an electrical shock or fire, only Shinko or other qualified service personnel may handle the inner assembly.
  • To prevent an electrical shock, fire or damage to the instrument, parts replacement may only be undertaken by Shinko or other qualified service personnel.

Safety Precautions

  • To ensure safe and correct use, thoroughly read and understand this manual before using this instrument.

  • This instrument is intended to be used for industrial machinery, machine tools and measuring equipment. Verify correct usage after purpose-of-use consultation with our agency or main office. (Never use this instrument for medical purposes with which human lives are involved.)

  • External protection devices such as overcurrent protection fuse, etc. must be installed, as malfunction of this product could result in serious damage to the system.
    Proper periodic maintenance is also required.

  • This instrument must be used under the conditions and environment described in this manual. Shinko Technos Co., Ltd. does not accept liability for any injury, loss of life or damage occurring due to the instrument being used under conditions not otherwise stated in this manual.

Caution with Respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the manufacture of weapons of mass destruction (i.e. military applications, military equipment, etc.), please investigate the end users and the final use of this instrument.
In the case of resale, ensure that this instrument is not illegally exported.

Installation Precautions

Caution
This instrument is intended to be used under the following environmental conditions (IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:

  • A minimum of dust, and an absence of corrosive gases

  • Few mechanical vibrations or shocks

  • No exposure to direct sunlight, an ambient temperature of 0 to 55 (32 to 131 ) that does not change rapidly, and no icing

  • Mount the instrument at the position where granule level actually changes.

  • If the granule load is large, mount an adequate guard plate.

  • Avoid mounting the instrument under the falling point of granules as well as near the outlet.

  • Mount the unit using the Main unit mounting nut.
    When it is difficult to set or remove the wing in a hopper, use a flange (sold separately).

  • Do not push and insert wing shaft too hard.
    Insert it up to the point carefully, and then revolve it manually.

Wiring Precautions

Caution

  • This instrument has no built-in power switch and fuse.
  • It is necessary to install a power switch and fuse near the instrument.
    (Recommended fuse: Time-lag fuse, rated voltage 250 V AC, rated current 2 A)

Operation and Maintenance Precautions

Caution

  • Do not touch live terminals. This may cause electrical shock or problems in operation.
  • Turn the power supply to the instrument OFF before retightening the terminal or cleaning. Working on or touching the terminal with the power switched ON may result in severe injury or death due to electrical shock.
  • Use a soft, dry cloth when cleaning the instrument. (Alcohol based substances may tarnish or deface the unit.)
  • Do not strike or scratch it with a hard object or put pressure on it.

Name of Sections

Shinko LV-300 Level Switch-fig2

  1. Cover
  2. Case
  3. Main unit mounting nut
  4. Wing shaft fixing nut
  5. Detector wing
  6. Cabtyre cord
  7. Solderless terminal (ring type)

Mounting to Hopper

Site Selection and Precautions
Ensure the mounting location corresponds to the following conditions, and follow precautions below.

  1. A minimum of dust, and an absence of corrosive gases

  2. Few mechanical vibrations or shocks

  3. No exposure to direct sunlight, an ambient temperature of 0 to 55 (32 to 131 ) that does not change rapidly, and no icing

  4. Mount the instrument at the position where granule level actually changes.

  5. If the granule load is large, mount an adequate guard plate.

  6.  Avoid mounting the instrument under the falling point of granules as well as near the outlet.

  7. Mount the unit using the Main unit mounting nut.
    When it is difficult to set or remove the wing in a hopper, use a flange (sold separately).

  8. Do not push and insert wing shaft too hard.
    Insert it up to the point carefully, and then revolve it manually.

Mounting Examples
[Good example]

Shinko LV-300 Level Switch-fig3

For large loading
(Mount the guard plate when the granule loading is large.)

Shinko LV-300 Level Switch-fig4

[Bad example]

Shinko LV-300 Level Switch-fig5

Nut and flange mounting

Shinko LV-300 Level Switch-fig6

Mounting of Wing Shaft

Shinko LV-300 Level Switch-fig7

  • Insert the wing shaft up to the point where it can be inserted fully to the end position. When it is difficult to insert the wing shaft to the end, revolve the wing shaft manually clockwise or counterclockwise. See (Fig.2.3-2).
  • Tighten the wing shaft with the fixing nut. See (Fig.2.3-3).

Notice: Tighten the Wing shaft fixing nut and Main unit mounting nut with the specified torque as shown below, otherwise the screws will be damaged.

| Appropriate Torque| Maximum Torque
---|---|---
Wing shaft fixing nut| 15 N•m| Within 30 N•m
Main unit mounting nut| 20 N•m| Within 30 N•m

External Dimensions (Scale: mm)

Shinko LV-300 Level Switch-fig8

Detector Length (L) Mounting Direction
85 mm
100 mm
150 mm
200 mm Vertical mounting
250 mm Vertical mounting

Hopper Cutout (Scale: mm)

Terminal Arrangement

Warning

  • Turn the power supply to the instrument OFF before wiring and checking.
  • Working on or touching the terminal with the power switched ON may result in severe injury or death due to electrical shock.

Caution

  • This instrument has no built-in power switch and fuse.
  • It is necessary to install a power switch and fuse near this instrument.
    (Recommended fuse: Time-lag fuse, rated voltage 250 V AC, rated current 2 A)
Terminal Code Lead Wire Color
A White
C Orange (Yellow)
1 Black
2 Brown
3 Green

Solderless terminal for the cabtyre cord
Use a solderless terminal (ring type) in which an M4 screw fits as shown in (Fig. 3-1).

Operation and Action

Operation
When mounting to the hopper and wiring are completed, check the action as follows.

  1. Turn the power supply to this instrument ON.
  2. Detector wing starts to revolve with no load.
    • Between terminals 1 and 2 : Conductive
    • Between terminals 2 and 3 : Open
  3. When the load is added to the detector wing, the wing stops rotating. Between terminals 1 and 2 : Open
    Between terminals 2 and 3 : Conductive

Action Explanation

  • When granule resistance is applied to the detector wing, the wing stops because the granule resistance keeps it from revolving.
  • Micro switch between terminals 2 and 3 for internal load is conducted by the bar fixed on the motor.
  • When the granule resistive load is given, power supply for the motor is disconnected because the micro-switch for the motor operates.
  • When the granule level lowers, the detector wing is exposed, granule resistance does not work and the detector wing starts to revolve with the motor.
  • Micro switch between terminals 1 and 2 for internal load is conducted at this time.

 Specifications

  • Name: Level switch
  • Model: LV-300
  • Torque: Detecting torque: 0.049 N•m (0.5 kg•cm) minimum (fixed)
  • Number of revolution: 1 min-1 (60Hz)
  • Power supply voltage: 100 V, 110 V, 115 V, 200 V, 220/230 V, 240 V AC (Must be specified) 50/60 Hz
  • A llowable voltage fluctuation range: 15% of the power supply voltage
  • Contact capacity: 3 A 250 V AC (resistive load)
  • Ambient temperature: 0 to 55
  • Detector length: 85, 100, 150, 200, 250 mm (Must be specified)
  • Mounting: Nut screwing (Mounting part thickness: Maximum 7 mm)
  • Material:
    • Case, Cover: Aluminum die-cast
    • Detector shaft : Stainless steel, 8.0 mm
    • Detector wing: Stainless steel, t1.5 mm
  • Lead wire: 5-core cabtyre cord, Length: 2 m
  • Weight (Including cabtyre cord 2 m):
    Detector

Length

| 85 mm| 100 mm| 150 mm| 200 mm| 250 mm
---|---|---|---|---|---
Weight| Approx. 645 g| Approx. 650 g| Approx. 670 g| Approx. 690 g| Approx. 710 g

  • Color: Case, Cover: 7.5BG4/2.5 (Munsell value)
  • Drip-proof/Dust-proof structure: IP66 (excluding parts from the Main unit mounting nut to detector wing)