JONES STEPHENS PEXALGAS Gas Piping System Installation Guide
- August 12, 2024
- JONES STEPHENS
Table of Contents
JONES STEPHENS PEXALGAS Gas Piping System
Product Information
The Jones Stephens Gas multilayer system combines the positive features of crosslinked polyethylene PEX-b and aluminum. PEX-b offers excellent mechanical, physical, and chemical properties while the butt-welded aluminum pipe enhances mechanical resistance, flexibility, and malleability for easy installation. This product is composed of different layers of material, connected to each other, allowing for excellent properties that wouldn’t be possible with a single material pipe.
Specifications:
- Working Pressure: Up to 72 psi
- Material: Multilayer system combining crosslinked polyethylene PEX-b and aluminum
Product Installation Instructions
- Design and Installation: Design and install the system according to the requirements provided in the guide. Use only Jones Stephens piping components as specified.
- Compliance: Follow local codes or National Fuel Gas Code ANSI Z223.1 in the USA, and CAN/CGA – B149.1 & B149.2 in Canada. Local code takes precedence in case of conflicts unless approved by the local authority.
- Inspection and Testing: Perform inspection, testing, and purging according to National Fuel Gas Code ANSI Z223.1, CAN/CGA – B149 installation Codes, or local codes.
- Underground Installation: When burying underground, lay pipes at least 3 feet away from waste pipes and above them. Use an appropriate bedding and cover with at least 8 inches of fine sand or strained clay.
- Piping Handling: Unwind and route piping carefully without kinking, tangling, or applying excessive force. Cap piping end before installation to prevent contamination.
- Precautions: Avoid sharp bends, stretching, kinking, twisting, or contact with sharp objects during installation. Replace tubing if damage occurs.
FAQ:
-
Q: Can components from other PEX-AL-PEX systems be used with Jones Stephens piping?
A: No, only Jones Stephens piping components should be used as they are not interchangeable with components from other systems. -
Q: What is the maximum working pressure for the Jones Stephens Gas Piping system?
A: The system is certified for working pressures up to 72 psi. Contact Jones Stephens at 800.355.6637 or visit jonesstephens.com for further assistance.
“`
PEXALGAS®
Installation Instructions English
Jones Stephens PEXALGAS® Installation Instructions
AT TENTION!
The installation of Jones Stephens PEXALGAS® piping must be performed by a
trained installer as required by the state and local administrative authority
administering the provisions of the code where the gas piping is installed.
All systems using Jones Stephens piping shall be designed and installed
according to the requirements of this guide.
Only Jones Stephens piping components may be used in the system. Components
from other PEX-AL-PEX systems are not interchangeable. Only components
supplied or specified by Jones Stephens shall be used.
Installation shall be in accordance with local codes, or in their absence, in
accordance with the National Fuel Gas Code ANSI Z223.1 in the USA, and CAN/CGA
– B149.1 & B149.2 in Canada. In cases where the requirements of this guide
conflict with the local code, the local code must take precedence, unless the
local authority having jurisdiction approves a variance, or change.
Inspection, testing, and purging shall be performed according to the
procedures in Part 4 of the National Fuel Gas Code, ANSI Z223.1, and CAN/CGA –
B149 installation Codes or in accordance with local codes.
This system and related components (pipes, fittings, and tools included in the
Jones Stephens PEXALGAS® catalog) shall be used only in gas piping systems
where the operating gas pressure does not exceed 72 psi (5 bar).
Piping may be buried underground. Underground pipes must be laid at a distance
of at least 3 feet from any waste pipes and they must be positioned above the
same. The piping does not require any protection in particular when laid
underground, as long as an appropriate bedding is prepared for the pipes and
the same are covered with a layer of at least 8 inches of fine sand or
strained clay.
Jones Stephens does not recommend the burial of brass fittings, but if the
fittings are installed in particularly moist conditions, embedded in soil, or
subject to particularly aggressive compounds (such as concrete or cement
mortars) they need to be protected. In such cases, the installer shall cover
the fittings with self-joining bituminous tape. The installation of Jones
Stephens PEXALGAS in solid floor should be in accordance with IRC sections
G2415.8.1 and G2415.8.2, IFGC sections 404.8.1 and 404.8.2. Tracer wire shall
be installed adjacent to the underground piping in accordance with IRC section
G2415.17.3, IFGC section 404.17.3. Underground pipes that enter the building
must be fitted with a sealed sleeve at the end, in order to prevent water, gas
and animals from entering the building.
The PEXALGAS® pipe is typically routed: · Beneath, through and alongside floor
joists · Inside interior wall cavities · On top of ceiling joists in attic
space
The PEXALGAS® pipe does not have a fire rating for runs through plenums that
is required by most building codes. If your building code requires products to
have a certain rating established by the ASTM E84 testing specification, then
PEXALGAS® shall not be installed through a plenum.
Carefully unwind and route the piping from the reel to the required location,
making certain not to kink, tangle or apply excessive force.
Piping end must be temporarily capped closed prior to installation to prevent
contamination from foreign material.
When installing Jones Stephens gas piping avoid sharp bends, stretching,
kinking, twisting, or contacting sharp objects. The tubing shall be replaced
if damage occurs.
800.355.6637 jonesstephens.com
1
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
IMPORTANT – READ ENTIRE MANUAL
This document is the sole property of Jones Stephens. It shall not be copied
or reproduced without the prior permission of Jones Stephens.
INTRODUCTION
USER WARNINGS
The use of fuel gas can be dangerous. Special attention must be given to the
proper design, installation, testing and application of the gas piping system.
Sound engineering practices and principles must be exercised, as well as
diligent adherence to the proper installation procedures to ensure the safe
operation of the piping system. All installed systems must pass customary
installation inspections by the local building official have authority prior
to being placed into service. This document is intended to provide the user
with general guidance when designing and installing a Jones Stephens piping
system, its use with any other gas tubing system is inappropriate and may
result in serious bodily injury and property damage. When local gas or
building codes impose greater requirements than this document, you should
adhere to the local code requirements. Performance of accessory devices, such
as pressure regulators and shut off valves, should be reconfirmed by
contacting the accessory device manufacturer and receiving the latest
technical data on sizing, installation, and performance.
Improper installation methods or procedures could lead to accidents such as
explosions, fires, gas poisoning, asphyxiation, etc. This system shall be
installed with strict adherence to this guide as well as local building codes.
All installed systems must pass installations inspections by the authorized
local building official prior to being placed into service. Jones Stephens
shall have no responsibility for any misinterpretation of the information
contained in this manual or any improper installation, repair work, or
deviation from the procedures recommended in this manual, whether pursuant to
local building codes or engineering specifications.
Jones Stephens piping components shall not be used with other PEX-AL-PEX
piping systems from other manufacturers.
Jones Stephens piping shall be used only in gas piping systems where the
operation gas pressure does not exceed 72 psi (5 bar). Accessories for systems
shall be rated for the operating gas pressure used. Thus, for example,
accessories for 25 psi systems shall be rated for 25 psi service. Performance
of accessory devices, such as pressure regulators and shut-off valves should
be reconfirmed by contacting the accessory device manufacturer and receiving
the latest technical data on sizing, installation, and performance.
800.355.6637 jonesstephens.com
2
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
A gas delivery system consisting of Jones Stephens piping offers significant
advantages over other gas delivery systems because of its wall dimensions and
design. In contrast to copper or rigid steel pipe, Jones Stephens piping does
not require intermediate joints in most installations because the piping is
capable of being installed in one continuous run, reducing not only the total
number of joints, but also the potential for leaks at joints. Jones Stephens
piping’s flexibility also affords more installation options because an
installer can avoid existing obstacles, and it eliminates repetitive
measuring, cutting, threading and joint assemble that are common with rigid
piping systems. Jones Stephens piping’s flexibility offers further safety
advantages in geographic areas that are prone to seismic activity because the
tubing provides greater flexibility to withstand certain movement of the
ground or structural shifts. Jones Stephens fittings are insulated to
eliminate metal to metal contact between pipe and fittings. To maximize
protection of the entire structure from lightning damage, installation of a
lightning protection system shall be installed per NFPA 780 and other
standards, particularly in areas prone to lightning. Note that lightning
protections systems set forth in NFPA 780 and other standards go beyond the
scope of this manual. Users of Jones Stephens piping systems shall consider
all the limitations and benefits of Jones Stephens piping systems for their
particular situation.
LIMITATION OF MANUAL
This document is intended to aid the user in the design, installation and
testing of Jones Stephens piping systems to distribute fuel gas in residential
housing units and commercial structures. It would be impossible for this
guideline to anticipate and cover every possible variation in housing
configuration, appliance loads and local restrictions. Therefore, there may be
applications which are not covered in this manual. For applications beyond the
scope of this guide, contact Jones Stephens. The techniques included within
this guide are recommend practice for generic applications. These practices
must be reviewed for compliance with all applicable local fuel gas and
building codes. Accordingly, where local gas or building codes impose greater
requirements than this manual, you should adhere to the local code
requirements. This system and related components (pipes, fittings, and tools
included in the Jones Stephens PEXALGAS® catalog) should only be used as fuel
gas piping where the operation gas pressure does not exceed 72 psi (5 bar).
LISTING OF APPLICABLE CODES AND STANDARDS
Jones Stephens Gas Piping System complies with the following codes: · 2021,
2018, 2015, 2012 and 2009 International Fuel Gas Code® (IFGC) · 2021, 2018,
2015, 2012 and 2009 International Residential Code® (IRC) · 2021, 2018, 2015,
2012 and 2009 Uniform Plumbing Code® (UPC)
Jones Stephens Gas Piping System complies with the following standards as
certified by the ICC-ES PMG-1588 certificate:
· ASTM F1281 Standard Specification for Cross-linked Polyethylene/Aluminum
/Cross-linked Polyethylene
· ISO17484 Specification for Multilayer pipe systems for indoor gas
installations
· AS 4176.8-2010 Metal-Plastic Multilayer Pipes and Brass Fittings for
Conveying Combustible Gases in Systems in Pressure up to 5 bar
800.355.6637 jonesstephens.com
3
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
DESCRIPTION OF SYSTEM AND COMPONENTS
Piping
The Jones Stephens PEXALGAS® Gas Piping System has been engineered, tested,
and certified to meet the performance requirements of American Fuel Gas
systems. As such is acceptable for use with all recognized fuel gases,
including natural gas and propane (LPG).
The Jones Stephens Gas multilayer system combines the positive features that
are typical of crosslinked polyethylene PEX-b and also those of aluminum;
crosslinked polyethylene PEX-b offers excellent mechanical, physical and
chemical properties and the butt-welded aluminum pipe strengthens mechanical
resistance introducing excellent characteristics of flexibility and
malleability, fundamental features for accelerating and simplifying
installation operations.
The result is a product that is composed of different layers of material,
connected to each other, that allows excellent properties to be reached that
otherwise would not be possible with a pipe made of one single material.
The Jones Stephens Gas Piping system is certified for systems with working
pressures up to 72 psi.
Attention: Do not store or install PEXALGAS® exposed to direct sunlight.
Fittings
Jones Stephens Crimp Fittings is a system of crimp fittings suitable for a
variety of applications. By using a portable crimping machine equipped with a
suitable jaw, the pipe is shaped around the fitting insert. Even in the
presence of temperature fluctuations, the joint remains perfectly gastight and
cannot be loosened thanks to the stainless-steel sleeve that covers the
portion of pipe in contact with the insert. The sleeve has inspection holes to
verify the correct insertion of the pipe on the fitting.
The PEXALGAS® Crimp Fittings require the use of Jones Stephens approved
PEXALGAS® crimping jaws or the Jones Stephens PEXALGAS® manual crimper,
designed specifically for Jones Stephens PEXALGAS® systems.
Protection Devices:
Protective devices are to be used when piping passes through studs, joists, or
other building materials that limit or restrict the movement of the flexible
piping making it susceptible to physical damage from nails, screws, drill bits
and other puncture threats. · Striker plates (hardened steel Gauge 16) to be
attached directly to studs and joists. · Strip wound metallic conduit shall be
used in locations where additional protection may be required.
Pressure Regulators:
Required to be used to reduce elevated pressure, over 14 inches water column
(1/2 PSI), to standard low pressure required for most appliances.
800.355.6637 jonesstephens.com
4
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
DESCRIPTION OF SYSTEM AND COMPONENTS
Manifolds:
· Multiport gas distribution manifolds supply multiple gas appliances in
parallel arrangement from a main distribution point.
· Multiple sizes and configurations ranging in female NPT sizes ½ through 2
with 3, 4 and 6 port cross manifold configurations.
Shutoff Valves
Used to control the gas flow. Ball valves shut off the gas supply at
appliances, manifolds, & regulators. Valves can be utilized at manifold
locations reducing the number of joints due to the integrated fitting
connection.
SYSTEM OVERVIEW
INTRODUCTION:
The following section will be used to assist you while you design and size
your Jones Stephens Gas multilayer system. At any point in which you require
further assistance with this process you can visit our webpage
(jonesstephens.com) or contact Jones Stephens.
It is required by this standard to provide installation instructions which
include proper sizing tables and methods of sizing.
SYSTEM DESIGN
In order to properly design a fuel gas piping system, you must first recognize
all the important criteria. Requirements for a proper system design include: ·
Verify your system meets all local codes. When local codes conflict with the
manufactures guidelines the local
codes must always take precedence. · Determine the supply pressure coming from
the meter by means of a gauge or a rating supplied by the gas company. ·
Determine your total system demand for all appliances as well as the largest
single load. · Prepare a floor plan sketch with the load and length
combinations for all appliances. · Determine your allowable pressure drop.
NOTE:
Please note that Jones Stephens sizing tables refer only to the pipe without
including any other losses. Sizing must be done in accordance with NFPA 54
(National Fuel Gas Code), using the pressure losses from both the PIPE and the
FITTINGS sizing tables to allow a more accurate sizing of the system for your
installation.
When choosing a pressure drop to size a Jones Stephens Gas multilayer system
the minimum operating pressure of the appliance must be considered. Choosing a
pressure drop that will reduce the supply pressure below the minimum operating
pressure of the appliance will cause the appliance to perform poorly or not at
all.
800.355.6637 jonesstephens.com
5
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
GENERAL INSTALLATION PRACTICES
ATTENTION:
JONES STEPHENS PEXALGAS® GAS PIPING SYSTEM IS AN ENGINEERED FUEL GAS PIPING
SYSTEM AND AS SUCH, THE TUBING AND FITTINGS ARE NOT INTERCHANGEABLE WITH OTHER
PEX-AL-PEX MANUFACTURER’S PRODUCTS. THE USE OF OTHER PEX-AL-PEX PRODUCTS WITH
THE JONES STEPHENS GAS PIPING SYSYEM IS PROHIBITED.
A. All System hardware should be stored in its original package in a clean dry
location prior to installation. Care must be taken to ensure the PEXALGAS®
piping is not damaged prior to installation.
B. Piping ends must be temporarily capped or plugged prior to installation to
prevent dirt or other foreign debris from entering the tubing.
C. PEXALGAS® piping exposed to extreme low temperatures shall be allowed to
come up to room temperature prior to installation and all the related
activities such as uncoiling, bending, cutting, chamfering, and/or connecting
to fittings. Once installed, PEXALGAS® piping is able to withstand low
temperature conditions, down to -40°F (-40°C).
D. Care must be taken to not kink, tangle, twist, stretch or apply excessive
force to the piping or fittings. The Jones Stephens Gas Piping is a flexible
piping system and can be bent during installation around obstructions. Avoid
stressing the tubing with tight bends. Refer to the table for the recommended
bend radius.
PIPE SIZE (mm)
16
20
26
32
PIPE SIZE (in)
3/8
1/2
3/4
1
MINIMUM BEND RADIUS
2″
3″
3″
5″
E. When installing in, through or around sharp metal structures (i.e. metal
studs, sheet metal, I-beams), rubber grommets or protective tubing should be
used to prevent any direct contact which could subject the piping to damage.
F. Tubing should be supported in a workman like manner with metallic pipe
straps, bands, brackets, hangers or building structural components suitable
for the size of piping support intervals are not to exceed those shown in the
table below (see table under the Horizontal Run section on page 9). A proper
support is one which is designed to be used as a pipe hanger, does not damage
the piping during installation, and provides full support of the
tubing once installed. Plastic zip ties or cable ties are not to be used as
the primary support for the PEXALGAS® tubing.
800.355.6637 jonesstephens.com
6
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
FITTING ASSEMBLY
1. Cut the pipe at a right angle using a suitable pipe cutter. Check the
tidiness and the sharpening of the blade to avoid any ovalization or damage to
the pipe.
2. Calibrate and chamfer the pipe to obtain a perfectly round inner
circumference of the pipe. Always make sure that the reamer has no dents or
damage as they would damage the pipe and compromise the seal.
3. Insert the fitting on the pipe checking through the sleeve inspection
holes that the pipe has been properly inserted. Remove any residual material
left inside the pipe.
800.355.6637 jonesstephens.com
7
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
4. For crimp machines: Position the crimping machine so that the crimping jaw
is aligned and in position with respect to the body of the fitting and tighten
by pressing the start button on the crimping machine (for more details refer
to the instructions supplied with the crimping machine). Use crimping jaws
provided by Jones Stephens whose crimping profile (TH) is compatible with the
fitting that you are installing.
For manual crimper: position the manual crimper so that the crimping jaw is
aligned and in position with the respect of the body of the fitting and close
the tool completely until it clicks (for more details refer to the
instructions supplied with the tool).
5. Remove the crimping jaw and verify through the metal sleeve inspection holes that the pipe has remained fully inserted during the whole connecting process.
NPT Threaded Connections
Use Teflon (PTFE) tape or pipe thread sealants is acceptable if needed. Wrap
PTFE tape clockwise 3-4 times. Apply thread sealant starting at the opening of
the fitting that is significantly thick enough to fill the grooves of the
first half of the thread only. The proper method of assembling tapered
threaded connectors is to assemble them finger tight and then wrench tighten
further to the specified number of turns from finger tight (T.F.F.T.) given in
the table. Tightening torque should not exceed the values listed in the table
below.
CONNECTION SIZE (NPT)
1/2″ 3/4″ 1″
T.F.F.T.
2-3 2-3 1.5-2.5
MAXIMUM TORQUE (ft-lb)
30 37 52
Do not use Teflon tape or thread sealant on any Jones Stephens PEXALGAS® crimp connections. Ensure thread sealant does not contact pipe or remain inside the fittings.
800.355.6637 jonesstephens.com
8
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Floor/Wall Mounting Fittings
When using the Jones Stephens Wall/Floor Mounting fittings it is necessary to
drill an adequately sized hole using a hole saw. Please reference the table
below to choose the proper hole saw for the fitting being used.
FLOOR/WALL MOUNTING FITTING 16 mm x 1/2″ 20 mm x 1/2″ 20 mm x 3/4″ 26 mm x 1″ 26 mm x 3/4″ 32 mm x 1″
HOLE SAW SIZE 7/8″ (22mm) 1-1/8″ (29mm) 1-1/8″ (29mm) 1-3/8″ (35mm) 1-3/8″ (35mm) 1-3/4″ (44mm)
TUBING ROUTING
VERTICAL RUNS
Vertical runs inside hollow wall cavities are the preferred location for
installation of vertical sections. To avoid damage, tubing should be free to
move within the wall cavity without immediate supports between floors but must
be supported at the point of penetration between floors. Vertical run support
spacing is not to exceed 10 feet, requiring hangers only where the height of
each floor is greater than 10 feet. The run must conform to Section x
Protection, if it is installed in a location that it will be concealed.
HORIZONTAL RUNS
Areas beneath, alongside, or through floor and ceiling joists or other
structural members are typical installation locations for both residential and
commercial applications. Structural members may be considered supports for
horizontal tubing if they meet the requirements as specified in the table
below. The run must conform to Protection Section of this manual, if it is
installed in a location that it will be concealed.
PIPE SIZE (mm)
16
20
26
32
PIPE SIZE (in)
3/8
1/2
3/4
1
MINIMUM HANGER SPACING
40″ 50″ 60″ 80″
Expansion/Contraction of Piping
The coefficient of linear expansion of PEX-AL-PEX is 0.00017 in / ft * °F).
The hangers use the flexibility of the pipes to accommodate the expansion and
contraction of the straight lengths of pipe of the Jones Stephens PEXALGAS®
system. Use of rigid clamps require accommodation for liner expansion and
contraction of pipe. There are several techniques that can be used.
800.355.6637 jonesstephens.com
9
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Preliminary considerations
All materials are subject to expansions or contractions, which are caused by
the increase or decrease in temperature. The variation in length L of a pipe
of length L caused by a variation in temperature T between the temperature at
which the pipe was installed and the current temperature is given by:
L = · L · T
where, is the coefficient of linear heat expansion of the material. The
following figure can be used to calculate the expansion or contraction of a
pipe in relation to the difference in temperature to which it is subjected.
The prevention of such a variation in length in the material would generate a
tensile stress (with T<0) or a compression stress (with T>0) given by:
= E · · T
where, E is the modulus of elasticity of the material. When calculating
expansions or contractions, the difference between the temperature at which
the pipe was (or will be) installed and the maximum/minimum temperature
expected when the system is operating, must always be taken into
consideration.
The coefficient of linear expansion of PEX-AL-PEX is 0.00017 in / ft * °F).
800.355.6637 jonesstephens.com
10
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
The effects of heat expansion and contraction of plastic materials influence
the methods of installation of gas supply systems, which require different
rules according to the type of installation chosen (refer to the following
sections for further details).
Example: Calculate the linear heat expansion of a 26 ft PEXALGAS® pipe that is
installed at a temperature of 50°F and is subject to a maximum temperature of
160°F.
By using the formula previously given and considering the heat expansion
coefficient of PEX-AL-PEX, we have: L= · L · T = 0.00017 · 26 · (160-50) =
0.49 in
Compensation using a flexible arm (Type L)
This type of compensation avails of the changes of direction of the pipes; the
segment of pipe (flexible arm) of length LB accommodates the movement as a
result of the thermal expansion of a segment of pipe of length L perpendicular
to it. In this case, the correct distance of the pipe from the walls must be
guaranteed to allow the movement, it is therefore necessary to install the
brackets according to the structure of the flexible arm.
The length of the flexible arm LB [in] is calculated using the formula:
LB = C · De · L
where C is the material constant, which for PEXALGAS® pipes is 33, De is the
diameter of the pipe [in] and L is the change in length of the segment of pipe
to be accommodated.
800.355.6637 jonesstephens.com
11
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Example: Calculate the length of the flexible arm of a PEXALGAS® pipe with a
diameter of 1″ (32 mm) and a length of 160 ft that is installed at a
temperature of 70°F and subject to a maximum temperature of 130°F.
The thermal expansion of the section of pipe is:
L = L T = 0.00017 160 (130 – 70) = 1.63 in
and, using the formula, the deflection arm LB is calculated: LB = C · De · L =
33 · 1.26 · 1.63 = 47.29 in 47.29 in = 3.94 ft
The same flexible arm (LB) is subject to a heat expansion of: L’ = LB T =
0.00017 3.94 (130 – 70) = 0.04 in
and requires therefore that part of the main pipe section is free to
accommodate this expansion, the arm that is free to expand is:
L’B = C · De · L’ = 33 · 1.26 · 0.04 = 7.41 in
Compensation using flexible arm misalignment (Type Z)
This type of compensation avails of a misalignment of the pipe; the section of
pipe (flexible arm) of length LB accommodates the expansions of the pipe of
length L perpendicular to it.
The distance between the flexible arm and the brackets must not be shorter
than the length of the flexible arm L.
The length of the flexible arm LB [mm] is calculated using the formula:
LB = 0.65 · C · De · L
where C is the material constant, which for Jones Stephens multilayer pipes is
33, De is the pipe diameter [in], and L is the change in length of the segment
of pipe to be accommodated.
800.355.6637 jonesstephens.com
12
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Example: Calculate the length of the flexible arm misalignment of a PEXALGAS®
pipe with a 3/4″ (26 mm) diameter and a length of 130 ft installed at a
temperature of 50°F and subject to a maximum temperature of 120°F. The heat
expansion of the section of pipe is:
L = L T = 0.00017 130 (120 – 50) = 1.55 in and, using the formula, the
deflection arm LB is calculated:
LB = 0.65 · C · De · L = 0.65 · 33 · 1.02 · 1.55 = 26.97 in
“Omega” Expansion Bend (Type U)
This type of compensation is generally employed in risers or in basement
collectors when the expansions cannot be accommodated by the changes in
direction of the pipes. Whereas in the case of deflection arm compensation,
changes in direction of the system are used, in this case the configuration
must be created especially.
The total length of the “omega” expansion bend LB [mm] is calculated using the formula (also shown in the following diagram):
LB = 2 · l1 + l2 = C · De · L
where, C is the material constant, which, for Jones Stephens multilayer pipes
is 33, De is the pipe diameter [in], L is the change in length of the pipe
section to be accommodated, l1 and l2 are the sides of the “omega” expansion
bend. The “omega” compensation must be configured depending on the available
space; however, where possible, it is recommended to maintain the following
dimensional ratio:
and therefore:
l1 = 2 l2
l1 = 0.4 LB l2 = 0.2 LB
800.355.6637 jonesstephens.com
13
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Example: Calculate the “omega” expansion bend for the PEXALGAS® pipe section
of diameter 1″ (32 mm) and 82 ft length, installed at a temperature of 60°F
and subject to a maximum temperature of 150°F. The thermal expansion of the
pipe section is:
L = L T = 0.00017 82 (150 – 60) = 1.25 in
and, using the formula, the total length is calculated for the “omega” LB: LB
= C · De · L = 33 · 1.26 · 1.25 = 41.49 in
and considering the dimensional ratio suggested, the result is: l1 = 0.4 LB =
0.4 41.49 = 16.6 in l2 = 0.2 LB = 0.2 41.49 = 8.3 in.
800.355.6637 jonesstephens.com
14
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Example: Calculate the flexible arms for the gas supply system indicated in
the figure created with PEXALGAS® pipe, installed at a temperature of 50°F and
subject to a maximum temperature of 140°F.
LB4
L = 10 ft
LB2
L = 20 ft
L = 10 ft
LB3
LB5
L = 2 ft
LB1 The pipe sections LB3 and LB5 are not subject to flexure due to the anchor
point (F) near the cross branch. The sections subject to flexure are: LB1
which represents the flexible arm of section L1, LB2 which represents the
flexible arm of L2, LB4 which represents the flexible arm of L4 = L2 + L3.
800.355.6637 jonesstephens.com
15
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English L4
L2
L1
The extensions of the above mentioned sections are:
L1 = L1 T = 0.00017 2 (140 – 50) = 0.03 in L2 = L2 T = 0.00017 10 (140 – 50) =
0.15 in L4 = L4 T = 0.00017 20 (140 – 50) = 0.31 in which correspond to the
following flexible arms:
LB1 = C · (De1 · L1) = 33 · (1.26 · 0.03) = 6.42 in LB2 = C · (De2 · L2) = 33
· (1.26 · 0.15) = 14.35 in LB4 = C · (De4 · L4) = 33 · (1.02 · 0.31) = 18.56
in
800.355.6637 jonesstephens.com
16
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Example: The figure shows a shaft in which a riser has been installed, subject
to a thermal expansion near the branch of 20 ft.
Assess whether the change in direction made with a 1/2″ (20 mm) PEXALGAS®
pipe, is sufficient to accommodate such an expansion, keeping the geometries
indicated in the figure in consideration.
12 in
From the figure we can see that the available space for creating a flexible
arm is L=12 in, which is the distance between the wall, through which the
change in direction passes, and the riser. You need to ensure that this
distance is sufficient to allow the pipe to flex without it being damaged, it
is therefore necessary to calculate the actual length of the flexible arm and
assess whether this is less than the available space.
At the point indicated, the expansion L = 0.25 in, the length of the actual
flexible arm is therefore:
LB = C · De · L = 33 · 0.79 ·0.25 = 14.7 in > 12 in
Greater space is required to give the pipe sufficient room for movement;
however, if the Jones Stephens multilayer pipe is installed with insulation
where it passes through the wall, this could be capable of absorbing part of
the flexure that the pipe exerts inside the wall itself. It is possible to
calculate approximately the extent of the movement of the pipe inside the wall
to verify whether the insulation can absorb the movement.
800.355.6637 jonesstephens.com
17
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Lp = L (LB- L )/LB = 0.25 2.7 / 14.7 = 0.046 in
800.355.6637 jonesstephens.com
18
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
PROTECTION
INTRODUCTION
Jones Stephens piping shall be protected from physical damage caused by
screws, nails, drill bits, etc. The piping is most susceptible to puncture at
all points of support. The best practice is to install the piping in those
areas where the likelihood of physical damage is minimized, and no protection
is needed; for example: A. Where piping is supported at least 3 inches from
any outside edge of a stud, joist, etc. or wall surface. B. Where any
unsupported piping can be displaced in the direction of potential penetration
at least 3 inches. C. Where piping is supported under the joist in basements
or crawl spaces and is not concealed by wall board or
ceilings. When Jones Stephens piping is installed in locations where the
potential of physical damage exists, the use of Striker Plates, listed for gas
piping, must be used. The tubing may also be routed inside strip wound conduit
or schedule 40 pipe when protection is required. In areas where penetration
through studs, joists, plates, and other similar structural members occur
striker protection is required when all of the following criteria apply: 1.
When the piping system is installed in a concealed location and is not
viewable. 2. When the piping system is installed in a location that does not
allow free movement to avoid puncture threats. 3. When the piping system is
installed within 3 inches of possible points of penetration.
STRIKER PLATES
Striker plates are used to prevent piping damage in areas where potential
penetration threats exist through studs, joists, plates, and other similar
structural members. For installations where all three above criteria apply,
PEXALGAS® tubing must be adequately protected from risk of puncture or
physical damage at all points of penetration through studs, joists, plates, or
similar structures using 16 gauge hardened steel striker plates in accordance
with the requisite state and/or local fuel gas code.
800.355.6637 jonesstephens.com
19
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
A. At concealed support points and points of penetration less than 2 inches from any edge of a stud, joist, plate, etc. shielding is required at the area of support and extending 5 inches in one or both directions (if appropriate).
5 in.
Full
Support
Striker Plate
5 in.
Unrestrained Vertical
26
in.
Run
Adequate Escape Allowance
Nail, Puncture-Safe Non-Restricted Length
5 in.
< 2 in.
Support
3 in.
Half Striker Plate
800.355.6637 jonesstephens.com
20
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
B. At concealed support points and points of penetration within 2 to 3 inches from any stud, joist, plate, etc., listed quarter striker plates are required at the area of support.
Floor
3″
= or <24″
Ceiling/Floor Joist
2″ to 3″
Ceiling
Quarter Striker Plate
C. Piping routed horizontally through structural members shall be protected from puncture threats with the appropriate shielding material. At penetration joints, listed stud guards of the appropriate size shall be utilized. Piping between constraints that are less than 24 inches apart and meeting the criteria requiring full striker plates, shall be additionally protected by stripwound metal-conduit, or schedule 40 pipe.
Floor
3″
24″
= or <24″
Ceiling/Floor Joist
< 2″
Ceiling
Full Striker Plate
Steel Conduit
D. Piping greater than 32 mm nominal diameter (26 mm internal diameter)
installed within a concealed hollow wall cavity of 2″ x 4″ construction shall
be protected along the entire concealed run length with stripwound metal
conduit, or schedule 40 pipe.
E. Should an unfinished ceiling (I.e. basement) be covered at a later date,
quarter striker plates should be replaced with appropriate protection devices
that provide adequate protection for potential penetration threats.
800.355.6637 jonesstephens.com
21
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
STRIPWOUND METAL CONDUIT
A. At termination points not covered by ANSI specifications, stripwound metal
conduit (heavy wall) shall be installed as additional protection.
B. Strip wound metal conduit shall also be used to shield piping from puncture
threats when the piping is installed in a concealed location where it cannot
be displaced a minimum 3″ from a potential puncture threat or the distance
between supports is less than 24 inches.
INSTALLATION IN INSULATED WALLS
Rigid installations present significant puncture threats for Jones Stephens
PEXALGAS® in concealed spaces.
In concealed spaces, e.g. wall cavities, rigid insulation will prevent
PEXALGAS® from being displaced. Jones Stephens piping shall not be installed
in a wall cavity with foam insulation without additional protection as
described below.
A. Piping shall be routed through an approved conduit in walls where “foamed
in” insulation is to be used i.e. rigid steel pipe or conduit. Approved
conduit shall be secured according to local building practice.
B. Protection methods such as pipe, conduit and strip wound hose, supply
protection and give the piping space in which to move. On exterior walls the
tubing may be fastened to the sheathing with cable clamps or secured with
sticks/wires sprung between studs to center tubing between interior and
exterior surfaces.
C. When piping is installed inside walls with batt insulation the tubing shall
be routed between the face (craft paper/vapor barrier) and the wall surface.
If installed in a concealed location where it cannot be displaced a minimum 3″
from a potential puncture threat the run shall be protected with stripwound
conduit.
D. Jones Stephens PEXALGAS® piping does not need additional protection where
it is more than three inches from any puncture threats although consideration
must be given to the chance that it may migrate toward penetration threats as
the insulation is applied and during curing.
FITTINGS PROTECTION
If the fittings are installed in particularly moist conditions, embedded in
soil, or subject to particularly aggressive compounds (such as concrete or
cement mortars) they need to be protected. In such cases, the installer shall
cover the fittings with self-joining bituminous tape.
800.355.6637 jonesstephens.com
22
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
METER-CONNECTIONS
UNSUPPORTED METERS
A. Meters which depend on the service and house piping for support shall not
be directly connected to the PEXALGAS®.
B. The use of an outdoor termination fitting mounted to the exterior of the
structure, meter stub out, other rigidly mounted termination fitting, or
transitioning to rigid black pipe are acceptable transitional methods.
SELF SUPPORTED METERS
A. Meters which are independently supported by a bracket shall not be directly
connected to the flexible gas piping. B. The use of an outdoor termination
fitting mounted to the exterior of the structure, meter stub out, other
rigidly
mounted termination fitting, or transitioning to rigid black pipe are
acceptable transitional methods.
APPLIANCE CONNECTIONS
MOVEABLE APPLIANCES
IMPORTANT: JONES STEPHENS PIPING AND FITTINGS ARE NOT RATED AS FLEXIBLE
APPLIANCE CONNECTORS AND MUST NOT BE DIRECTLY CONNECTED TO MOVABLE APPLIANCES.
A. When using Jones Stephens Gas piping with moveable appliances such as a
ranges or dryers, the piping must be
rigidly terminated before the appliance. Appliance stub outs, termination
fittings or transitioning to rigid black pipe are acceptable means to
terminate PEXALGAS® prior to the appliance.
B. Final connection from PEXALGAS® termination point to a movable appliance
shall be made with a flexible appliance connector or another approved
connection device.
NON-MOVEABLE APPLIANCE
A. Jones Stephens piping can be directly connected to a non-moveable appliance
such as a furnace or water heater (be sure to check with local code if this is
acceptable prior to installation).
B. In this type of application, no termination fitting is required, and the
piping should be terminated at the appliance shut off valve.
SPECIAL APPLICATIONS
Prolonged UV exposure due to direct sunlight is detrimental to all PEXALGAS®.
Jones Stephens PEXALGAS® shall not be installed exposed in direct sunlight.
For outdoor installations, special care must be provided that the PEXALGAS® is
not left exposed to sunlight and special care shall be made to protect the
piping system from accidental damage.
800.355.6637 jonesstephens.com
23
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
INFRARED HEATERS
Infrared heaters mounted from ceilings and walls of structures shall be
connected to the Jones Stephens gas piping system ANSI 383.6 “Standard for gas
fired infrared heaters”.
PAD MOUNTED GAS APPLIANCES
Gas appliances mounted on concrete pads or blocks, such as gas furnaces, air
conditioners, pool heaters and NGV refueling systems, shall be connected to
the Jones Stephens gas piping system at a termination fitting using either
rigid pipe or an approved outdoor appliance connector. Pad mounted equipment
(in most cases) is considered “fixed” if not moved for cleaning, maintenance,
etc. (i.e. A/C units).
GAS FIREPLACES
Attention: Jones Stephens Gas piping shall not be routed directly into a
metallic fireplace enclosure. The piping connection shall be made outside of
the enclosure to a section of rigid metallic pipe. A. When routing Jones
Stephens Gas piping through masonry construction, for connection to gas
fireplaces and gas
logs, the piping is required to be sleeved in a nonmetallic conduit through
the masonry structure. The annular space between the piping and sleeve should
be caulked at both the interior and exterior locations.
B. For any fireplace application where installation of Jones Stephens Gas
piping is desired, a Fireplace Stubout shall be used to terminate the piping
outside the enclosure. While other listed installation practices are
acceptable this method is preferred to prevent inadvertent damage, that can be
caused by the fireplace enclosure, to the PEXALGAS® system.
C. Adherence to local codes and manufacturer’s instructions are required, be
sure to know and understand all requirements prior to installation.
PRESSURE REGULATORS and VENT LINE INSTALLATION GUIDELINES
A Jones Stephens Gas piping system utilizing gas line pressures above ½ PSI
are required to use a line pressure regulator upstream of the appliances to
reduce the line pressure to less than ½ PSI. The regulator shall incorporate
construction which will “lock up” under no-flow conditions to limit the
downstream pressure to not more than 1/2 psi. The guidelines below highlight
requirements from most Fuel Gas Codes and are for your reference only. The
regulator shall comply with a nationally recognized standard for pressure
regulators. Installation of the regulator must be done in accordance with the
manufacturer’s instructions and local fuel gas code requirements.
Regulators used to reduce elevated system pressure for appliance use must also
conform to the following:
Sized to supply the required appliance load.
Equipped with an acceptable vent limiting device, supplied by the
manufacturer, or be capable of being vented to the outside atmosphere.
Installed in accordance with manufacturer’s printed instructions.
Installed in an accessible location.
A CSA Design Certified shutoff valve must be installed upstream of the
pressure regulator.
800.355.6637 jonesstephens.com
24
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
REGULATOR VENTING REQUIREMENTS
VENT LINES
Venting is required for all regulators to avoid a gas buildup in an enclosed
area in the event that the regulator diaphragm ruptures. Vent lines should be
properly sized per the manufacturer’s instructions and installed to ensure
proper operation.
VENT LINE INSTALLATION GUIDELINES:
The vent line shall not be smaller than the vent connected to the pressure
regulator.
The recommended minimum size vent line for the regulator is 1/4″ nominal ID
copper tubing or other approved material. The maximum length installed for
this size vent line should be less than 30 feet. Larger diameter vent lines
can be used if necessary. In determining the proper size vent line for a
particular installation, a test may be necessary with the vent line and
regulator under normal use to ensure proper regulator operation. Consult with
the regulator manufacturer for limitations of length and size of the vent
line.
The vent shall be designed and installed to prevent the entry of water,
insects or other foreign materials that could cause blockage.
Under no circumstances shall a regulator be vented to the appliance flue or
building exhaust system.
VENT LIMITER OPTION:
Vent limiters are an alternate venting option available some regulators. When
a vent limiter is desired all installation guidelines for the vent limiter and
regulator must be followed to ensure proper operation of the unit.
VENT LIMITER INSTALLATION GUIDELINES:
Regulators must be installed in the horizontal upright position and in a well-
ventilated area when using a vent limiter. Consult with local code before
installation.
Only a vent limiter supplied by the regulator manufacturer may be used, no
piping shall be installed between the regulator and vent limiting device.
Leak detection fluids may not be used on vent limiters as they can cause
corrosion and operational failure. Remove the vent limiter and check the vent
opening if a leaking diaphragm is suspected. Remember, regulators will
“breathe” when regulating, creating a bubble – A leak will blow bubbles
constantly. Do not leak test the vent limiter with liquid leak test solution.
This action will contaminate the internal ball check mechanism or plug the
breathing hole, resulting in erratic regulator operation.
Vent limiters shall not be used outside or anyplace where they are subject to
damage from the environment. Vent protection devices shall be used in outdoor
installations.
800.355.6637 jonesstephens.com
25
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
OVER PRESSURIZATION PROTECTION
Gas systems using pressures above 2 psi up to 5 psi must use OPD (Over
Pressure Protection Devices).
PRESSURE TESTING AND INSPECTION PROCEDURE
The final installation is to be inspected and tested for leaks at 1 1/2 times
the maximum working pressure, but not less than 3 psi, using procedures
specified in Chapter 7 “Inspection, Testing and Purging” of the National Fuel
Gas Code, NFPA 54/ANSI Z223.1. In Canada, refer to the applicable sections of
the CAN/CGA – B149 Installation codes.
Maximum test pressures recommended – 40 PSI MAX.
Do not connect appliances until after pressure test is completed.
Inspect the installed system to ensure: · Presence of listed stud guards and
other protective devices at all required locations. · Acceptable physical
condition of the tubing. · Presence of fittings (properly pressed). · Correct
regulator and manifold arrangement with proper venting requirements. · All gas
outlets for appliance connections should be capped during pressure testing. ·
Pressure testing should be performed during rough construction of the facility
(before interior walls are finished).
This will permit a more complete inspection of the piping system during the
pressure testing.
The elevated pressure system requires a two-part pressure test. · The first
part is performed on the elevated pressure section, between the meter
connection and the pressure
regulator. · The second part is performed on the low-pressure section, between
the pressure regulator and the individual
gas appliance outlets.
800.355.6637 jonesstephens.com
26
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
ELECTRICAL BONDING
Jones Stephens Gas piping system crimp fittings dielectrically isolate the metal fitting from the internal aluminum pipe layer. As such, there are no additional bonding requirements in this manual for the Jones Stephens Gas piping system in the same manner as the minimum requirements for rigid metal piping. However, installers must always adhere to any local requirements that may conflict with these instructions.
ALL OWNERS should consult a lightning safety consultant to determine whether
installation of a lightning protection system would be required to achieve
sufficient protection for all building components from lightning. Factors to
consider include whether the area is prone to lightning.
Lightning protection systems are beyond the scope of this manual and
installation guidelines, but are covered by National Fire Protection
Association, NFPA 780, the Standard for the Installation of Lightning
Protection Systems, and other standards.
Consult local building codes as to required separations for piping from such
continuous metallic systems including metallic chimney liners, metallic
appliance vents, metallic ducting and piping, and insulated or jacketed
electrical wiring and cables.
800.355.6637 jonesstephens.com
27
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
SIZING TABLES
Jones Stephens sizing tables reflect the real pressure drop of the pipe and
fittings. Sizing must be done in accordance with NFPA 54 (National Fuel Gas
Code), using both the TUBES and the FITTINGS sizing tables: using the pressure
losses from both the PIPE and the FITTINGS sizing tables :this allows a more
accurate sizing of the system for your installation.
Natural Gas <2psi
Working Conditions
Natural gas
–
–
Inlet Pressure
6″ WC
–
Pressure drop
0.300 WC [inch]
Imperial diam.
Pipe [mm] Length [ft] 5 10 15 20 25 30 40 50 60 70 80 90 100 150 200 250 300
350 400 450 500
3/8″
1/2″
3/4″
1″
16
20
26
32
Flow Rate Natural Gas [ft3/h]
97
206
370
737
67
142
254
506
54
114
204
407
46
97
175
348
41
86
155
308
37
78
140
279
31
67
120
239
28
59
107
212
25
54
97
192
23
49
89
177
22
46
83
164
20
43
78
154
19
41
73
146
15
33
59
117
13
28
50
100
12
25
45
89
11
23
40
80
10
21
37
74
9
19
35
69
8
18
32
65
8
17
31
61
800.355.6637 jonesstephens.com
28
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
SIZING TABLES
Natural Gas <2psi
Working Conditions
Natural gas
–
–
Inlet Pressure
6-7″ WC
–
Pressure drop
0.500 WC [inch]
Imperial diam.
Pipe [mm] Length [ft] 5 10 15 20 25 30 40 50 60 70 80 90 100 150 200 250 300
350 400 450 500
3/8″
1/2″
3/4″
1″
16
20
26
32
Flow Rate Natural Gas [ft3/h]
128
272
488
971
88
187
335
668
71
150
269
536
60
128
231
459
54
114
204
407
48
103
185
368
41
88
158
315
37
78
140
279
33
71
127
253
31
65
117
233
29
61
109
217
27
57
102
203
25
54
97
192
20
43
78
154
17
37
66
132
15
33
59
117
14
30
53
106
13
27
49
98
12
25
46
91
11
24
43
85
11
23
40
80
800.355.6637 jonesstephens.com
29
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
SIZING TABLES
Natural Gas <2psi
Working Conditions
Natural gas
–
–
Inlet Pressure
8″ WC
–
Pressure drop
3.000 WC [inch]
Imperial diam.
Pipe [mm] Length [ft] 5 10 15 20 25 30 40 50 60 70 80 90 100 150 200 250 300
350 400 450 500
3/8″
1/2″
3/4″
1″
16
20
26
32
Flow Rate Natural Gas [ft3/h]
337
717
1287 2560
232
492
884
1760
186
395
710
1413
159
338
608
1209
141
300
539
1072
128
272
488
971
109
233
418
831
97
206
370
737
88
187
335
668
81
172
309
614
75
160
287
571
71
150
269
536
67
142
254
506
54
114
204
407
46
97
175
348
41
86
155
308
37
78
140
279
34
72
129
257
31
67
120
239
30
63
113
224
28
59
107
212
800.355.6637 jonesstephens.com
30
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
SIZING TABLES
Natural Gas <2psi
Working Conditions
Natural gas
–
–
Inlet Pressure
12-14″ WC
–
Pressure drop
6.000 WC [inch]
Imperial diam.
Pipe [mm] Length [ft] 5 10 15 20 25 30 40 50 60 70 80 90 100 150 200 250 300
350 400 450 500
3/8″
1/2″
3/4″
1″
16
20
26
32
Flow Rate Natural Gas [ft3/h]
490
1043
1872 3725
337
717
1287 2560
271
575
1033 2056
232
492
884
1760
205
436
784
1560
186
395
710
1413
159
338
608
1209
141
300
539
1072
128
272
488
971
118
250
449
894
109
233
418
831
103
218
392
780
97
206
370
737
78
166
297
592
67
142
254
506
59
126
226
449
54
114
204
407
49
105
188
374
46
97
175
348
43
91
164
327
41
86
155
308
800.355.6637 jonesstephens.com
31
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
SIZING TABLES
Natural Gas 2psi – 1psi
Working Conditions
Natural gas
–
–
Inlet Pressure
2.000
[Psi]
Pressure Drop
1.000
[Psi]
Imperial diam.
Pipe [mm] Length [ft] 5 10 15 20 25 30 40 50 60 70 80 90 100 150 200 250 300
350 400 450 500
3/8″
1/2″
3/4″
1″
16
20
26
32
Flow Rate Natural Gas [ft3/h]
1180 811 651 557 494 448 383 340 308 283 263 247 233 187 160 142 129 118 110 103 98
2510 1725 1385 1186 1051 952 815 722 654 602 560 525 496 399 341 302 274 252 234 220 208
4506 3097 2487 2129 1887 1709 1463 1297 1175 1081 1006 943 891 716 612 543 492 453 421 395 373
8968 6164 4950 4236 3754 3402 2912 2580 2338 2151 2001 1878 1774 1424 1219 1080 979 901 838 786 742
800.355.6637 jonesstephens.com
32
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
SIZING TABLES
Natural Gas 5psi – 3.5psi
Working Conditions
Natural gas
–
–
Inlet Pressure
5.000
[Psi]
Pressure Drop
3.500
[Psi]
Imperial diam.
Pipe [mm] Length [ft] 5 10 15 20 25 30 40 50 60 70 80 90 100 150 200 250 300
350 400 450 500
3/8″
1/2″
3/4″
1″
16
20
26
32
Flow Rate Natural Gas [ft3/h]
2457 1688 1356 1160 1029 932 798 707 640 589 548 514 486 390 334 296 268 247 229 215 203
5225 3591 2884 2468 2187 1982 1696 1503 1362 1253 1166 1094 1033 830 710 629 570 525 488 458 433
9381 6448 5178 4431 3928 3559 3046 2699 2446 2250 2093 1964 1855 1490 1275 1130 1024 942 876 822 777
18670 12832 10304 8819 7816 7082 6061 5372 4867 4478 4166 3909 3692 2965 2538 2249 2038 1875 1744 1636 1546
800.355.6637 jonesstephens.com
33
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
SIZING TABLES
LP Gas (Propane) <2psi
Working Conditions
Propane
–
Inlet Pressure
11
Pressure Drop
0.500
WC [inch] WC [inch]
Imperial diam.
Pipe [mm] Length [ft] 5 10 15 20 25 30 40 50 60 70 80 90 100 150 200 250 300
350 400 450 500
3/8″
1/2″
3/4″
1″
16
20
26
32
Flow Rate Propane [ft3/h]
208
443
795
1583
143
304
547
1088
115
244
439
874
98
209
376
748
87
185
333
663
79
168
302
600
68
144
258
514
60
127
229
455
54
115
207
413
50
106
191
380
46
99
177
353
44
93
167
331
41
88
157
313
33
70
126
251
28
60
108
215
25
53
96
191
23
48
87
173
21
44
80
159
19
41
74
148
18
39
70
139
17
37
66
131
800.355.6637 jonesstephens.com
34
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
SIZING TABLES
LP Gas (Propane) 2psi -1 psi
Working Conditions
Propane
–
–
Inlet Pressure
2.000
[Psi]
Pressure Drop
1.000
[Psi]
Imperial diam.
Pipe [mm] Length [ft] 5 10 15 20 25 30 40 50 60 70 80 90 100 150 200 250 300
350 400 450 500
3/8″
1/2″
3/4″
1″
16
20
26
32
Flow Rate Propane [ft3/h]
1915 1316 1057 904 802 726 622 551 499 459 427 401 379 304 260 231 209 192 179 168 159
4072 2799 2247 1924 1705 1545 1322 1172 1062 977 909 853 805 647 553 491 444 409 380 357 337
7312 5025 4035 3454 3061 2774 2374 2104 1906 1754 1631 1531 1446 1161 994 881 798 734 683 641 605
14551 10001 8031 6873 6092 5520 4724 4187 3794 3490 3247 3046 2878 2311 1978 1753 1588 1461 1359 1275 1205
800.355.6637 jonesstephens.com
35
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
SIZING TABLES
LP Gas (Propane) 5psi -3.5 psi
Working Conditions
Propane
–
–
Inlet Pressure
5.000
[Psi]
Pressure Drop
3.500
[Psi]
Imperial diam.
Pipe [mm] Length [ft] 5 10 15 20 25 30 40 50 60 70 80 90 100 150 200 250 300
350 400 450 500
3/8″
1/2″
3/4″
1″
16
20
26
32
Flow Rate Propane [ft3/h]
3986 2740 2200 1883 1669 1512 1294 1147 1039 956 889 835 788 633 542 480 435 400 372 349 330
8477 5826 4679 4004 3549 3216 2752 2439 2210 2033 1892 1775 1677 1346 1152 1021 925 851 792 743 702
15221 10462 8401 7190 6373 5774 4942 4380 3968 3651 3396 3187 3010 2417 2069 1834 1661 1528 1422 1334 1260
30292 20820 16719 14309 12682 11491 9835 8716 7898 7266 6759 6342 5991 4811 4117 3649 3306 3042 2830 2655 2508
800.355.6637 jonesstephens.com
36
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
SIZING TABLES
FITTINGS PRESSURE LOSSES IN EQUIVALENT PIPE LENGTH (ft)
FITTING NPT Male Couplings
FLOWRATE DIRECTION
VALUE 3.28
NPT Female Couplings 3.28
Wingback Elbows 3.28
Floor/Wall Mountings 3.28
Couplings 1.03
Crimp & NPT Elbows 2.26
800.355.6637 jonesstephens.com
37
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
SIZING TABLES
FITTINGS PRESSURE LOSSES IN EQUIVALENT PIPE LENGTH (ft)
FITTING Crimp & NPT tees
FLOWRATE DIRECTION
VALUE
1.64
4.51 4.92
800.355.6637 jonesstephens.com
38
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
EXAMPLE NO. 1
This is a typical single-family house installation with five (5) appliances, where the design layout of gas supply piping system is arranged in series with a main run branching at the appliances. The utility company’s supply pressure (downstream of the meter) is 8″ WC, and the utility company advises that the specific gravity of the gas delivered will be 0.60 and the energy content is 1 CFH = 1,000 BTUH. The allowable pressure drop across the system has been determined to be 3.0″ WC.
Appliances list: – Gas Furnace (70,000 BTUH 70 CFH) – Water Heater (35,000 BTUH 35 CFH) – Stove (50,000 BTUH 50 CFH) – Dryer (26,000 BTUH 26 CFH) – Fireplace (24,000 BTUH 24 CFH)
Gas Furnace 70 CFH
Water Heater
35 CFH
Stove 50 CFH
Dryer 26 CFH
F=10ft
G=15ft
Meter Trunks
A=30ft
B=5ft
H=10ft C=15ft
J=5ft
D=10ft
E=5ft
Fireplace 24 CFH
TRUNKS SECTION
A
B
C
D
LOAD DELIVERED BY SECTION 205 CFH
135 CFH
100 CFH
50 CFH
SECTION LENGTH
30′
5′
15′
10′
MOST DISADVANTAGED APPLIANCE
Dryer: – run length = 65′ – run fittings: 3 straight tees, 1 tee 90° and 1
termination
wingback elbow
Dryer: – run length = 65′ – run fittings: 3 straight tees, 1 tee 90° and 1
termination
wingback elbow
Dryer: – run length = 65′ – run fittings: 3 straight tees, 1 tee 90° and 1
termination
wingback elbow
Dryer: – run length = 65′ – run fittings: 3 straight tees, 1 tee 90° and 1
termination
wingback elbow
800.355.6637 jonesstephens.com
39
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Appliance Sections
APPLIANCE SECTION
E F G H J
APPLIANCE LOAD
24 CFH 70 CFH 35 CFH 50 CFH 24 CFH
TOTAL SECTION LENGTH
SECTION FITTINGS
65′
4 straight tees and 1 termination wingback elbow
40′
1 tee 90° and 1 termination wingback elbow
50′
1 straight tee, 1 tee 90° and 1 termination wingback elbow
60′
2 straight tees, 1 tee 90° and 1 termination wingback elbow
65′
3 straight tees, 1 tee 90° and 1 termination wingback elbow
Run Length for Trunk Sections = Distance from meter to most disadvantaged
appliance depending on the system layout and the total section length (it
means not just the furthest one but the one whose section has the highest
value of pressure losses).
Total section length for Appliance Sections = Distance from meter to each
appliance.
Sizing Run A: Utilize sizing table for natural gas at 8”WC + 3”WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 205 CFH · most disadvantaged appliance: Dryer
run to it = 65′ additional fittings of it: 3 tees straight + 1 tee 90° + 1
termination wingback elbow
total run = 65 + 31.64 + 4.51 + 3.28 = 77.71 rounded up to 80 According to
sizing table, Pipe size = 3/4in (26mm) (up to 287 CFH)
Sizing Run B: Utilize sizing table for natural gas at 8”WC + 3”WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 135 CFH · most disadvantaged appliance: Dryer
run to it = 65′ additional fittings of it: 3 tees straight + 1 tee 90° + 1
termination wingback elbow
total run = 65 + 31.64 + 4.51 + 3.28 = 77.71 rounded up to 80 According to
sizing table, Pipe size = 1/2in (20mm) (up to 160 CFH)
800.355.6637 jonesstephens.com
40
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Sizing Run C: Utilize sizing table for natural gas at 8”WC + 3”WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 100 CFH · most disadvantaged appliance: Dryer
run to it = 65′ additional fittings of it: 3 tees straight + 1 tee 90° + 1
termination wingback elbow
total run = 65 + 31.64 + 4.51 + 3.28 = 77.71 rounded up to 80 According to
sizing table, Pipe size = 1/2in (20mm) (up to 160 CFH)
Sizing Run D: Utilize sizing table for natural gas at 8”WC + 3”WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 50 CFH · most disadvantaged appliance: Dryer
run to it = 65′ additional fittings of it: 3 tees straight + 1 tee 90° + 1
termination wingback elbow
total run = 65 + 31.64 + 4.51 + 3.28 = 77.71 rounded up to 80 According to
sizing table, Pipe size = 3/8in (16mm) (up to 75 CFH)
Sizing Run E: Utilize sizing table for natural gas at 8”WC + 3”WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 24 CFH · run to relative appliance = 65′ · additional fittings
of the run: 4 tees straight + 1 termination wingback elbow
total run = 65 + 4*1.64 + 3.28 = 74.84 rounded up to 80 According to sizing
table, Pipe size = 3/8 in (16mm) (up to 75 CFH)
Sizing Run F: Utilize sizing table for natural gas at 8”WC + 3”WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 70 CFH · run to relative appliance = 40′ · additional fittings
of the run: 1 tee 90° + 1 termination wingback elbow
total run = 40 + 4.51 + 3.28 = 47.89 rounded up to 50 According to sizing
table, Pipe size = 3/8in (16mm) (up to 97 CFH)
800.355.6637 jonesstephens.com
41
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Sizing Run G: Utilize sizing table for natural gas at 8”WC + 3”WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 35 CFH · run to relative appliance = 50′ · additional fittings
of the run: 1 tee straight + 1 tee 90° + 1 termination wingback elbow
total run = 50 + 1.64 + 4.51 + 3.28 = 59.43 rounded up to 60 According to sizing table, Pipe size = 3/8in (16mm) (up to 88 CFH)
Sizing Run H: Utilize sizing table for natural gas at 8”WC + 3”WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 50 CFH · run to relative appliance = 60′ · additional fittings
of the run: 2 tees straight + 1 tee 90° + 1 termination wingback elbow
total run = 60 + 2*1.64 + 4.51 + 3.28 = 71.07 rounded up to 80 According to sizing table, Pipe size = 3/8in (16mm)m (up to 75 CFH)
Sizing Run J: Utilize sizing table for natural gas at 8”WC + 3”WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 26 CFH · run to relative appliance = 65′ · additional fittings
of the run: 3 tee straight + 1 tee 90° + 1 termination wingback elbow
total run = 65 + 3*1.64 + 4.51 + 3.28 = 77.71 rounded up to 80 According to sizing table, Pipe size = 3/8in (16mm) (up to 75 CFH)
Below are the sizes of the gas supply system:
SECTION
A B C D E F G H J
PIPE SIZE (MM) 26 20 20 16 16 16 16 16 16
PIPE SIZE (IN) 3/4 1/2 1/2 3/8 3/8 3/8 3/8 3/8 3/8
800.355.6637 jonesstephens.com
42
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
EXAMPLE NO. 2
This is a typical small single-family house installation with three (3)
appliances, where the design layout of gas supply piping system is arranged in
series with a main run branching at the appliances. The utility company’s
supply pressure (downstream of the meter) is 6″ WC, and the utility company
advises that the specific gravity of the gas delivered will be 0.60 and the
energy content is 1 CFH = 1.000 BTUH. The allowable pressure drop across the
system has been determined to be 0.3″ WC.
Appliances list: Water Heater (36,000 BTUH 36 CFH) Stove (52,000 BTUH 52
CFH) Dryer (25,000 BTUH 25 CFH)
Water Heater
36 CFH
Stove 52 CFH
Meter
D=30ft A=20ft
E=25ft B=40ft
C=15ft
Dryer 25 CFH
Trunks TRUNKS SECTION A
B
LOAD DELIVERED SECTION
BY SECTION
LENGTH
113 CFH
20′
77 CFH
40′
MOST DISADVANTAGED APPLIANCE
Stove: – run length = 85′ – run fittings: 1 straight tee, 1 tee 90° and 1
termination wingback elbow
Stove: – run length = 85′ – run fittings: 1 straight tee, 1 tee 90° and 1
termination wingback elbow
800.355.6637 jonesstephens.com
43
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Appliance Sections
APPLIANCE SECTION
C
APPLIANCE LOAD
25 CFH
TOTAL SECTION LENGTH
75′
SECTION FITTINGS 2 tees and 1 termination wingback elbow
D
36 CFH
50′
1 tee and 1 termination wingback elbow
E
52 CFH
85′
2 tees and 1 termination wingback elbow
Run Length for Trunk Sections = Distance from meter to most disadvantaged appliance depending on the system layout and the total section length (it means not just the furthest one but the one whose section has the highest value of pressure losses)
Total section length for Appliance Sections = Distance from meter to each appliance
Sizing Run A: Utilize sizing table for natural gas at 6”WC + 0.3”WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 113 CFH · most disadvantaged appliance: Stove
run to it = 85′ additional fittings of it: 1 tee straight + 1 tee 90° + 1
termination wingback elbow
total run = 85 + 1.64 + 4.51 + 3.28 = 94.43 rounded up to 100 According to sizing table, Pipe size = 1in (32mm) (up to 146 CFH)
Sizing Run B: Utilize sizing table for natural gas at 6”WC + 0.3”WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 77 CFH · most disadvantaged appliance: Stove
run to it = 85′ additional fittings of it: 1 tee straight + 1 tee 90° + 1
termination wingback elbow
total run = 85 + 1.64 + 4.51 + 3.28 = 94.43 rounded up to 100 According to sizing table, Pipe size = 1in (32mm) (up to 146 CFH)
Sizing Run C: Utilize sizing table for natural gas at 6” WC + 0.3” WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 25 CFH · run to relative appliance = 75′ · additional fittings
of the run: 2 tees straight + 1 termination wingback elbow
total run = 75 + 2*1.64 + 3.28 = 81.56 rounded up to 90 According to sizing table, Pipe size = 1/2in (20mm (up to 43 CFH)
800.355.6637 jonesstephens.com
44
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Installation Instructions English
Sizing Run D: Utilize sizing table for natural gas at 6” WC + 0.3” WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 36 CFH · run to relative appliance = 50′ · additional fittings
of the run: 1 tee 90° + 1 termination wingback elbow
total run = 50 + 4.51 + 3.28 = 57.79 rounded up to 60 According to sizing table, Pipe size = 1/2in (20mm (up to 54 CFH)
Sizing Run E: Utilize sizing table for natural gas at 6” WC + 0.3” WC pressure
drop + the table of the fittings pressure losses.
· Total Load = 52 CFH · run to relative appliance = 85′ · additional fittings
of the run: 1 tee straight + 1 tee 90° + 1 termination wingback elbow
total run = 85 + 1.64 + 4.51 + 3.28 = 94.43 rounded up to 100 According to sizing table, Pipe size = 3/4in (26mm) (up to 73 CFH)
Below are the sizes of the gas supply system:
SECTION A B C D E
PIPE SIZE (MM) 32 32 20 20 26
PIPE SIZE (IN)
1 1 1/2 1/2 3/4
800.355.6637 jonesstephens.com
45
©2023 Jones Stephens | 02712-08 | 10-18-2023
PEXALGAS®
Instrucciones de instalación Español
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>