RenewAire EV90 Energy Recovery Ventilator Owner’s Manual

August 2, 2024
RenewAire

RenewAire EV90 Energy Recovery Ventilator

Product Specifications

  • Model: EV 90
  • Product: Energy Recovery Ventilator
  • Ventilation Type: Static plate, heat and humidity transfer
  • Electrical Data: HP Volts 0.03 120, Hz 60, Phase Single, Watts 46 @ 90 CFM, FLA 0.35
  • Unit Weight: 36 lbs
  • Dimensions: 29″ L x 22″ W x 15″ H

Product Usage Instructions

Installation Orientation
The unit can be installed in any orientation as per your requirements.

Mounting & Application
The unit can be mounted in any orientation. The RA/EA airstream can be switched with the OA/SA airstream.

Control Options
There are multiple control options available to address individual climate conditions. Consult your local installer for the best installation controls for your climate.

Cleaning and Maintenance
Regularly clean and replace the filters as per the manufacturer’s instructions to maintain optimal performance.

Note : There are multiple control options designed to address individual climate conditions. Please consult your local installer for the best installation controls for your climate.

SPECIFICATIONS

  • Ventilation Type: Static plate, heat and humidity transfer
  • Typical Airflow Range: 40–110 CFM
  • Unit is HVI Tested/Certified per CSA C439 Protocol: Using one L-35-G5 Core
  • Standard Features:
    • White painted cabinet
    • Line-cord power supply
    • Low-voltage circuit for controls
    • Unit may be mounted in any orientation
    • Cross-core differential pressure ports

Control:
Onboard 24VAC transformer/relay package

Filters:

  • Total qty. 2, MERV 8, spun-polyester media : 9 5/8″ x 10 1/2″ x 1″
  • Unit Weight : 36 lbs.
  • Max. Shipping Dimensions & Weight (in carton): 29″ L x 22″ W x 15″ H 40 lbs.
  • Units Per Pallet: 10
  • Motor(s):  Qty. 2, Standard motorized impeller blowers

Accessories:

  • Backdraft damper: 6″, 8″
  • Automatic balancing damper: 4″, 5″, 6″
  • Motorized Dampers: 6″, 8″
  • Concentric Vent: 6″ (CV6-110)
  • Louvered wall vent 6″: white, brown
  • Digital time clock: wall mount (TC7D-W), in exterior enclosure (TC7D-E)
  • Carbon dioxide sensor/control: wall mount (CO2-W), duct mount (CO2-D)
  • IAQ sensor: wall mount (IAQ-W), duct mount (IAQ-D) Motion occupancy sensor/control:  ceiling mount (MC-C), wall mount (MC-W) Percentage timer control (PTL)
  • Push-button point-of-use controls (PBL), PTL req’d. Percentage timer control with furnace interlock (FM) MERV 13 filter: OA airstream (shipped loose)
  • Electric duct heater: RH series (1–3 kW); designed for indoor ductwork installation only

ELECTRICAL DATA

HP Volts Hz Phase Watts FLA
0.03 120 60 Single 46 @ 90 CFM 0.35

UNIT PERFORMANCE

Airflow (CFM)| External Static Pressure (Inches Water Column)
---|---
36| 0.60
53| 0.50
68| 0.40
81| 0.30
93| 0.20
108| 0.10

CORE PERFORMANCE

Airflow (CFM) Temp EFF% Total EFF% Winter/Summer
36 78 75/65
53 74 69/58
68 70 65/53
81 67 61/49
93 64 58/45
108 61 55/42

Note : These are core-only ratings and are not HVI certified. Total EFF% calculated at 35/33wb OA and 70/58wb RA (winter) and 98/78wb OA and 75/63wb RA (summer). HVI ratings apply to com-plete units only. This unit is HVI certified. See HVI certified ratings on pg. 47 of Single/Multi-Family Catalog and at hvi.org.

UNIT DIMENSIONS

AIRFLOW ORIENTATION
Available as shown in the dimension drawing.

UNIT MOUNTING & APPLICATION
Can be mounted in any orientation. RA/EA airstream can be switched with OA/SA airstream.

ABBREVIATIONS

  • EA : Exhaust Air to outside
  • OA: Outside Air intake
  • RA : Room Air to be exhausted
  • SA: Supply Air to the inside

INSTALLATION ORIENTATION
The unit may be installed in any orientation.

NOTE

  1. UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
  2. SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.

Subject to change without notice: RENEWAIRE.COM | 1.800.627.4499

Frequently Asked Questions

  • Q: Can the unit be installed outdoors?
    • A: The unit is designed for indoor use only.
  • Q: What type of filters does the unit use?
    • A: The unit uses MERV 8 spun-polyester media filters.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>