TCR8 IPS Colorful LCD Screen Smart Thermostat
“`html
Specifications:
- Supply voltage: AC100~240V 50/60Hz
- Power consumption: Wi-Fi 3W Max
- Temperature setting range: 5~95°F (41~203°F)
- Floor limited range: 20~90°F (68~194°F)
- On/off deviation: 0.5~10°F (1~10°F)
- Ambient temperature: -5~50°C (23~122°F)
- Protection level: IP20
- Shell material: Anti-Flammable PC
Product Overview:
This series of thermostat offers Floor Heating, Fan Coil, and
Integrated versions, suitable for various scenarios.
Product Usage Instructions:
1. Voice Control:
The device can be controlled by voice through Amazon Alexa and
Google Assistant.
2. Programmable Settings:
The thermostat is programmable with multiple periods allowed to
be set per day.
3. Display Symbols:
The display shows time, date, week, outdoor temperature, outdoor
humidity, Fan Coil valve status, Floor Heating valve status, mode,
and menu options.
4. Temperature Control Modes:
-
Auto Mode: Automatically adjusts temperature based on
settings. -
Child-lock Mode: Locks the thermostat to prevent unintended
changes. -
Frost Protection: Activates to prevent freezing
temperatures.
5. User Operation:
Press the buttons to switch between modes and adjust settings.
Use the knob for manual temperature control.
6. Wi-Fi and Bluetooth Settings:
Configure Wi-Fi settings for remote control capabilities.
Bluetooth Mode and Access Point Mode are also available for network
connectivity.
7. Timer Task Setting:
Set schedules by entering the menu page, selecting Auto Mode,
choosing Schedule, and adjusting parameters before saving.
8. Advanced Settings:
For professional technicians, access the Engineer Mode to adjust
settings like Handwheel, ModBus Address, Sensor Calibration, and
Temperature Differential.
FAQ:
Q: Can this thermostat be controlled remotely?
A: Yes, the thermostat can be controlled remotely through Wi-Fi
and voice assistants like Amazon Alexa and Google Assistant.
Q: What is the temperature setting range of this
thermostat?
A: The temperature setting range is from 41°F to 203°F (5°C to
95°C).
Q: How do I set a schedule on this thermostat?
A: Press the designated buttons to access the menu, select Auto
Mode, choose Schedule, adjust the parameters using the knob, and
save by pressing Home.
“`
IPS Colorful LCD Screen Smart Thermostat
03.11 Thur
18:00
Fair 22
Humidity 68%
68% ROOM
18.5
25.5
next
enter
home
back
Programmable device, multiple periods allowed to set per day.
The device can be controlled by voice through Amazon Alexa and Google Assistant
Parameter
Supply voltage Power consumption Temp. setting range Floor limited range On/off deviation Ambient temperature Protection level Shell material
AC100~240V50/60Hz Wi-Fi 3W Max 5~9541~203 20~9068~194 0.5~101~10Factory
setting 1 -5~5068~122 IP20
Anti-Flammable PC
Version:TCR8 1.1(12/2022)
Product Overview
This series of thermostat has Floor Heating, Fan Coil, and Integrated version,
meeting the requirements under different scenarios.
Version
System mode Model
Application
EP
Built-in & floor sensor, floor limit sensor + Weekly programming
Floor heating Floor heating
WP A NC/NO dual-output + Weekly programming
WPB
A NC/NO dual-output + Weekly programming+ Potential-free output
AC2 Timer task + 2-pipe system
Fan Coil
Heating /Cooling / Ventilation
AC2-485
Timer task + 2-pipe system + Timer task + Potential-free output + 485Modbus (optional) + Room card (optional)
AC4
Timer task + 4-pipe system + Timer task + Potential-free output + 485Modbus (optional) + Room card (optional)
Fan-Coil with
Floor heating & fan coil, weekly programming +
Integrated
Floor-Heating AWY Potential-free output + Timer task +
air condition system
485Modbus (optional) + Room card (optional)
Display Symbols
Time Display
Date Week Outdoor temp.
Outdoor humidity Fan Coil valve
Floor Heating valve Mode Menu
03.11 Thur
18:00
Fair 22
Humidity 68%
68% ROOM
18.5
25.5
next
enter
home
back
Fan Speed Temperature Control Mode(Floor Heating/Integrated)
Auto Mode
Child-lock Mode Frost Protection Wi-Fi Room humidity Set Temp.
Working mode Fan Auto Mode Manual Mode Temporary Mode
Knob
Manual Mode Thermostat works based on manually-set temperature, disconnecting
from auto mode. Temporary Mode Thermostat works based on manually-set
temperature temporarily and then shifts back to auto mode till next event.
User Operation
Temp setting: Rotate handwheel” “to change setting temperature by 0.5°C.
System mode: Press ” ” shortly to switch cooling/heating/ventilation. (Fan
Coil)
Press ” ” shortly to switch cooling/heating/ventilation/floor heating/floor
heating + heating. (Integrated) Temp control mode:
Wi-Fi setting
Wi-Fi setting Bluetooth Mode(Suggest) Access Point Mode
Bluetooth Mode
Bluetooth Mode
Access Point Mode
Access Point Mode
Please don’t leave, Bluetooth is in the network…
Please don’t leave, Access Point is in the network…
Timer Task Setting (Fan Coil/Integrated)
Press” “to enter the menu page. Turn the knob” “, choose “Auto Mode”, and then choose ” Schedule “. Set the parameters by turning the knob, then press ” Home “to save and exit to home page.
Time Setting Repeat Action
00:00 Everyday
OFF
Schedule
00:00
ON
OFF Everyday
Add
Advanced Setting (Usually for Professional Technicians)
Under power-on status, long press menu button ” ” to enter the menu page,
choose Engineer Mode, enter the advanced setting page. After setting the
parameters, press menu button ” ” to save and exit.
function list
Handwheel ” ”
ModBus Address Sensor Calibration Temp. Dif.
Adjustment range 0~250
-9.9~9.9(-9.9~9.9) 0.5~10(1~10)
Max Setting Value 5~95(41~203)
Min Setting Value 5~47(41~117)
Anti-Freeze Protection ON/OFF
Temperature Unit /
Default Integrated Fan Coil Floor Heating
Value
AWY AC2- AC4 AC2 EP WP WPB
485
0
×
0
1
50
5
OFF
Sensor Mode Floor limited Value
Built-in sensor Floor sensor Built-in Control & Floor Limitation
20~90(68~194)
IN 35
× × × × × ×
Monday to Friday Monday to Satuiday Monday to Sunday
2-day × × ×
Fan control settings
00: Fan speed controllable 01: Fan speed uncontrollable
00
×× ×
Linkage Time Delay 0~5min
0min × × ×
None Lock All All but power
None
Function Off Function On Function Saved Air-Condition Mode All/Cold Only
Temp Control
Manual/Auto
Reset All Settings Yes/No
Last
All
×× ×
Manual × × × × × ×
/
Enter menu: Press ” ” enter the menu interface. Child-lock: Press ” ” + ” ” for 3 seconds to activate child-lock.
IPS Colorful LCD Screen Smart Thermostat Auto-mode Setting (Fan Coil/Integrated)
Events
Workdays Weekends
Sunrise Morning Nooning Afternoon Evening
Night
Sunrise Night
Time Default value Modify
06:00 08:00 11:30 12:30 17:00 22:00 08:00 22:00
Default value 20 15 15 15 22 15 20 15
Dimensions (Unit: mm)
Floor Heating
11 32.6
51
EP
WP
WPB
Fan Coil
AC2
Rotate handwheel Rotate handwheel
Modify 51
Fan Coil #AC2-485 #AC4 Integrated #AWY
11 2 4
64 66
Mounting Steps
The thermostat adopt pre-guide and limited snap-fit design. It is easy to
mount. 1Release front cover by inserting a head screw-driver into bottom
crack.
2Insert the wires and then fix these wires with screws. Suggested wire-
stripping length is 7-9mm.
3Mount backing plate into wall-cassette, put screws and then fix thermostat.
Make sure that the thermostat is fixed without deformation. Suggested torque
is 0.2~0.4N.m (2.0~4. 1kgf.cm).
4Re-mount the front cover via snap-fit connection.
Sensor failure
Installation instructions
Connecting Diagram
The thermostat operates in full capacity in areas with the altitude of less
than 2500 above sea level. Power rating of external load should be less than
or equal to 80% rated power of the thermostat in areas with altitude of 2500m
to 4200m.
Floor Heating
TCR8-WIF-EP # TCR8-EP
L N N1 L1 AC100~240V
TCR8-WIFI-WP # TCR8-WP #TCR8-WIFI-WPB # TCR8-WPB
LN AC100~240V Normally-closed
electric actuator
NTC
PC1 PC2
Potential-free (Potential-free output, for model WPB only)
Dry contact signal to control boiler
Linkage control; delay time of linkage control is adjustable
PC1 PC2
L
N
AC100~240V
Normally-open electric actuator
Potential-free (Potential-free output, for model WPB only)
Dry contact signal to control boiler
Linkage control; delay time of linkage control is adjustable
PC1 PC2
LN AC100~240V
Potential-free
Three-wire (Potential-free output, for model WPB only) electrical ball valve
Dry contact signal
to control boiler
Fan Coil
Linkage control; delay time of linkage control is adjustable
L N HI MED LOW OPEN CLOSE
TCR8-WIFI-AC2 # TCR8-AC2
TCR8-WIFI-AC2-485 # TCR8-AC2-485
LN AC100~240V
N
Fan
Air conditoner
valve
N
CLOSE OPEN HI MED LOW L
89
N
Air conditoner
valve
N
PC1 PC2
Linkage control; delay time of linkage control is adjustable
16 15
CARD
14 13
Fan
L
AC100~240V
RG A B
12 11 10
TCR8-WIFI-AC4
Room card
Dry contact signal room card linkage
to control heat pump
(optional)
485A 485B (optional)
N CLOSE OPEN CLOSE OPEN HI MED LOW L
89
TCR8-AC4 N
N
Linkage control; delay time of linkage control is adjustable
L
Heat valve Cool valve
Fan AC100~240V
PC1 PC2 CARD
RG A B
16 15 14 13 12 11 10
Room card
Dry contact signal room card linkage
to control heat pump
(optional)
485A 485B (optional)
Integrated
TCR8-WIFI-AWY # TCR8-AWY
N CLOSE OPEN CLOSE OPEN HI MED LOW L
89
N
Floor system Air conditoner
valve
valve
Fan
L
AC100~240V
N
PC1 PC2 CARD RS RG A B
Linkage control; delay time of 16 15 14 13 12 11 10
linkage control is adjustable
Dry contact signal to control heat pump
NTC Room card
485A 485B (optional)
room card linkage(optional)
Read User Manual Online (PDF format)