ACiQ HP115B Standard Single Zone Mini Split User Manual
- July 31, 2024
- ACiQ
Table of Contents
HP115B Standard Single Zone Mini Split
“`html
Product Information
Specifications:
-
Models Covered: ACiQ-09W-HP115B, ACiQ-09Z-HP115B,
ACiQ-12W-HP115B, ACiQ-12Z-HP115B, ACIQ-12W-HP230B, ACiQ-12Z-HP230B,
ACIQ-18W-HP230B, ACiQ-18Z-HP230B, ACIQ-24W-HP230B, ACiQ-24Z-HP230B,
ACIQ-30W-HP230B, ACiQ-30Z-HP230B, ACIQ-36W-HP230B,
ACiQ-36Z-HP230B -
Version Date: 06-27-24
Product Usage Instructions
Precautions:
Before using the product, read the manual carefully and follow
all precautionary measures to prevent personal injury or damage to
the unit or property.
First Time Installation:
- Check all components for any damage.
- Follow the installation instructions provided in the
manual.
Refrigerant Recharge:
If refrigerant recharge is required, follow the guidelines
provided in the manual for a safe and proper recharge process.
Maintenance:
Regular maintenance is essential for optimal performance. Refer
to the manual for maintenance schedules and procedures.
Troubleshooting:
Refer to the troubleshooting section in the manual for guidance
on identifying and resolving common issues.
FAQ
Q: What should I do in case of an emergency?
A: If an emergency occurs, follow the safety
precautions outlined in the manual. Evacuate the area if necessary
and seek professional assistance.
Q: How often should I perform maintenance on the unit?
A: Regular maintenance should be performed as
per the recommendations in the manual. Typically, maintenance
checks are advised at least once a year.
“`
STANDARD SINGLE-ZONE MINI SPLIT
SERVICE MANUAL
Models Covered: ACiQ-09W-HP115B / ACiQ-09Z-HP115B ACiQ-12W-HP115B / ACiQ-12Z-
HP115B ACIQ-12W-HP230B / ACiQ-12Z-HP230B ACIQ-18W-HP230B / ACiQ-18Z-HP230B
ACIQ-24W-HP230B / ACiQ-24Z-HP230B ACIQ-30W-HP230B / ACiQ-30Z-HP230B ACIQ-36W-
HP230B / ACiQ-36Z-HP230B
VERSION DATE: 06-27-24
Table of Contents
§. Safety Precautions
1. Precautions 2. Information servicing(For flammable materials)
§. Specifications
1. Model Reference 2. Pipe length and the Drop Height 3. Refrigerant Cycle
Diagrams 4. Electrical Wiring Diagrams
§. Product Features
1. Display Function 2. Safety Features 3. Basic Features 4. Optional Features
§. Maintenance
1. First Time Installation Check 2. Refrigerant Recharge 3. Re-Installation
§. Indoor Unit Disassembly
1. Dimension 2. Indoor Unit Disassembly
§. Outdoor Unit Disassembly
1. Outdoor Unit Table 2. Dimension 3. Outdoor Unit Disassembly
Table of Contents
§. Troubleshooting
1. Safety Caution 2. General Troubleshooting 3. Complain Record Form 4. Error
Diagnosis and Troubleshooting Without Error Code 5. Quick Maintenance by Error
Code 6. Troubleshooting by Error Code 7. Check Procedures
Appendix
i) Temperature Sensor Resistance Value Table for T1,T2,T3 and T4 (°C K) ii)
Temperature Sensor Resistance Value Table for TP(for some units) (°C K) iii)
Pressure On Service Port
Safety Precautions
Contents
1. Precautions……………………………………………………………………………………………….2 2. Information
servicing(For flammable materials)………………………………………….3
1. Precautions
To prevent personal injury, or property or unit damage, adhere to all
precautionary measures and instructions outlined in this manual. Before
servicing a unit, refer to this service manual and its relevant sections.
Failure to adhere to all precautionary measures listed in this section may
result in personal injury, damage to the unit or to property, or in extreme
cases, death.
WARNING indicates a potentially hazardous situation which if not avoided could
result in serious personal injury, or death.
CAUTION indicates a potentially hazardous situation which if not avoided could
result in minor or moderate personal injury, or unit damage.
1.1 In case of Accidents or Emergency
WARNING
·· If a gas leak is suspected, immediately turn off the gas and ventilate the
area if a gas leak is suspected before turning the unit on.
·· If strange sounds or smoke is detected from the unit, turn the breaker off
and disconnect the power supply cable.
·· If the unit comes into contact with liquid, contact an authorized service
center.
·· If liquid from the batteries makes contact with skin or clothing,
immediately rinse or wash the area well with clean water.
·· Do not insert hands or other objects into the air inlet or outlet while the
unit is plugged in.
·· Do not operate the unit with wet hands. ·· Do not use a remote controller
that has previously
been exposed to battery damage or battery leakage.
CAUTION
·· Clean and ventilate the unit at regular intervals when operating it near a
stove or near similar devices.
·· Do not use the unit during severe weather conditions. If possible, remove
the product from the window before such occurrences.
1.2 Pre-Installation and Installation
WARNING
·· Use this unit only on a dedicated circuit. ·· Damage to the installation
area could cause the unit
to fall, potentially resulting in personal injury, property damage, or product
failure. ·· Only qualified personnel should disassemble, install, remove, or
repair the unit. ·· Only a qualified electrician should perform electrical
work. For more information, contact your dealer, seller, or an authorized
service center.
CAUTION
·· While unpacking be careful of sharp edges around the unit as well as the
edges of the fins on the condenser and evaporator.
1.3 Operation and Maintenance
WARNING
·· Do not use defective or under-rated circuit breakers. ·· Ensure the unit is
properly grounded and that a
dedicated circuit and breaker are installed. ·· Do not modify or extend the
power cable. Ensure
the power cable is secure and not damaged during operation. ·· Do not unplug
the power supply plug during operation. ·· Do not store or use flammable
materials near the unit. ·· Do not open the inlet grill of the unit during
operation. ·· Do not touch the electrostatic filter if the unit is equipped
with one. ·· Do not block the inlet or outlet of air flow to the unit. ·· Do
not use harsh detergents, solvents, or similar items to clean the unit. Use a
soft cloth for cleaning. ·· Do not touch the metal parts of the unit when
removing the air filter as they are very sharp. ·· Do not step on or place
anything on the unit or outdoor units. ·· Do not drink water drained from the
unit ·· Avoid direct skin contact with water drained from the unit. ·· Use a
firm stool or step ladder according to manufacturer procedures when cleaning
or maintaining the unit.
CAUTION
·· Do not install or operate the unit for an extended period of time in areas
of high humidity or in an environment directly exposing it to sea wind or salt
spray.
·· Do not install the unit on a defective or damaged installation stand, or in
an unsecure location.
·· Ensure the unit is installed at a level position ·· Do not install the unit
where noise or air discharge
created by the outdoor unit will negatively impact the environment or nearby
residences. ·· Do not expose skin directly to the air discharged by the unit
for prolonged periods of time. ·· Ensure the unit operates in areas water or
other liquids. ·· Ensure the drain hose is installed correctly to ensure
proper water drainage. ·· When lifting or transporting the unit, it is
recommended that two or more people are used for this task. ·· When the unit
is not to be used for an extended time, disconnect the power supply or turn
off the breaker.
Safety Precautions 2
2. Information servicing(For flammable materials)
2.1 Checks to the area
· Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimized.
· For repair to the refrigerating system, the following precautions shall be
complied with prior to conducting work on the system.
2.2 Work procedure
· Work shall be undertaken under a controlled procedure so as to minimise the
risk of a flammable gas or vapour being present while the work is being
performed.
2.3 Work procedure
· All maintenance staff and others working in the local area shall be
instructed on the nature of work being carried out.
· Work in confined spaces shall be avoided. · The area around the work space
shall be sectioned off.
Ensure that the conditions within the area have been made safe by control of
flammable material.
2.4 Checking for presence of refrigerant
· The area shall be checked with an appropriate refrigerant detector prior to
and during work, to ensure the technician is aware of potentially flammable
atmospheres.
· Ensure that the leak detection equipment being used is suitable for use with
flammable refrigerants, i.e. no sparking, adequately sealed or intrinsically
safe.
2.5 Presence of fire extinguisher
· If any hot work is to be conducted on the refrigeration equipment or any
associated parts, appropriate fire extinguishing equipment shall be available
to hand.
· Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
· Prior to work taking place, the area around the equipment is to be surveyed
to make sure that there are no flammable hazards or ignition risks.
· NO SMOKING signs shall be displayed.
2.7 Ventilated area
· Ensure that the area is in the open or that it is adequately ventilated
before breaking into the system or conducting any hot work. A degree of
ventilation shall continue during the period that the work is carried out. The
ventilation should safely disperse any released refrigerant and preferably
expel it externally into the atmosphere.
2.8 Checks to the refrigeration equipment
· Where electrical components are being changed, they shall be fit for the
purpose and to the correct specification. At all times the manufacturer’s
maintenance and service guidelines shall be followed. If in doubt consult the
manufacturer’s technical department for assistance. The following checks shall
be applied to installations using flammable refrigerants:
· the charge size is in accordance with the room size within which the
refrigerant containing parts are installed;
· the ventilation machinery and outlets are operating adequately and are not
obstructed;
· if an indirect refrigerating circuit is being used, the secondary circuit
shall be checked for the presence of refrigerant; marking to the equipment
continues to be visible and legible.
· markings and signs that are illegible shall be corrected;
· refrigeration pipe or components are installed in a position where they are
unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
2.6 No ignition sources
· No person carrying out work in relation to a refrigeration system which
involves exposing any pipe work that contains or has contained flammable
refrigerant shall use any sources of ignition in such a manner that it may
lead to the risk of fire or explosion.
· All possible ignition sources, including cigarette smoking, should be kept
sufficiently far away from the site of installation, repairing, removing and
disposal, during which flammable refrigerant can possibly be released to the
surrounding space.
2.9 Checks to electrical devices
· Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures. If a fault exists that could
compromise safety, then no electrical supply shall be connected to the circuit
until it is satisfactorily dealt with. If the fault cannot be corrected
immediately but it is necessary to continue operation, an adequate temporary
solution shall be used. This shall be reported to the owner of the equipment
so all parties are advised. Initial safety checks shall include:
Safety Precautions 3
· that capacitors are discharged: this shall be done in a safe manner to avoid
possibility of sparking;
· that there no live electrical components and wiring are exposed while
charging, recovering or purging the system;
· that there is continuity of earth bonding.
2.10 Repairs to sealed components
· During repairs to sealed components, all electrical supplies shall be
disconnected from the equipment being worked upon prior to any removal of
sealed covers, etc. If it is absolutely necessary to have an electrical supply
to equipment during servicing, then a permanently operating form of leak
detection shall be located at the most critical point to warn of a potentially
hazardous situation.
· Particular attention shall be paid to the following to ensure that by
working on electrical components, the casing is not altered in such a way that
the level of protection is affected. This shall include damage to cables,
excessive number of connections, terminals not made to original specification,
damage to seals, incorrect fitting of glands, etc.
· Ensure that apparatus is mounted securely.
· Ensure that seals or sealing materials have not degraded such that they no
longer serve the purpose of preventing the ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer’s
specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types
of leak detection equipment. Intrinsically safe components do not have to be
isolated prior to working on them.
2.11 Repair to intrinsically safe components
· Do not apply any permanent inductive or capacitance loads to the circuit
without ensuring that this will not exceed the permissible voltage and current
permitted for the equipment in use. Intrinsically safe components are the only
types that can be worked on while live in the presence of a flammable
atmosphere. The test apparatus shall be at the correct rating.
· Replace components only with parts specified by the manufacturer. Other
parts may result in the ignition of refrigerant in the atmosphere from a leak.
2.12 Cabling
· Check that cabling will not be subject to wear, corrosion, excessive
pressure, vibration, sharp edges or any other adverse environmental effects.
The check
shall also take into account the effects of aging or continual vibration from
sources such as compressors or fans.
2.13 Detection of flammable refrigerants
· Under no circumstances shall potential sources of ignition be used in the
searching for or detection of refrigerant leaks. A halide torch (or any other
detector using a naked flame) shall not be used.
2.14 Leak detection methods
· The following leak detection methods are deemed acceptable for systems
containing flammable refrigerants. Electronic leak detectors shall be used to
detect flammable refrigerants, but the sensitivity may not be adequate, or may
need re-calibration. (Detection equipment shall be calibrated in a
refrigerant-free area.) Ensure that the detector is not a potential source of
ignition and is suitable for the refrigerant used. Leak detection equipment
shall be set at a percentage of the LFL of the refrigerant and shall be
calibrated to the refrigerant employed and the appropriate percentage of gas
(25 % maximum) is confirmed. Leak detection fluids are suitable for use with
most refrigerants but the use of detergents containing chlorine shall be
avoided as the chlorine may react with the refrigerant and corrode the copper
pipe-work.
· If a leak is suspected, all naked flames shall be removed or extinguished.
· If a leakage of refrigerant is found which requires brazing, all of the
refrigerant shall be recovered from the system, or isolated (by means of shut
off valves) in a part of the systemremote from the leak. Oxygen free nitrogen
(OFN) shall then be purged through the system both before and during the
brazing process.
2.15 Removal and evacuation
· When breaking into the refrigerant circuit to make repairs or for any other
purpose, conventional procedures shall be used. However, it is important that
best practice is followed since flammability is a consideration.
· The following procedure shall be adhered to:
· remove refrigerant;
· purge the circuit with inert gas;
· evacuate;
· purge again with inert gas;
· open the circuit by cutting or brazing.
Safety Precautions 4
· The refrigerant charge shall be recovered into the correct recovery
cylinders. The system shall be flushed with OFN to render the unit safe. This
process may need to be repeated several times. Compressed air or oxygen shall
not be used for this task. Flushing shall be achieved by breaking the vacuum
in the system with OFN and continuing to fill until the working pressure is
achieved, then venting to atmosphere, and finally pulling down to a vacuum.
This process shall be repeated until no refrigerant is within the system. When
the final OFN charge is used, the system shall be vented down to atmospheric
pressure to enable work to take place. This operation is absolutely vital if
brazing operations on the pipe-work are to take place.
· Ensure that the outlet for the vacuum pump is not close to any ignition
sources and there is ventilation available.
2.16 Charging procedures
· In addition to conventional charging procedures, the following requirements
shall be followed:
· Ensure that contamination of different refrigerants does not occur when
using charging equipment. Hoses or lines shall be as short as possible to
minimize the amount of refrigerant contained in them.
· Cylinders shall be kept upright.
· Ensure that the refrigeration system is earthed prior to charging the system
with refrigerant.
· Label the system when charging is complete (if not already).
· Extreme care shall be taken not to overfill the refrigeration system.
· Prior to recharging the system it shall be pressure tested with OFN. The
system shall be leak tested on completion of charging but prior to
commissioning. A follow up leak test shall be carried out prior to leaving the
site.
2.17 Decommissioning
Before carrying out this procedure, it is essential that the technician is
completely familiar with the equipment and all its detail. It is recommended
good practice that all refrigerants are recovered safely. Prior to the task
being carried out, an oil and refrigerant sample shall be taken.
In case analysis is required prior to re-use of reclaimed refrigerant. It is
essential that electrical power is available before the task is commenced.
· Become familiar with the equipment and its operation.
· Isolate system electrically.
· Before attempting the procedure ensure that:
· mechanical handling equipment is available, if required, for handling
refrigerant cylinders;
· all personal protective equipment is available and being used correctly;
· the recovery process is supervised at all times by a competent person;
· recovery equipment and cylinders conform to the appropriate standards.
· Pump down refrigerant system, if possible.
· If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
· Make sure that cylinder is situated on the scales before recovery takes
place.
· Start the recovery machine and operate in accordance with manufacturer’s
instructions.
· Do not overfill cylinders. (No more than 80 % volume liquid charge).
· Do not exceed the maximum working pressure of the cylinder, even
temporarily.
· When the cylinders have been filled correctly and the process completed,
make sure that the cylinders and the equipment are removed from site promptly
and all isolation valves on the equipment are closed off.
· Recovered refrigerant shall not be charged into another refrigeration system
unless it has been cleaned and checked.
2.18 Labelling
· Equipment shall be labelled stating that it has been decommissioned and
emptied of
· refrigerant. The label shall be dated and signed. Ensure that there are
labels on the equipment stating the equipment contains flammable refrigerant.
2.19 Recovery
· When removing refrigerant from a system, either for servicing or
decommissioning, it is recommended good practice that all refrigerants are
removed safely.
· When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed. Ensure that the correct numbers
of cylinders for holding the total system charge are available. All cylinders
to be used are designated for the recovered refrigerant and labelled for that
refrigerant (i.e. special cylinders for the recovery of refrigerant).
Cylinders shall be complete with pressure relief valve and associated shut-off
valves in good working order.
Safety Precautions 5
· Empty recovery cylinders are evacuated and, if possible, cooled before
recovery occurs.
· The recovery equipment shall be in good working order with a set of
instructions concerning the equipment that is at hand and shall be suitable
for the recovery of flammable refrigerants. In addition, a set of calibrated
weighing scales shall be available and in good working order.
· Hoses shall be complete with leak-free disconnect couplings and in good
condition. Before using the recovery machine, check that it is in satisfactory
working order, has been properly maintained and that any associated electrical
components are sealed to prevent ignition in the event of a refrigerant
release. Consult manufacturer if in doubt.
· The recovered refrigerant shall be returned to the refrigerant supplier in
the correct recovery cylinder, and the relevant Waste Transfer Note arranged.
Do not mix refrigerants in recovery units and especially not in cylinders.
· If compressors or compressor oils are to be removed, ensure that they have
been evacuated to an acceptable level to make certain that flammable
refrigerant does not remain within the lubricant. The evacuation process shall
be carried out prior to returning the compressor to the suppliers. Only
electric heating to the compressor body shall be employed to accelerate this
process. When oil is drained from a system, it shall be carried out safely.
Safety Precautions 6
Specifications
Contents
1. Model Reference……………………………………………………………………………………….2 2. Pipe Length and Drop
Height …………………………………………………………………….3 3. Refrigerant Cycle Diagrams
……………………………………………………………………….4 4. Electrical Wiring
Diagrams…………………………………………………………………………9
1. Model Reference
Refer to the following table to determine the specific indoor and outdoor unit
model.
Outdoor Unit Model ACIQ-12Z-HP230B ACIQ-18Z-HP230B ACIQ-24Z-HP230B ACIQ-30Z- HP230B ACIQ-36Z-HP230B ACIQ-09Z-HP115B ACIQ-12Z-HP115B
Indoor Unit Model ACIQ-12W-HP230B ACIQ-18W-HP230B ACIQ-24W-HP230B ACIQ-30W- HP230B ACIQ-36W-HP230B ACIQ-09W-HP115B ACIQ-12W-HP115B
Capacity (Btu/h) 12k 18k 24k 30k 36k 9k 12k
Power Supply
208/230V~, 60Hz, 1Phase
115V~, 60Hz, 1Phase
Specifications 2
2. Pipe Length and Drop Height
The length and elevation of connection pipe are shown in the table below. if
the pipe length exceeds max pipe length, additional refrigerant should be
charged to ensure nominal cooling/heating capacity.
Capacity(Btu/h) Standard Length Max Pipe Length Max Elevation
Additional Refrigerant
9k~12k 17k~18k
22k 24k/30k
36k
7.5m (24.6ft)
25m (82ft) 30m (98.4ft) 30m (98.4ft) 50m (164ft) 65m (213.3ft)
10m (32.8ft) 20m (65.6ft) 20m (65.6ft) 25m (82ft) 30m (98.4ft)
15g/m (0.16oz/ft) 30g/m (0.32oz/ft)
If oil flows back into the outdoor unit’s compressor, this might cause liquid compression or deterioration of oil return. Oil traps in the rising gas pipe can prevent this.
1. Indoor unit is installed higher than outdoor unit
2. Outdoor unit is installed higher than indoor unit
If indoor unit is installed higher than outdoor unit, oil trap should be set every 10m(32.8ft) of vertical distance.
If the outdoor unit is installed higher than the indoor unit, proper oil should return to the compressor along with the suction of refrigerant to keep lubrication of compressor. If the suction flow velocity drops below 7.62m/s(1500fpm (feet per minute)), oil won’t return to the compressor. An oil trap should be installed every 6m(20ft) of vertical distance.
Specifications 3
3. Refrigerant Cycle Diagrams
ACIQ-09Z-HP115B, ACIQ-12Z-HP115B, ACIQ-12Z-HP230B
ACIQ-18Z-HP230B
Specifications 4
ACIQ-30Z-HP230B ACIQ-36Z-HP230B
Specifications 5
ACIQ-24Z-HP230B
Specifications 6
Specifications 7
Specifications 8
4. Electrical Wiring Diagrams
Indoor and outdoor unit wiring diagram
Outdoor Unit
ODU Model
ODU Wiring Diagram
ACIQ-09Z-HP115B ACIQ-12Z-HP115B ACIQ-12Z-HP230B ACIQ-18Z-HP230B ACIQ-24Z- HP230B
16022000035851 16022000035853 16022000035849
ACIQ-30Z-HP230B ACIQ-36Z-HP230B
16022000036331
Indoor Unit
IDU Model
IDU Wiring Diagram
ACIQ-09W-HP115B ACIQ-12W-HP115B ACIQ-12W-HP230B ACIQ-18W-HP230B
16022000019694
ACIQ-24W-HP230B ACIQ-30W-HP230B ACIQ-36W-HP230B
Specifications 9
Outdoor unit printed circuit board diagram
ODU Model
Outdoor Unit ODU Printed Circuit Board
ODU IPM Printed Circuit Board
ACIQ-18Z-HP230B
17122000046453
/
ACIQ-09Z-HP115B
17122000047115
/
ACIQ-12Z-HP115B
ACIQ-12Z-HP230B
17122000048121
/
ACIQ-24Z-HP230B
17122000048064
/
ACIQ-30Z-HP230B
17122000047742
/
ACIQ-36Z-HP230B
Specifications 10
Indoor unit abbreviations
Abbreviation Y/G ION CAP
PLASMA L N T1 T2
Outdoor unit abbreviations
Abbreviation 4-WAY AC-FAN DC-FAN CT1 COMP T3 T4 TH TP EEV L-PRO H-PRO
Paraphrase Yellow-Green Conductor Positive and Negative Ion Generator
Capacitor Electronic Dust Collector
LIVE NEUTRAL Indoor Room Temperature Coil Temperature of Indoor Heat Exchanger
Paraphrase Gas Valve Assembly/4-WAY VALVE
Alternating Current FAN Direct Current FAN AC Current Detector Compressor
Coil Temperature of Condenser Outdoor Ambient Temperature Compressor Suction
Temperature Compressor Discharge Temperature
Electronic Expansion Valve Low Pressure Switch High Pressure Switch
Specifications 11
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>