ACiQ PTAC Series Packaged Terminal Air Conditioner Owner’s Manual
- June 10, 2024
- ACiQ
Table of Contents
- PTAC Series Packaged Terminal Air Conditioner
- SAFETY PRECAUTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- AIR CONDITIONER FEATURES
- CONTROL PANEL OPERATION
- DIP SWITCHES CONFIGURATIONS (Optional)
- DIP SWITCHES CONFIGURATIONS by PANEL CONTROL (Optional)
- WALL THERMOSTAT TERMINAL (Optional)
- INSTALLATION
- CARE AND CLEANING
- TROUBLESHOOTING
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
PTAC Series
Installation & Owners’ Manual
PACKAGED TERMINAL AIR CONDITIONER/HEAT PUMP
Before using your air conditioner, please read this manual carefully and keep it for future reference.
PTAC Series Packaged Terminal Air Conditioner
Read This Manual
Inside you will find many helpful hints on how to use and maintain your air
conditioner properly. Just a little preventive care on your part can save you
a great deal of time and money over the life of your air conditioner. You’ll
find many answers to common problems in the chart of troubleshooting tips. If
you review our chart of Troubleshooting Tips first, you may not need to call
for service at all.
CAUTION
- This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play the appliance. Cleaning and user maintenance shall not be made by children without supervision. ( be applicable for the European Countries )
- This appliance is not intended for use by persons (including children) with reduced physical , sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. (be applicable for other countries except the European Countries )
- Children should be supervised to ensure that they do not play with the appliance.
- If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
- The appliance shall be installed in accordance with national wiring regulations.
- Do not operate your air conditioner in a wet room such as a bathroom or laundry room.
- The appliance with electric heater shall have at least 1 meter space to the combustible materials.
- Contact the authorised service technician for repair or maintenance of this unit.
- Contact the authorised installer for installation of this unit.
- When there are wide differences between USER S MANUAL and Remote controller Illustration on function description,the description on USER S MANUAL shall prevail.
- If the air conditioner is knocked over during use, turn off the unit and unplug it from the main power supply immediately. Visually inspect the unit to ensure there is no damage. If you suspect the unit has been damaged, contact a technician or customer service for assistance.
- In a thunderstorm, the power must be cut off to avoid damage to the machine due to lightning.
- To reduce the risk of fire or electric shock, do not use this fan with any solid-state speed control device.
- Do not run cord under carpeting. Do not cover cord with throw rugs, runners, or similar coverings. Do not route cord under furniture or appliances. Arrange cord away from traffic area and where it will not be tripped over.
SAFETY PRECAUTIONS
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring of instructions may cause harm or damage. The seriousness is classified by the following indications.
WARNING| This symbol indicates the possibility of death or serious
injury.
---|---
CAUTION| This symbol indicates the possibility of injury or damage to
property.
• Meanings of symbols used in this manual are as shown below.
| Never do this.
---|---
**| Always do this.**
WARNING
Plug in power plug properly.| Do not operate or stop the unit by
inserting or pulling out the power plug.| Do not damage or use an
unspecified power cord.
---|---|---
• Otherwise, it may cause electric shock or fire due to excess heat
generation.| • It may cause electric shock or fire due to heat generation.| •
It may cause electric shock or fire. If the power cord is
damaged, it must be replaced by the manufacturer or an authorized service
centre or a similarly qualified person in order to avoid a hazard.
Do not modify power cord length or share the outlet with other appliances.|
Do not operate with wet hands or in damp environment.| Do not
direct airflow at room occupants only.
• It may cause electric shock or fire due to heat generation.| • It may cause
electric shock.| • This could damage your health.
Always ensure effective earthing.| Do not allow water to run into
electric parts.| Always install circuit breaker and a dedicated power
circuit.
• Incorrect earthing may cause electric shock.| • It may cause failure of
machine or electric shock.| • Incorrect installation may cause fire and
electric shock.
Unplug the unit if strange sounds, smell, or smoke comes from it.| Do
not use the socket if it is loose or
damaged.| Do not open the unit during operation.
• It may cause fire and electric shock.| • It may cause fire and electric
shock.| • It may cause electric shock.
WARNING
Keep firearms away.| Do not use the power cord close to heating
appliances.| Do not use the power cord near flammable gas or
combustibles, such as gasoline, benzene, thinner, etc.
---|---|---
• It may cause fire.| • It may cause fire and electric shock.| • It may cause
an explosion or fire.
Ventilate room before operating air conditioner if there is a gas
leakage from another appliance.| **** Do not disassemble or modify unit.
---|---
• It may cause explosion, fire and, burns.| • It may cause failure and
electric shock.
CAUTION
When the air filter is to be removed, do not touch the metal parts of the
unit.| Do not clean the air conditioner with water.| Ventilate the
room well when used together with a stove, etc.
---|---|---
• It may cause an injury.| • Water may enter the unit and degrade the
insulation. It may cause an electric shock.| • An oxygen shortage may occur.
When the unit is to be cleaned, switch off, and turn off the circuit breaker.|
Do not put a pet or house plant where it will be exposed to direct air
flow.| Do not use for special purposes.
• Do not clean unit when power is on as it may cause fire and electric shock,
it may cause an injury.| • This could injure the pet or plant.| • Do not use
this air conditioner to preserve precision devices, food, pets, plants, and
art objects. It may cause
deterioration of quality, etc.
Stop operation and close the window in storm or hurricane.| Hold the plug by
the head of the power plug when taking it out.| Turn off the main power
switch when not using the uni
• Operation with windows opened may cause wetting of indoor and soaking of
household furniture.| • It may cause electric shock and damage.| • It may
cause failure of product or fire.
CAUTION
Do not place obstacles around air-inlets or inside of air-outlet.|
Ensure that the installation bracket of the outdoor appliance is not damaged
due to prolonged exposure.| Always insert the filters securely. Clean filter
once every two weeks.
---|---|---
• It may cause failure of appliance or accident.| • If bracket is damaged,
there is concern of damage due to falling of unit.| • Operation without
filters may cause failure.
Do not use strong detergent such as wax or thinner but use a soft
cloth.| Do not place heavy object on the power cord and ensure that the
cord is
not compressed.| Do not drink water drained from air conditioner.
• Appearance may be deteriorated due to change of product color or scratching
of its surface.| • There is danger of fire or electric shock.| • It contains
contaminants and could make you sick.
Use caution when unpacking and installing. Sharp edges could cause injury.
If water enters the unit, turn the unit off at the power outlet and switch off
the circuit breaker. Isolate supply by taking the power-plug out and contact a
qualified service technician.
Clean the evaporator once every three months by professional people.
• Otherwise it may cause failure of electric heating feature.
IMPORTANT SAFETY INSTRUCTIONS
NOTE The power supply cord with this air conditioner contains a current
detection device designed to reduce the risk of fire.
Please refer to the section Operation of Current Device for details. In the
event that the power supply cord is damaged, it cannot be repaired-it must be
replaced with a cord from the Product Manufacturer.
Do not, under any circumstances, cut, remove, or bypass the grounding prong.
Power supply cord with 3-prong grounding plug and current detection device
WARNING For your safety
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
- Avoid fire hazard or electric shock. Do not use an extension cord or an adaptor plug. Do not remove any prong from the power cord.
WARNING Electrical Information
- Be sure the electrical service is adequate for the model you have chosen. This information can be found on the serial plate, which is located on the side of the cabinet and behind the grille.
- Be sure the air conditioner is properly grounded. To minimize shock and fire hazards, proper grounding is important. The power cord is equipped with a three-prong grounding plug for protection against shock hazards.
- Your air conditioner must be used in a properly grounded wall receptacle. If the wall receptacle you intend to use is not adequately grounded or protected by a time delay fuse or circuit breaker, have a qualified electrician install the proper receptacle.
- Ensure the receptacle is accessible after the unit installation.
- Do not run air conditioner without side protective cover in place. This could result in mechanical damage within the air conditioner.
- The appliance shall be installed in accordance with national wiring regulations.
- Do not use an extension cord or an adapter plug.
NOTE:
The shape may be different according to its model:
Power Card| | | | | |
---|---|---|---|---|---|---
Power Suppy| 230V,15A| 230V,20A| 230V,30A| 265V,15A| 265V,20A| 265V,30A
Operation of Current Device(optional)
The power supply cord contains a current device that senses damage to the
power cord. To test your power supply cord do the following:
NOTE: Some plugs have buttons on the top.
- Plug in the Air Conditioner.
- The power supply cord will have TWO buttons on the plug head. Press the TEST button, you will notice a click as the RESET button pops out.
- Press the RESET button, again you will notice a click as the button engages.
- The power supply cord is now supplying electricity to the unit. (On some products this it also indicated by a light on the plug head.)
NOTES:
- Do not use this device to turn the unit on or off.
- Always make sure the RESET button is pushed in for correct operation.
- The power supply must be replaced if it fails reset when either the TEST button is pushed, or it cannot be reset. A new one can be obtained from the product manufacturer.
- If power supply cord is damaged, it cannot be repaired. It MUST be replaced by one obtained from the product manufacturer.
- V units are to be installed, the power supply must be permanent wiring.Permanent٢٦٥When
- V units wiring may be done through the accessory subbase. An exposed cord connection on ٢٦ are not permitted
AIR CONDITIONER FEATURES
This unit has many featrues. The servicer must be familiar with these features in order to properly service the unit.
-
Compressor Restart Delay
This feature extends the overall life of compressor by preventing the short- cycling of the air conditioner. When the compressor restarts, the unit is designed to give a minimum of three minutes to have a time of equalizing the refrigerant pressures for optimizing cycling. -
Memory
The unit has memory .If power is lost, all of the control settings(mode, fan speed, on/off and configuration) are remembered. So when power is restored, the unit will start back up in the mode (and configuration) it was in, when power was lost. -
Automatic Evaporator Freeze Protection
Automatically to keep the evaporator from freezing, the compressor is tuuned off and the indoor fan is turned on when the evaporator temperature is too lower. If the evaporator temperature is not too lower this function is off. -
Automatic Quick Warm-up (for heat pump models only)
If the room temperature falls to 4.5OC/8OF below the set point temperature, the reverse cycle heat is shut off and the electric strip heat is turned on for one cycle, until heating is satisfied. -
LED Indicators and Buttons
The touch pad has buttons for MODE, FAN, POWER, SETPOINT UP and SETPOINT DOWN. It also has LEDs that correspond to the mode, fan speed, power and setpoint operation, to indicate the unit s status. LEDs for HIGH,MED and LOW indicate the fan speed that is selected. LEDs for FAN,COOL and HEAT indicate what operating mode is active. LED for POWER is the unit ON/OFF status LED. If the unit is in ON mode, the LED will be green. If the unit is OFF, the LED will be off.
NOTE: HEAT mode is for Cooling & Heating models only. -
High Temperature Protection In Heating Operation
The compressor and(or) electric heater will be switched off to prevent damage in high indoor blow air temperature or error indoor temperature sensor. -
Unit Configuration
ºF or ºC
The unit can display in either F or C.
CONTROL PANEL OPERATION
The control panel keypad will look like the following Fig.1. For some models with REMOTE SIGNAL RECEPTOR, the unit can be controlled by the control panel alone or by the remote. NOTE: Some models have no REMOTE SIGNAL RECEPTOR.
-
POWER
- Press the POWER button to turn the unit on or off.
-
MODE
-
Push this button to cycle through the modes from COOL-HEAT-FAN-COOL. The indicator light beside the “MODE” option will illuminate, identifying the mode selected.
-
COOL: Cooling begins automatically when the room temperature is above the set point, and stops when the room temperature is 2OC(4OF) below the set point. But the compressor will run 5 minutes at least in COOL mode before stoping.
-
HEAT: The maximum temperature can be set up to 29OC/84OF. For heat pump models, the unit can alternate to run between in reverse cycle heat mode and electric heater mode according to the difference between the setting temperature and the room temperature. The fan motor cycles with the compressor stop.
NOTE: The reverse cycle and electric heater cannot be run at the same time. In following cases, it is normal that the reverse cycle does not operate.
1.When the outdoor temperature is lower than 4OC/40OF or the room temperature falls to 4.5OC/8OF below the set point temperature.
2.There is a 3-minute minimum compressor run time at any setting to prevent short cycling. The indoor fan motors starts before the compressor and stops after the compressor cycles off.
3.Push the S1 on the DIP SWITCHES to UP (ON) position.
4.When frost builds up to the evaporator coils, the unit will defrost automatically and the compressor will cycle off. -
FAN: Fan operation only without heating and cooling. Note: If the unit has DIP SWITCHES feature, the temperature range can be setted is controlled by DIP SWITCHES. See DIP SWITCHES CONFIGURATIONS on page 8 for details.
-
-
UP/DOWN BUTTONS ( / )
- Push the UP (or DOWN) button to increase (or decrease) the set temperature of the unit in cooling or heating mode. The temperature can be set by increments of 1OC (1OF). The setting temperature appears in the display.
NOTE: Press and hold and buttons together for 3 seconds will alternate the temperature display between OC & OF scale.
- Push the UP (or DOWN) button to increase (or decrease) the set temperature of the unit in cooling or heating mode. The temperature can be set by increments of 1OC (1OF). The setting temperature appears in the display.
-
FAN (FAN SPEED)
- Every time you push this button, the fan speed cycles through the settings as follows: HIGH-MEDLOW-HIGH.
-
CONSTANT FAN
- In cooling mode, press the button to turn on or off the constant fan function. When the function is turned on, the constant fan light will illuminate, identifying the fan continuous run for cooling. When the function is turnd off, the constant fan light will go out, identifying the fan cycle run with compressor stop.
NOTE: Every time the unit is turned on, the function will work as the DIP SWITCHES CONFIGURATIONS
- In cooling mode, press the button to turn on or off the constant fan function. When the function is turned on, the constant fan light will illuminate, identifying the fan continuous run for cooling. When the function is turnd off, the constant fan light will go out, identifying the fan cycle run with compressor stop.
-
DISPLAYS:
- Shows the set temperature in OC or OF. While on Fan only mode, it shows the room temperature. Control code (on some models):
LC- Pads on the control panel is not available. The unit can be setted by using wire cotroller only.
FC -Pads on the control panel and wire controller are not available. The unit can be setted by using FRONT DESK CONTROL only. Error codes:
AS -Room temperature sensor error;
ES -Evaporator temperature sensor error;
CS -Condenser temperature sensor error;
OS -Outside temperature sensor error;
HS -Exhaust temperature sensor error;
LE -Wire cotroller error;
NOTE: When error occurs, unplug the unit and plug it back in. If error repeats, call for service.
Other codes:
LO -Room temperature is lower than 0OC/32OF;
HI -Room temperature is higher than 37OC/99OF;
FP -Low temp. Protection.
NOTE: All the illustrations in this manual are for explanation purpose only. Your air conditioner may be slightly different. The actual shape shall prevail.
- Shows the set temperature in OC or OF. While on Fan only mode, it shows the room temperature. Control code (on some models):
NOTE: This air conditioner is designed to be operated under condition as follows:
Cooling operation| Outdoor temp:| 18-43°C/64-109°F (18-52°C/64-125°F for
special tropical models)
---|---|---
Indoor temp:| 17-32°C/62-90°F
Heating operation| Outdoor temp:| -5-24 C/23-76 F
Indoor temp:| 0-27°C/32-80°F
Note: Performance may be reduced outside of these operating temperatures.
Accessory
NOTE: When the unit displays LC (Pads on the control panel is not
available. The unit can be setted by using wire controller only.) You can
install the Accessory on the control panel.
NOTE: For some models, there is corresponding operation happened after 3
seconds when pressing any button.
NOTE: When there are wide differences between USERS MANUAL and Remote
controller Illustration on function description, the description on USERS
MANUL shall prevail.
DIP SWITCHES CONFIGURATIONS (Optional)
-
REMOVING THE FRONT PANEL
- Dip switches controls are located behind front panel, through an opening below the control panel. To access, remove front panel. See Fig.2.
- Dip switches are accessible without opening the control box. See Fig.3.
- Unit must be powered OFF to effectively change their status.
- Pull out at the bottom to release it from the tabs .
- Then lift up .
-
DIP SWITCHES CONFIGURATIONS
- See Table 1 and Fig.4 for Dip Switches configurations and functions of each dip switch position.
Table 1 DIP SWITCHES CONFIGURATIONS
No . | UP(ON) | DOWN(OFF) | Remarks |
---|---|---|---|
S1 | Electric Heat Only | Electric Heat and Pump Heat | For Heat Pump unit only |
S2 | Temperature Display in °F | Temperature Display in °C | |
S3 | Wall Thermostat Enable | Control Panel Enable | |
S4*S5 | UP*UP:61°F-86°F(16°C-30°C); |
UPDOWN:65°F-78°F(18°C-26°C);
DOWNUP:63°F-80°F(17°C-27°C);
DOWNDOWN:68°F-75°F(20°C-24°C);| Two configurations (S4S5) combine to select
set point range.
S6| Fan Continuous Run for Heating Fan Cycle for Heating|
S7| Fan Continuous Run for Cooling| Fan Cycle for Cooling|
S8| Low temp. Protection enable| Low temp. Protection disable| Optional
S9
(S3 UP)| Use some types of wall Thermostat| Use PTAC other Wall Thermostat|
you can consult with the
sales agency or manufacturer for details
S9 (S3
DOWN)| Use Control Panel only| Use Control Panel or some types of wall
Thermostat| Use control Panel or some types of wall Thermostat, the other one
must be turned off
Sw11| Load delay for 3 seconds| Normal| Optional
NOTE: On heating mode, the setting temperature can not be higher than 29º C/84º F.
-
Wall Thermostat Enable
- A wired wall thermostat can be connected to the unit .If it is, this dip switch must be moved to the Wall Thermostat Enable Position, before the wall thermostat will begin control.
-
Low temp. Protecton(optional)
- If unit senses a room temperature below 32º F (0º C), the fan motor and electric strip heat will turn on and warm the room to 40º F(4.4º C). The fan stops a short time after the temperature is satisfied.
-
Electric Heat Only (for heat pump unit only)
- This setting is typically used for Emergency Heating.
-
Heat and Cool Fan CON/CYC Dip-switches
-
Allows the fan to operate in continuous or cycle modes while the unit is in heating and cooling mode.
CON(Continuous) -
Allows fan to run continuously, circulating air even when the temperature setting has been satisfied. This switch helps to maintain the room temperature closer to the thermostat setting.
CYC(Cycle) -
This setting allows the fan to cycle on and off with the compressor or electric heater. The fan stops a short time after the temperature setting is satisfied.
-
-
Setpoint Temperature Limits
- Provides a restricted range of temperature control.
DIP SWITCHES CONFIGURATIONS by PANEL CONTROL (Optional)
-
DIP SWITCHES CONFIGURATIONS by PANEL CONTROL
-
Turn off the unit.
-
Press the up (+) and down (-) buttons together for 3 seconds to activate the dip switches configurations by panel control (see Fig.4).
-
See Table 1 for Dip Switches configurations and functions by panel control.
NOTE: Press the up (+) and down (-) buttons together for 3 seconds again or no operation within 30 seconds to exit the dip switches configurations by panel control and the unit will save the last settings. -
Display function settings with 2 digitals in LED display window, high (left) for dip switches, low (right) for functions (see Fig.4).
-
Press up (+) button to set the dip swithces, press down (-) button to set the functons.
-
Table 1 DIP SWITCHES CONFIGURATIONS by PANEL CONTROL
No . | High(left) | Low(right) | Remarks |
---|---|---|---|
/ | 0 | 1-by panel control | 0-by dip switches |
S1 | 1 | 1-electric heat only | 0-electric heat and pump heat |
only
S2| 2| 1-tmperature display in °F| 0-temperature display in °C|
S3S9| 3| 3- use control panel or some types of wall thermostat;
2-use some types of wall thermostat; 1-use PTAC other wall thermostat;
0-control panel enable.| You can consult with the sales agency or manufacturer
for details
S4S5| 4| 4-62°F-86°F(17°C-30°C); 3-61°F-86°F(16°C-30°C);
2-65°F-78°F(18°C-26°C); 1-63°F-80°F(17°C-27°C);
0-68°F-75°F(20°C–24°C);|
S6| 6| 1-fan continuous run for heating| 0-fan cycle for heating| Not
available for” use PTAC other wall thermostat”.
S7| 7| 1-fan continuous run for cooling| 0-fan cycle for cooling
S8| 8| 1-low temp. protection enable| 0-low temp. protection disable| Optional
SW7| A| 1-front desk control disable| 0-front desk control enable| Optional
Sw11| B| 1-Load delay for 3 seconds| 0-normal| Optional
NOTE:
- The LED display window will show 00 when you first enter the setting mode, only when you set 01 you can start the next settings.
- To activate front dest control function, you need to pull the dip switch SW7 to DOWN(OFF) , and then set the panel control to A0 .
- After all set, press up (-) and down (+) buttons together for 3 seconds to exit the operation interface and cut off the power. When re-power on, the settings are activated.
WALL THERMOSTAT TERMINAL (Optional)
- IMPORTANT: Only trained, qualified personnel should access electrical panel on unit and install electrical accessories. Please contact your local electrical contractor, dealer, or distributor for assistance.
- Thermostat Wire Routing
Thermostat wire is field supplied. Recommended wire gauge is 18 to 20 gauge solid thermostat wire.
NOTE: It is recommended that extra wires are run to unit in case any are damaged during installation.
Thermostat wire should always be routed around or under, NEVER through, the wall sleeve. The wire should then be routed behind the front panel to the easily accessible terminal connector.
Fig. A – Proper Wire Routing Beneath Unit
NOTE: Refer to thermostat installation instructions for details on installing wall thermostat.
-
Installation instruction of some types of wall Thermostat (you can Consult with the Thermostat sales agency or manufacturer for details)
-
Pull the dip switch to the DOWN(OFF) position as shown below.
-
Insert the wire connector of the wall thermostat into the relevant terminal according to different shapes as shown below.
-
-
Installation instruction of PTAC other Wall Thermostat
- Remove the two screws as shown below and take the cover panel down.
Terminal of PTAC other Wall Thermostat(MODE A)
TERMINAL | DESIGNATION |
---|---|
FC(L) | Front desk control terminal L |
FC(N) | Front desk control terminal N |
LOW-FAN | Low fan speed |
HI-FAN | High fan speed |
4-WAY | 4-way valve; Reverse cycle (Energized in Heat) For heat pump models |
HEAT2 | Electrical heater 2 |
HEAT1 | Electrical heater 1 |
COMP | Compressor |
24V(N) | 24VAC terminal N(Neutral),Common |
24V(L) | 24VAC terminal L |
Terminal of PTAC other Wall Thermostat(MODE B)
CAUTION
UNIT DAMAGE HAZARD
-
Failure to follow this caution may result in equipment damage or improper operation.
-
Improper wiring may damage unit electronics. Common busing is not permitted. Damage or erratic operation may result.
-
FRONT DESK CONTROL
The controller can handle a switch signal from FC(L) and FC(N) input, called front desk control.
Input must be 24VAC. If system doesn’t receive a 24VAC signal, it will turn unit off; otherwise, the unit runs in normal control.- The DIP switch can control the FRONT DESK CONTROL feature. The DIP switch is on the DOWN position, the unit will be turn off; other wise, the unit runs in normal control. See Fig B.
NOTE:
- The DIP switch can control the FRONT DESK CONTROL feature. The DIP switch is on the DOWN position, the unit will be turn off; other wise, the unit runs in normal control. See Fig B.
-
Use terminal 4-way for heat pump connection only.
-
Suggest set the compressor protection time morn than 3 minutes in wall thermostat If set less than 3 minutes, the compressor will restart delay 3 minutes still.
-
Wall thermostat must be heating changeover 4-way valve.
-
For thermostats that have only one fan speed output (on or auto),the fan speed is determined by how the terminal connector is wired. If Low fan is desired, wire the G output from the thermostat to (LOW-FAN) on the units terminal block. If High fan is desired, wire the G output from the the mostat to (HI-FAN) on the units terminal block.
-
The range of set temperature of Wall thermostat must be in consonance with the range of DIP switch setting.
-
Wall thermostat must be set the type properly in consonance with the unit type : heat pump or no heat pump.
-
If the Wall thermostat has only one electrical heater output, connect the two terminals of HEAT 1 and HEAT 2, the unit can operate two electrical heaters(only for the unit has two electrical heaters). Otherwise operate one electrical heater.
-
Please do not remove the control panel.
INSTALLATION
-
HOW TO INSTALL THE UNIT
CAUTION -
There are sharp edges that can cause serious cuts.
-
When lifting the air conditioner, it is HEAVY. Use 2 people to lift.
-
For existing sleeve, you should measure the wall sleeve dimensions.
-
Install the new air conditioner according to these installation instructions to achieve the best performance.
All wall sleeves used to mount the new air conditioner must be in good structural condition and have a rear grille that securely attaches to the sleeve or the flange of the sleeve to secure the new air conditioner. -
To avoid vibration and noise, make sure the unit is installed securely and firmly.
-
When installing the sleeve, make certain there is nothing within 20 of the back that would interfere with heat radiation and exhaust air flow. (See Fig.5)
-
-
PREPARATION OF SLEEVE ASSEMBLY(optional)
- Refer to the installation instruction of sleeve assembly for details.
-
PREPARATION OF REAR GRILLE ASSEMBLY (optional)
- Refer to the installation instruction of rear grille assembly for details.
-
UNIT INSTALLATION
-
- Carefully remove shipping tapes from the front panel. (See Fig.6)
- Remove the front panel. (See Fig.7)
- Remove the shipping screw from the vent door.(See Fig.8)
Dimension of air conditioner
Dimension of sleeve assembly (optional)
-
* Pull out at the bottom to release it from the tabs 1 .
Then lift up 2 .
Fig.7 -
UNIT INSTALLATION (CONTINUED)
- Rotate the vent control lever to either open or close the vent door.(See Fig.9)
NOTE: When vent control lever set at CLOSE, only the air inside the room
is circulated and filtered.
When set at OPEN, some outdoor air will be drawn into room. This will reduce
heating or cooling efficiency.
CAUTION
-
Do not put obstacles around air-inlet or inside of air-outlet of the unit, such as window curtain etc.
-
Always insert the filter securely, clean filter once every two weeks as required.
-
Lift unit level and slide unit into wall sleeve until firmly against front of wall sleeve and secure with 4 screws and washers (supplied in the SLEEVE ASSEMBLY ) through the unit flange holes. (See Fig.10 and Fig.11)
-
Reinstall front panel.(See Fig.12)
-
Place tabs over top rail 1 . Push Inward at bottom until panel snaps into
place 2 .
Fig.12
CARE AND CLEANING
- FRONT PANEL AND CASE
- Turn unit off and disconnect power supply. To clean, use water and a mild detergent.DO NOT use bleach and abrasivers. Some commercial cleaners may damage the plastic parts.
- OUTDOOR COIL
- Coil on outdoor side of unit should be checked regularly. Unit will need to be removed to inspect dirt build-up that will occur on the inside of the coil.
If clogged with dirt and soot ,coil should be professionally cleaned. Clean inside and outside of outdoor coils regularly.
NOTE: Never use a high-pressure spray on coil.
- Coil on outdoor side of unit should be checked regularly. Unit will need to be removed to inspect dirt build-up that will occur on the inside of the coil.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damge or improper
operation.
Airflow restriction may cause damage to the unit.
- AIR FILTERS
IMPORTANT:TURN UNIT OFF BEFORE CLEANING.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damge or improper
operation.
-
Do not operate unit without filters in place. If a filter becomes torn or damaged, it should be replaced immediately.
-
Operating without filters in place or with damaged filter will allow dirt and dust to reach indoor coil and reduce cooling, heating, airflow and efficiency of unit. Airflow restriction may cause damage to unit.
-
The most important thing you can do to maintain unit efficiency is to clean the filters once every two weeks as required.
Clogged filters reduce cooling, heating and airflow. -
Keeping filters clean will:
Decrease cost of operation.
Save energy.
Prevent clogged indoor coil.
Reduce risk of premature component failure. -
To Clean Air Filters:
Vacuum off heavy soil.
Run water through filter.
Dry thoroughly before replacing. -
Removing Air Filter
-
Replacing Air Filter
-
-
VENT DOOR FILTER
IMPORTANT:TURN UNIT OFF BEFORE CLEANING.- If the vent door is open, access requires the removal of the unit from the wall sleeve. Clean the vent filter twice a year or as required.
- Make sure to remove the shipping screw from the vent door.(See.Fig.8)
- Rotate the vent control lever to open the vent door. (See. Fig.15)
- Remove four screws from the vent door filter. (See.Fig.15)
- First pull out the vent door steel wire from the hole of the vent door, then take off the vent door and filter. (See.Fig.15)
- Clean the filter. Dry thoroughly before replacing.
- Replac the vent door and filter, reinstall the four screws.
- Reinsert the vent door steel wire into the hole of the vent door.
TROUBLESHOOTING
POSSIBLE CAUSES | SOLUTONS |
---|
UNIT DOES NOT START
• Unit may have become unplugged
• Fuse may have blown
• Circuit breaker may have been tripped
• Unit may be off
• Unit may be in a protection mode.| • Check that plug is plugged securely in
wall receptacle.
Note: Plug has a test/reset button on it. Make sure that the plug has not
tripped.
• Replace the fuse. See Note 1.
• Reset circuit breaker. See Note 1.
• Turn unit on (bottom right button on keypad).
UNIT NOT COOLING/HEATING ROOM
• Unit air discharge section is blocked
• Temperature setting is not high or low enough
Note: Setpoint limits may not allow the unit to heat or cool the room to the
temperature desired. Check section on dipswitch settings.
• Unit air filters are dirty.
• Room is excessively hot or cold when unit is started.
• Vent door left open.
• Unit may be in a protection mode.
• Compressor is in time delay.| • Make sure that curtains, blinds or furniture
are not restricting or blocking unit airflow.
• Reset to a lower or higher temperature setting.
• Remove and clean filters.
• Allow sufficient amount of time for unit to heat or cool the room. Start
heating or cooling early before outdoor temperature, cooking heat or
gatherings of people make room uncomfortable.
• Close vent door.
• Check dipswitch and wall thermostat settings for desired comfort.
• Wait approximately 3 minutes for compressor to start.
DISPLAY HAS STRANGE NUMBERS/ CHARACTERS ON IT| • The unit may be in a
protection mode.
• The unit may be set for °C (instead of °F).
UNIT MAKING NOISES| • Clicking, gurging and whooshing noises are normal
during operation of unit.
WATER DRIPPING OUTSIDE| • If a drain kit has not been installed,
condensation runoff during very hot and humid weather is normal. See Note 2.If
a drain kit has been installed and is connected to a drain system, check
gaskets and fittings around drain for leaks and plugs.
WATER DRIPPING INSIDE
• Wall sleeve is not installed level| • Wall sleeve must be installed level
for proper drainage of condensation .Check that installation is level and make
any necessary adjustments.
ICE OR FROST FORMS ON INDOOR COIL
• Low outdoor temperature
• Dirty filters| • When outdoor temperature is approximately 550F or below,
frost may form on the indoor coil when unit is in Cooling mode. Switch unit to
FAN operation until ice or frost melts.
• Remove and clean filters.
COMPRESSOR PROTECTION
• Power may have cycled, so compressor is in a restart protection.| • Random
Compressor restart- Whenever the unit is plugged in,or power has been
restarted, a random compressor restart will occur. After a power outage, the
compressor will restart after approximately 3 minutes.
• Compressor Protection- To prevent short cycling of the compress or,
there is a random startup delay of 3 minutes and a minimum compressor run time
of 3 minutes.
ELECTRIC HEATING FAILURE| • Clean the evaporator once every three months
by professional people.
NOTES:
- If circuit breaker is tripped or fuse is blown more than once, contact a qualified electrician.
- If unit is installed where condensation drainage could drip in an undesirable location, an accessory drain kit should be installed and connected to drain system.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>