RenewAire EV 300 Indoor Unit Residential Light Commercial Owner’s Manual
- July 31, 2024
- RenewAire
Table of Contents
RenewAire EV 300 Indoor Unit Residential Light Commercial
Note : There are multiple control options designed to address individual climate conditions. Please consult your local installer for the best installation controls for your climate.
ELECTRICAL DATA
HP | Volts | Hz | Phase | Watts | FLA |
---|---|---|---|---|---|
0.2 | 120 | 60 | Single | 315 @ 297 CFM | 3.3 |
SPECIFICATIONS
-
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range: 150–300 CFM -
Unit is HVI Tested/Certified per CSA C439 Protocol:
Using one L-100-G5 Core -
Standard Features:
White painted cabinet
Line-cord power supply
Low-voltage circuit for controls
Unit may be mounted in any orientation
Cross-core differential pressure ports -
Controls :
Onboard 24VAC transformer/relay package -
Filters :
Total qty. 2, MERV 8, spun-polyester media: 10 1/2″ x 21 3/4″ x 1″ -
Unit Weight: 72 lbs.
-
Max. Shipping Dimensions & Weight (on pallet):
34″ L x 44″ W x 34″ H
115 lbs. -
Units Per Pallet: 4
-
Motor(s):
Qty. 1, Double-shaft standard motor -
Accessories:
-
Backdraft damper: 8″
-
Automatic balancing damper: 4″, 5″, 6″
-
Motorized Dampers: 8″
-
Louvered wall vent 8″: taupe vinyl, galvanized, paintable galvanneal
-
Louvered wall vent with 8″ round duct connection: 12″ W x 8″ H
-
Hooded wall vent 8″: galvanized, paintable galvanneal
-
Digital time clock: wall mount (TC7D-W), in exterior enclosure (TC7D-E)
-
Carbon dioxide sensor/control: wall mount (CO2-W), duct mount (CO2-D)
-
IAQ sensor: wall mount (IAQ-W), duct mount (IAQ-D)
-
Motion occupancy sensor/control: ceiling mount (MC-C), wall mount (MC-W)
Percentage timer control (PTL)
Push-button point-of-use controls (PBL), PTL req’d.
Percentage timer control with furnace interlock (FM) -
MERV 13 filter: OA airstream (shipped loose)
Electric duct heater: RH series (1–10 kW); designed for indoor ductwork installation only
-
UNIT PERFORMANCE
Airflow (CFM)| External Static Pressure (Inches Water
Column)
---|---
170| 1.00
191| 0.90
214| 0.80
256| 0.70
278| 0.60
295| 0.50
311| 0.40
CORE PERFORMANCE
Airflow (CFM) | Temp EFF% | Total EFF% Winter/Summer |
---|---|---|
170 | 78 | 73/59 |
191 | 77 | 71/57 |
214 | 75 | 69/55 |
256 | 73 | 66/51 |
278 | 71 | 65/49 |
295 | 70 | 63/47 |
311 | 69 | 62/46 |
Note : These are core-only ratings and are not HVI certified. Total EFF% calculated at 35/33wb OA and 70/58wb RA (winter) and 98/78wb OA and 75/63wb RA (summer). HVI ratings apply to com-plete units only. This unit is HVI certified. See HVI certified ratings on pg. 48 of Single/Multi-Family Catalog and at hvi.org.
UNIT DIMENSIONS
AIRFLOW ORIENTATION
Available as shown in dimension drawing.
UNIT MOUNTING & APPLICATION
Can be mounted in any orientation. RA/EA airstream can be switched with OA/SA
airstream.
ABBREVIATIONS
- EA: Exhaust Air to outside
- OA: Outside Air intake
- RA: Room Air to be exhausted
- SA: Supply Air to inside
INSTALLATION ORIENTATION
Unit may be installed in any orientation.
NOTE
- UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
- SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.
Subject to change without notice: RENEWAIRE.COM | 1.800.627.4499