Nexans 10264907 Defrost Flex Drum Cable Instructions

July 30, 2024
Nexans

Nexans 10264907 Defrost Flex Drum Cable

Specifications

  • Product Name: DEFROST FLEX Drum Cable
  • International Designation: DEFROST FLEX
  • Nexans Ref.: 10264907
  • Country Ref.: 1008196

DESCRIPTION

DEFROST FLEX is a series-resistant heating cables for installation inside water pipes. It comprises 4 single-core resistance wire for heating, out of which one is a pure copper wire, plus a grounding wire. The nominal output is 7-12 W/m, and the maximum operating voltage is 500V. For 230V, suitable lenghts are between 60 and 170 meters, and for 400V, suitable lengths are between 95 and 295 meters. For other voltages, calculations can be made. All 4 conductors are connected in one end of the cable, and according to the installed length, the resistance wires are connected to the power supply cable in various patterns. Only the original end- and termination kit supplied by Nexans (10265444) is approved for the installation of DEFROST FLEX Nexans insertion nipple (10212358) must be used for insertion of heating cable in drinking water pipes

Technical data

  • Nominal linear power: From 7 W/m to 12 W/m
  • Nominal operating voltage : 230V or 400V
  • Tolerance on conductor resistance: – 5% / +10%
  • Min. installation temperature : 0 °C
  • Mechanical class: M2

Nexans-10264907-Defrost Flex-Drum-Cable-FIG- \(1\)

Usage Instructions

  1. Ensure the correct voltage requirements for your installation(230V or 400V).
  2. Use the Nexans insertion nipple (10212358) for inserting the heating cable into drinking water pipes.
  3. Connect all 4 conductors at one end of the cable according to the installation length.
  4. Use the approved end- and termination kit supplied by Nexans for installation.
  5. Follow the guidelines for suitable cable lengths based on voltage.

CHARACTERISTICS

Nexans-10264907-Defrost Flex-Drum-Cable-FIG- \(2\)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

Generated 7/17/24

www.nexans.no

FAQ

Q: Can I use a different termination kit with DEFROST FLEX?
A: No, only the original end- and termination kit supplied by Nexans (10265444) is approved for use with DEFROST FLEX.

Q: What is the maximum operating voltage of DEFROST FLEX?
A: The maximum operating voltage is 500V for DEFROST FLEX.

Q: Is DEFROST FLEX suitable for potable water applications?
A: Yes, DEFROST FLEX is approved for use with potable water.