DESCRIPTION

FXQJMCMK HF EMC is a halogen free, XLPE-insulated, HFFR-sheathed cable with circular, stranded copper conductors for cross-sections up to 35 mm2. Larger cross-sections have sector shaped, stranded copper conductors. FXQJ/MCMK HF EMC is designed according to HD 604. The cable has a screen of annealed copper wires with opposite overlapping helix of copper tape. The copper screen has an optical coverage of 100 % and fulfil the EMC directive when it is correct installed. The conductors have resistance and number of wires according to IEC 60228 class 2. The cores are identified by colors according to HD 308. The outer sheath is UV-protected and is marked type/manufacturer/flame propagation//year month/meter marking. FXQJ/ MCMK HF EMC meets the requirements for flame class Dcas2d2a2 according to CPR and emits no corrosive gases during fire. The cable is certified by Intertek SEMKO.

LifeSmart (TM) recycling marking
The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.

Standards
FXQJ/MCMK HF EMC is manufactured and tested according to HD 604 S1-5D in applicable parts. The cable can be loaded according to SS 424 14 24.

Certification
Approved by Intertek SEMKO.

Quality and environmental management system
Certified according to ISO 9001, IRIS, ISO/TS 16949 and ISO 14001.

Conductor flexibility Stranded
![Conductor flexibility

Stranded](https://manuals.plus/wp- content/uploads/2024/01/Screenshot_1-1081.png)
Halogen free Yes
![Halogen free

Yes](https://manuals.plus/wp-content/uploads/2024/01/Screenshot_2-983.png)
Rated Voltage Uo/U (Um) 0.6/1 kV
![Rated Voltage Uo/U

(Um](https://manuals.plus/wp-content/uploads/2024/01/Screenshot_3-920.png)
Minimum installation temperature -10 °C
![Minimum

installation

temperature](https://manuals.plus/wp- content/uploads/2024/01/Screenshot_4-831.png)
Maximum operating temperature 90 °C
![Maximum operating

temperature](https://manuals.plus/wp- content/uploads/2024/01/Screenshot_5-798.png)
U.V resistance Yes
![U.V resistance

Yes](https://manuals.plus/wp-content/uploads/2024/01/Screenshot_6-738.png)
Electro magnetic interference resistance
![Electro magnetic

interference

resistance](https://manuals.plus/wp- content/uploads/2024/01/Screenshot_7-700.png)
Water proof Good
![Water proof

Good](https://manuals.plus/wp-content/uploads/2024/01/Screenshot_8-649.png)

CHARACTERISTICS

Construction characteristics

Conductor material| Bare copper
Conductor flexibility| Stranded
Insulation| XLPE (chemical)
Outer sheath| HFFR (polyolefin)
Color| Black
Halogen free| Yes
Conductor shape| Sector-shaped
With Green/Yellow core| No
With smaller neutral conductor| No
Dimensional characteristics
Conductor diameter| – mm
Number of cores| 4
Average insulation thickness| 1.0 mm
Screen section| 25 mm²
Average sheath thickness| 2.0 mm
Nominal outer diameter| 29.0 mm
Approximate weight| 290.0 kg/100m
Conductor cross-section| 50 mm²
Neutral conductor section (when smaller)| – mm²
Electrical characteristics
Max. DC resistance of the conductor at 20°C| 0.387 Ohm/km
Resistance of the screen| 0.73 Ohm/km
Rated Voltage Uo/U (Um)| 0.6/1 kV
Usage characteristics
Minimum installation temperature| -10 °C
Recommended minimum installation temperature| 0 °C
Maximum operating temperature| 90 °C
U.V resistance| Yes
Short-circuit max. conductor temperature| 250 °C
Electro magnetic interference resistance|
Packaging| K12
Water proof| Good
Length| 500 m
Bending factor when installed| 8 (xD)
Bending factor when laying| 12 (xD)
Gases corrosivity| IEC 60754-2
Installation type| Indoor/Outdoor
Minimum operating temperature| -40 °C
Smoke density| IEC 61034

SELLING AND DELIVERY INFORMATION

FXQJ/MCMK HF EMC will be delivered in lengths of 500 m. The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

Generated 12/9/22
www.nexans.no

Company logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Nexans User Manuals

Related Manuals