Model#
| Content| Weight
---|---|---
lb| kg
MASTERKIT 15-72| SERVICEKIT 15 GMP 6| 30.2| 13.7
MASTERKIT 30-72| SERVICEKIT 30 GMP 6| 32.2| 14.6
MASTERKIT 60-72| SERVICEKIT 60 GMP 6| 33.3| 15.1
Expansion Tank
Model# | Volume | Connection | Dimension | Weight |
---|---|---|---|---|
A | B | |||
gal | L | in | mm | in |
HGT15 | 2.1 | 8 | ½˝ | 7.9 |
HGT30 | 4.8 | 18 | ½˝ | 10.6 |
HGT60 | 8 | 30 | ½˝ | 13.8 |
Glycol Make-Up Package
Model# | Volume | Pump | Dimension | Weight |
---|---|---|---|---|
A | B | C | ||
gal | L | PSI | in | mm |
GMP6 | 6 | 22.7 | 60 | 12 |
The kit includes
Service Center
Steel frame
Model# | Length | Height | Width |
---|---|---|---|
HGSC-MULTI | 10¾ ˝ | 4½ ˝ | 2³⁄ 8 ˝ |
Pressure Gauge
¹⁄8˝MNPT • 0-30 PSI
Model# | Weight |
---|---|
lb | kg |
GAGE0-30BOTTOM | 0.22 |
Automatic Brass Vent
¹⁄8˝MNPT
Model# | Weight |
---|---|
lb | kg |
R8818 | 0.24 |
Service Valve with drain
½˝ MNPT × ½˝ FNPT
Model# | Weight |
---|---|
lb | kg |
HGSV12 | 0.66 |
Connection Hose
Braided hose 72˝
½˝FNPT×½˝MNPT
Model# | Weight |
---|---|
lb | kg |
BH72 | 1.32 |
Expansion Tank
Model# | Volume | Weight |
---|---|---|
gal | L | lb |
HGT15 | 2.1 | 8 |
HGT30 | 4.8 | 18 |
HGT60M | 6 | 23 |
HGT60 | 8 | 30 |
Glycol Make-Up Package
Model# | Volume | Weight |
---|---|---|
gal | L | lb |
GMP6 | 6 | 22.7 |
Their function is to automatically supply pressurized water or a water/glycol
mixture to a closed-loop space heating, chilled water, snowmelt, solar,
radiant heating or process control system, to ensure that minimum system
pressure levels are maintained.
RESIDENTIAL AND COMMERCIAL
COMMERCIAL AND INDUSTRIAL
Calefactio’s GMP are economical yet rugged, compact and easy to use fluid feeders for small closed-loop systems.
Their function is to automatically supply pressurized water or a water/glycol mixture to a closed-loop space heating, chilled water, snowmelt, solar, radiant heating or process control system, to ensure that minimum system pressure levels are maintained.
Technical Specifications
Model# | Volume | Pump | Dimension | Weight |
---|---|---|---|---|
A | B | C | ||
gal | L | PSI | Ampere | in |
GMP6 | 6 | 22.7 | 60 | 0.6 A |
GMP18 | 18 | 68.1 | 60 | 0.6 A |
GMPLC55 | 55 | 208 | 100 | 0.9 A |
GMPLC100 | 100 | 379 | 100 | 0.9 A |
GMP6S | 6 | 15.0 | 100 | 0.6 A |
GMP18S | 18 | 22.7 | 100 | 0.6 A |
Discover the master kit junior which includes seven products in a single box on .
Specifications
-
Pump : 1.6 GPM (6 L/m)
GMP6 and GMP 18: 60 PSI
GMPLC55 and
GMPLC100: 100 PSI -
Discharge connection: ½˝FNPT
-
120 VAC/1 ph/60 Hz, standard plug with 1.8 m (6 ft) power cord.
-
Level switch with plug (piggyback), pump power cutoff when the liquid in the tank is too low.
-
The pressure regulation valve is easily adjustable to maintain pressure up to 412.8 kPa
(60 psig), and 690 kPa
(100 psig) for solar models.
A : Flexible braided hose
B : ¾˝Opening for return from the system safety valve
C : By-pass valve
D : Pressure adjustment valve
E : Pump
F : Glycerine pressure gauge (0-100 PSI)
G : 3-way filling valve**