Danfoss iC7 Series Air Cooled Common Mode Filter Installation Guide
- July 23, 2024
- Danfoss
Table of Contents
- iC7 Series Air Cooled Common Mode Filter
- Specifications
- Product Usage Instructions
- Mechanical Installation
iC7 Series Air Cooled Common Mode Filter
“`html
Specifications
Product Name: iC7 Series Air-cooled Common-mode
Filter OFXC1
Filter Sizes: 3, 4, or 5 cores
Installation: Suitable for IP00 and IP54
installation
Product Usage Instructions
Mechanical Installation
Safety Information
WARNING: SHOCK HAZARD FROM THE COMPONENTS The
components of the drive are live when the drive is connected to
mains. – Do not make changes in the AC drive when it is connected
to mains.
CAUTION: BURN HAZARD The filter is hot during
operation. – Do not install the filter on a combustible surface. –
Do not touch the filter when hot.
Only qualified personnel are allowed to perform the installation
described in this guide. Follow the instructions in this guide and
relevant local regulations. Also read the instructions and safety
information in the operating guide for the iC7 Series System
Modules.
Installation Requirements
The products that are described in this guide have the
protection rating IP00/UL Open Type. Install them in a cabinet or
other enclosure that has a correct level of protection against the
ambient conditions in the installation area. Make sure that the
cabinet gives protection against water, humidity, dust, and other
contaminations.
The cabinet must also be sufficiently strong for the weight of
the system modules and other devices.
The protection rating of the cabinet must be at least IP21/UL
Type 1. When preparing the installation, obey the local
regulations.
Installing the Common-mode Filter into the Cabinet
See the installation dimension in 2.6 Dimensions of the
Common-mode Filter.
Mechanical Installation
Mounting Holes of the Common-mode Filter
Mounting holes
In IP54 installations, attach the assembly plate of the AuxBus
temperature measurement board to the cabinet, but outside the IP54
section. Mount the assembly plate with 4 screws.
Connecting and Routing of the Temperature Measurement Wire
Connect the temperature measurement wire from the filter to
terminal X204 on the AuxBus temperature measurement board.
The length of the wire is 1.5 m (4.9 ft). If necessary, the wire
can be cut shorter. Route the wire through the grommet included in
the delivery. Attach the wire to the assembly plate with a cable
tie.
FAQ
Q: What are the different sizes of the Common-mode Filter
available?
A: The Common-mode Filter is available in 3, 4, or 5 cores
sizes.
Q: What type of installations is the Common-mode Filter
suitable for?
A: The filter is suitable for both IP00 and IP54
installations.
“`
Installation Guide
iC7 Series Air-cooled Common-mode Filter OFXC1
1 Overview
1.1 Common-mode Filter
The Common-mode Filter reduces bearing and ground currents, and high frequency
noise in the motor cables. There are 3 sizes of the filter with 3, 4, or 5
cores. The filter is suitable for IP00 and IP54 installation.
e30bk554.10
e30bk558.11
Illustration 1: Common-mode Filter with 3 Cores (IP00 Installation) and with 5
Cores (IP54 Installation)
1.2 Contents of the Delivery
1
3
6
4
2
5
Illustration 2: Items Included in the Delivery
1
Common-mode Filter
5
2
Temperature measurement wire, 1.5 m (4.9 ft),
6
mounted 7
3
AuxBus temperature measurement board assembly
8
4
Cable ties, 3 pcs
7
8
M5x10 screws, 2 pcs AuxBus cable, 3 m (9.8 ft) Grommet, Ø25.3 mm (Ø1 in)
AuxBus terminals, 2 pcs
Danfoss A/S © 2023.08
AN440742666343en-000201 / 172K0615 | 1
iC7 Series Air-cooled Common-mode Filter OFXC1 Installation Guide
Mechanical Installation
2 Mechanical Installation
2.1 Safety Information
WARNING
SHOCK HAZARD FROM THE COMPONENTS The components of the drive are live when the
drive is connected to mains.
– Do not make changes in the AC drive when it is connected to mains.
CAUTION
BURN HAZARD The filter is hot during operation.
– Do not install the filter on a combustible surface. – Do not touch the
filter when hot.
Only qualified personnel are allowed to perform the installation described in this guide. Follow the instructions in this guide and relevant local regulations. Also read the instructions and safety information in the operating guide for the iC7 Series System Modules.
2.2 Installation Requirements
The products that are described in this guide have the protection rating
IP00/UL Open Type. Install them in a cabinet or other enclosure that has a
correct level of protection against the ambient conditions in the installation
area. Make sure that the cabinet gives protection against water, humidity,
dust, and other contaminations.
The cabinet must also be sufficiently strong for the weight of the system
modules and other devices.
The protection rating of the cabinet must be at least IP21/UL Type 1. When
preparing the installation, obey the local regulations.
2.3 Installing the Common-mode Filter into the Cabinet
See the installation dimension in 2.6 Dimensions of the Common-mode Filter.
Procedure 1. Attach the Common-mode Filter to the cabinet using the Ø6 mm (Ø0.24 in) mounting holes.
1
1
e30bk561.11
1
1
1
1
1
1
1
1
Illustration 3: Mounting Holes of the Common-mode Filter
1
Mounting holes
2. In IP54 installations, attach the assembly plate of the AuxBus temperature
measurement board to the cabinet, but outside the IP54 section. Mount the
assembly plate with 4 screws.
See Illustration 5.
2 | Danfoss A/S © 2023.08
AN440742666343en-000201 / 172K0615
e30bk562.10 e30bk574.10
iC7 Series Air-cooled Common-mode Filter OFXC1 Installation Guide
1
1
2
2
Mechanical Installation
Illustration 4: Mounting Holes of the Assembly Plate
1
Mounting holes with keyholes, Ø5/3
2
Mounting holes, Ø5.5
3. Connect the temperature measurement wire from the filter to terminal X204
on the AuxBus temperature measurement board.
The length of the wire is 1.5 m (4.9 ft). If necessary, the wire can be cut
shorter. Route the wire through the grommet included in the delivery. Attach
the wire to the assembly plate with a cable tie.
IP54 IP00
1
23
1.5 m
Illustration 5: Connecting and Routing of the Temperature Measurement Wire
1
Grommet
2
Cable tie
3
Terminal X204
Danfoss A/S © 2023.08
AN440742666343en-000201 / 172K0615 | 3
iC7 Series Air-cooled Common-mode Filter OFXC1 Installation Guide
Mechanical Installation
2.4 Installing the AuxBus Temperature Measurement Board on the Common-mode
Filter, IP00
Optionally in IP00 installations, the AuxBus temperature measurement board can
be mounted on the Common-mode Filter. Before mounting the AuxBus temperature
measurement board on the Common-mode Filter, the AuxBus temperature
measurement board assembly must be disassembled.
Procedure 1. Remove the touch cover of the AuxBus temperature measurement
board by removing the M4x8 screw. Save the screw.
e30bk576.10
e30bk575.10
Illustration 6: Removing the Touch Cover 2. Remove the 2 cable clamps from the
assembly plate by removing the 2 size M4x8 screws. Save the screws.
Illustration 7: Removing the Cable Clamps
4 | Danfoss A/S © 2023.08
AN440742666343en-000201 / 172K0615
e30bk573.10
iC7 Series Air-cooled Common-mode Filter OFXC1 Installation Guide
Mechanical Installation
3. Remove the AuxBus temperature measurement board from the assembly plate by removing the 3 size M4x8 screws. Save the screws.
Illustration 8: Removing the AuxBus Temperature Measurement Board on the Assembly Plate 4. Attach the AuxBus temperature measurement board to the filter with 3 of the M4x8 screws.
e30bk570.10
Illustration 9: Mounting the AuxBus Temperature Measurement Board to the Filter 5. Mount the 2 cable clamps to the filter frame with 2 of the M4x8 screws.
e30bk572.10
Illustration 10: Mounting the Cable Clamps Danfoss A/S © 2023.08
AN440742666343en-000201 / 172K0615 | 5
iC7 Series Air-cooled Common-mode Filter OFXC1 Installation Guide
6. Mount the touch cover on top of the board with 1 of the M4x8 screws.
Mechanical Installation
e30bk571.10 e30bk557.10
Illustration 11: Mounting the Touch Cover
7. Connect the temperature measurement wire from the filter to terminal X204
on the AuxBus temperature measurement board. The length of the wire is 1.5 m
(4.9 ft). It is recommended to cut the wire shorter.
1
2 1
Illustration 12: Connecting and Routing of the Temperature Measurement Wire
1
Cable ties
2
Terminal X204
2.5 Cooling Requirements
The maximum ambient operating temperature of the Common-mode Filter is 40 °C
(104 °F), with derating up to 55 °C (131 °F).
The product requires forced air cooling. Make sure that the cooling airflow
through the filter cores is sufficient. The minimum airflow is 3 m/s (10
ft/s).
6 | Danfoss A/S © 2023.08
AN440742666343en-000201 / 172K0615
e30bk583.10
iC7 Series Air-cooled Common-mode Filter OFXC1 Installation Guide
Illustration 13: Airflow Through the Filter Cores
Mechanical Installation
Danfoss A/S © 2023.08
AN440742666343en-000201 / 172K0615 | 7
iC7 Series Air-cooled Common-mode Filter OFXC1 Installation Guide
2.6 Dimensions of the Common-mode Filter
230 (9.06) 204 (8.03)
70 (2.76)
50
141.5 (1.97)
(5.57) 33
A
(1.30)
10 x Ø6 (0.24)
107.5 (4.23)
177
B
(6.97) 68.5
(2.70)
Mechanical Installation
e30bk556.11
213 (8.39) 104
C
(4.09)
E
121.2 (4.77)
Ø3 (0.12)
Ø5 (0.20)
Ø5.5 (0.22)
D
84 (3.31)
120.5 (4.74)
F
141.4 (5.57)
76.8 (3.02)164.4
(6.47)
Illustration 14: Dimensions of the Common-mode Filter in mm (in)
A
Filter with 3 cores
B
Filter with 4 cores
C
Filter with 5 cores
D
AuxBus temperature measurement board assembly
E
Depth of the filter in IP54 installation
F
Depth of the filter in IP00 installation
8 | Danfoss A/S © 2023.08
AN440742666343en-000201 / 172K0615
iC7 Series Air-cooled Common-mode Filter OFXC1 Installation Guide
Electrical Installation
3 Electrical Installation
3.1 Power Cabling
Install the Common-mode Filter at the inverter output. If the inverter has
parallel power units, install a separate Common-mode Filter at the output of
each power unit. The Common-mode Filter can be installed as the only output
filter, or it can be used with a dU/dt Filter or Sine-wave Filter. If another
output filter is installed, install the Common-mode Filter between the other
output filter and the motor. See 3.4 Wiring Diagrams.
NOTICE
If grounding conductors are routed through the filter cores, the filter does
not function properly.
– Only route the motor phase cables or busbars through the filter cores. – Do
not route any ground conductors through the filter cores.
Make sure that the cables or busbars do not touch the filter cores.
During operation, the filter cores can heat up to 130 °C (266 °F). If cables
are used, they must be able to withstand this temperature. If the cables are
not rated for such high temperatures, they must be routed so that they do not
touch the filter cores.
3.2 Preparing the AuxBus Cable
1. Cut the cable to the required length. 2. To reveal the wires, strip the
cable at both ends. 3. At 1 end of the cable, remove approximately 15 mm (0.59
in) of the insulation of the cable. 4. Strip the wires 7 mm (0.28 in). 5.
Connect the wires to the terminals included in the delivery. Use the
tightening torque 0.220.25 Nm (1.92.2 in-lb).
Table 1: Wiring of the AuxBus Terminals
Pin
Wire color
Signal
1
White
+24 V
2
Brown
GND
3
Green
CAN_H
4
Yellow
CAN_L
5
Grey
+24 V
e30bk577.10
12
3
Illustration 15: The Ready AuxBus Cable
21
Danfoss A/S © 2023.08
AN440742666343en-000201 / 172K0615 | 9
e30bk560.10 e30bk559.10
iC7 Series Air-cooled Common-mode Filter OFXC1 Installation Guide
Electrical Installation
1
Terminals
2
Wires
3
Shield removed
3.3 AuxBus Connections
NOTICE
For the drive to be able to protect the filters, AuxBus must be connected.
For more information about AuxBus, see the iC7 Series System Module operating
guides.
1. Connect the AuxBus cable between the filter and the power unit. If there
are several power units and filters, connect each filter to the power units
individually. – a. Connect the end of the AuxBus cable where the insulation
was removed to terminal X25 on the power unit. – b. Connect the other end of
the AuxBus cable to terminal X86 on the AuxBus temperature measurement board.
X201
X202
X86
X203
X204
X205
X85
X206
Illustration 16: Terminals on the AuxBus Temperature Measurement Board
X20_ X85
Temperature measurement input AuxBus in
X86 AuxBus out
Control unit
Optical fiber cable
Power unit X25 AuxBus Cable X86 Filter
Control unit
Optical fiber cable
Star coupler board Optical fiber cable
Optical fiber cable Optical fiber cable
Power unit 1 X25 AuxBus cable X86
Filter 1
Power unit 2 X25 AuxBus cable X86
Filter 2
Power unit N X25 AuxBus cable X86
Filter N
Illustration 17: AuxBus Topology
2. Route the cable so that there is no risk of getting in touch with bare
busbars or terminals. 3. Ground each AuxBus cable at 1 end, at the X25
terminal. To make the grounding connection, attach the shield of the cable
to the frame with a cable clamp.
The lower part of the cable clamp fixes the cable to the plate and provides
strain relief. The upper part provides ~360° grounding for the cable shield.
10 | Danfoss A/S © 2023.08
AN440742666343en-000201 / 172K0615
iC7 Series Air-cooled Common-mode Filter OFXC1 Installation Guide
1
2
3
e30bj147.10
Electrical Installation
e30bg725.11
Illustration 18: Using the Cable Clamps
1
Stripping length, 15 mm (0.59 in)
2
Strain relief
3
Grounding
4. At the terminal X86 end of the cable, place the cable in a cable clamp for strain relief.
3.4 Wiring Diagrams
1
2
3
4
U
U’
U
DC+
DC+ V
V’
V
DC-
DCW
W’
W
Illustration 19: Wiring Diagram for Inverter and Common-mode Filter
1
DC fuses
4
2
Inverter module
5
3
dU/dt Filter or Sine-wave Filter (optional)
U/T1 V/T2 W/T3 PE
Common-mode Filter Motor
5
U1 V1 M W1 3~ PE
Danfoss A/S © 2023.08
AN440742666343en-000201 / 172K0615 | 11
iC7 Series Air-cooled Common-mode Filter OFXC1 Installation Guide
DC+ DC-
1
2
U
DC+
V
DC-
W
3
U’
U
V’
V
W’
W
U
DC+
V
DC-
W
U’
U
V’
V
W’
W
4
U/T1 V/T2 W/T3
U/T1 V/T2 W/T3
Electrical Installation
5
U1 V1 M W1 3~ PE
e30bg726.11
U
DC+
V
DC-
W
U’
U
V’
V
W’
W
U/T1 V/T2 W/T3
PE DC+ DC-
Illustration 20: Wiring Diagram for Inverter with Parallel Power Units and
Common-mode Filters
1
DC fuses
2
Inverter modules
3
dU/dt Filters or Sine-wave Filters (optional)
4
Common-mode Filters
5
Motor
Vacon Ltd, Member of the Danfoss Group Runsorintie 7 FIN-65380 Vaasa
www.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogs,
brochures and other printed material. Danfoss reserves the right to alter its
products without notice. This also applies to products already on order
provided that such alterations can be made without subsequential changes being
necessary in specifications already agreed. All trademarks in this material
are property of the respective companies. Danfoss and the Danfoss logotype are
trademarks of Danfoss A/S. All rights reserved.
12 | Danfoss A/S © 2023.08
172K0615B
AN440742666343en-000201 / 172K0615
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>