solis S6EH3P-50K-HV 3 Phase 50kw Hybrid Inverter User Guide

July 22, 2024
solis

solis S6EH3P-50K-HV 3 Phase 50kw Hybrid Inverter

Specifications

  • Model: S6-EH3P50k-H
  • Version: 1.0
  • Maximum Number of Inverters in Parallel: 6
  • Communication: Bluetooth
  • Communication Wiring: Standard CAT5/6 ethernet cable

FAQ

Frequently Asked Questions

  • Q: Can I use any type of ethernet cable for communication between the inverters?
    • A: It is recommended to use standard CAT5/6 ethernet cables for communication between the inverters to ensure proper functionality.
  • Q: Should I create a password the first time I connect to the inverter via Bluetooth?
    • A: Yes, first-time users must create a password when connecting to the inverter via Bluetooth for security purposes.

Communication Wiring

Parallel Terminal Connections

  • Up to 6 inverter units of the inverter can be connected in parallel. The inverters parallel communication P-A and P-B terminals should be connected in a daisy chain configuration as per the below diagram.
    • E. g. Inverters Master P-A >> Slave 1 P-B || Slave 1 P-A >> Slave 2 P-B
    • NB. Standard CAT5/6 ethernet cable can be used.
  • The P-A and P-B communication cables are supplied with the inverter. Standard straight ethernet cables with RJ45 plugs can also be used for the parallel cables between the inverters.

Setting the Parallel Dip Switches

Before starting and running a parallel system ensure that both parallel dip switches 1 & 2 marked in figure 2.1-2 below are both set to the “ON” position on the first and last inverter.
These must Not be switched on or off while the machine is on.

Connecting to the Inverter via Bluetooth

  • Step 1: Open Solis Cloud App and select the “Services” icon as per below.
  • Step 2: Select the “Local Operations” menu
  • Step 3: Select “Connect with Bluetooth” option
  • Step 4: Select the correct inverter serial number
  • Step 5: Log into the inverter
    • NB. First time users must create a password

Master Inverter Parallel Settings

  • Step 1: Select “Parallel Setting” menu
  • Step 2: Set Parallel Mode to “Parallel”
  • Step 3: Set “Physical Address ID” to next # sequence
  • Step 4: Set Manual Master/Slave to “Master”
  • Step 5: Set the Total Number of inverters
  • Step 6: Turn Parallel Sync “On”
    • NB. These settings should be completed with “Parallel Sync” set to the “On” position

Slave Inverter Parallel Settings

  • Step 1: Select “Parallel Setting” menu
  • Step 2: Select “Parallel” from the Parallel Mode menu
  • Step 3: Set “Physical Address ID” to next # sequence
  • Step 4: Set Manual Master/Slave to “Slave
  • Step 5: Set the Total Number of inverters
  • Step 6: Turn off “Parallel Sync”
    • NB. These settings should be completed with “Parallel Sync” set to the “Off” position on the slave inverters.