PEDROLLO CB2 Fixed Speed Pressure Units Instructions
- July 18, 2024
- pedrollo
Table of Contents
PEDROLLO CB2 Fixed Speed Pressure Units
- Domestic use
- Civil use
- Industrial use
- Agricultural use
INSTALLATION AND USE
CB2 is a pre-assembled pumping system comprising two pumps, designed for water supply and pressurization in residential, commercial, and public buildings, hotels, and hospitals, as well as for garden and agricultural irrigation. CB2 is suitable for pumping clean water or aqueous solutions that do not chemically or mechanically damage the materials used and do not contain abrasive or fibrous sub-stances.
PRODUCT DESCRIPTION
CB2 is a pressurization system featuring two pumps assembled in a unit, ready for connection to the water mains or a primary collection tank. Controlled by mechanical pressure switches, CB2 ensures automatic activation of one or both pumps in response to increased user demand, optimizing water supply and minimizing electricity consumption. The system’s electronic circuitry facilitates automatic pump switching during start/stop cycles and protects against potential faults.
COMPONENTS
- Pumps connected in parallel via suction and discharge manifolds. Each unit is equipped with ball valves on the discharge and suction side, non-return valves on the suction side (with 2CP, 3-5CR, FCR, MK pumps), or on the discharge side (with HT pumps).
- BASE is made of metal profile and fitted with adjustable vvibration-dampingfeet.
- PRESSURE SWITCHES mounted on the delivery manifold and connected to the electrical panel for switching the pumps on and off according to regulation.
- ELECTRONIC ELECTRICAL PANEL (model E2) protects against dry running by monitoring electrical parameters and allows advanced users to adjust settings to tailor the operation of the pressure unit to specific sys-tem requirements.
- Power supply:
- CB2m: single-phase 230 V – 50 Hz
- CB2: three-phase 400 V – 50 Hz
CB2 – 2CP
Pressurization unitscompriseg two twin impeller centrifugal pumps, designed to
enhance water pressure. Ideal for both residential and commercial water supply
applications, they are well-suited for large-scale garden and agricultural
irrigation. They also excel at handling clean water in various industrial
settings.
TECHNICAL DATA
- Liquid temperature between +5 °C and +55 °C
- Ambient temperature between +5 °C and +40 °C
- Max. pressure in the pump body 10 bar (6 bar for 2CP25/130)
- Continuous running duty S1
CB2 – 3-5CR
Pressurization units comprising two multistage centrifugal pumps. They are
well-suited for domestic water supply, garden irrigation, and gen-eral clean
water handling.
TECHNICAL DATA
- Liquid temperature between +5 °C and +55 °C
- Ambient temperature between +5 °C and +40 °C
- Max. pressure in the pump body 7 bar
- Continuous running duty S1
CB2 – FCR
Pressurization units comprising two horizontal multistage centrifugal pumps.
Especially well-suited for residential and commercial water supply, in-
dustrial pressure boosting, and gar-den and field irrigation.
TECHNICAL DATA
- Liquid temperature between +5 °C and +55 °C
- Ambient temperature between +5 °C and +40 °C
- Max. pressure in pump body 11 bar (for FCR 80-100 7 bar)
- Continuous running duty S1
CB2 – HT
Pressurization units comprising two vertical multistage centrifugal pumps.
They are well-suited for residential and commercial water supply, ir-rigation,
and general clean water handling, including industrial appli-cations
TECHNICAL DATA
- Liquid temperature between +5 °C and +55 °C
- Ambient temperature between +5 °C and +40 °C
- Max. pressure in the pump body 16 bar
- Continuous running duty S1
FIELD AND PERFORMANCE DATA
TYPE| POWER P2| Q| m³/h| 0| 2.4| 4.8| 7.2| 9.6| 10.8|
12.0| 13.2| 14.4| 16.8| 19.2
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 40| 80| 120| 160| 180| 200| 220|
240| 280| 320
CB2 – 2CPm 25/130| –| 2×0.75| 2×1|
H metres
| 42| 39| 34.5| 28.5| 22| 18| 15| | | |
CB2 – 2CPm 25/14B| CB2 – 2CP 25/14B| 2×1.1|
2×1.5| 54| 52| 47.5| 41| 32.5| 27.5| 22| | | |
CB2 – 2CPm 25/16C| CB2 – 2CP 25/16C| 2×1.1|
2×1.5| 47| 46| 44| 40.5| 36| 33.5| 30.5| 27.5| 24| |
CB2 – 2CPm 25/16B| CB2 – 2CP 25/16B| 2×1.5|
2×2| 58| 56| 54| 51| 47.5| 45.5| 43| 40| 37| 30|
–| CB2 – 2CP 25/16A| 2×2.2| 2×3| 68| 67| 65| 62| 58.5|
56| 54| 51| 48| 40.5| 32
TYPE| POWER P2| Q| m³/h| 0| 4.8| 7.2| 9.6| 12.0| 14.4|
16.8| 19.2| 21.6| 24.0| 30.0
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 80| 120| 160| 200| 240| 280| 320|
360| 400| 500
–| CB2 – 2CP 32/200C| 2×3| 2×4|
H metres
| 70| 67| 65| 63| 60.5| 58| 55| 52| 48.5| 45.5| 36
–| CB2 – 2CP 32/200B| 2×4| 2×5.5| 85| 81| 79| 77| 74.5|
71.5| 69| 66| 62.5| 59| 49
–| CB2 – 2CP 32/210B| 2×5.5| 2×7.5| 94| 94| 93| 91| 89|
86| 83| 79| 75| 70| 56
–| CB2 – 2CP 32/210A| 2×7.5| 2×10| 112| 111| 110| 109|
107| 105| 102| 99| 95| 90| 74
TYPE| POWER P2| Q| m³/h| 0| 12| 18| 24| 30| 36| 42| 48| 54
---|---|---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 200| 300| 400| 500| 600| 700| 800|
900
–| CB2 – 2CP 40/180C| 2×4| 2×5.5|
H metres
| 65| 63| 60| 55.5| 50| 43| 35| |
–| CB2 – 2CP 40/180B| 2×5.5| 2×7.5| 80| 78| 75| 71|
65.5| 59| 51| 42|
–| CB2 – 2CP 40/180A| 2×7.5| 2×10| 92| 90| 87.5| 84|
79| 73.5| 66| 58| 48
- The data shown in the diagram and tables indicate performance with 2 pumps in operation
PERFORMANCE CURVES
ABSORPTION
TYPE
Single- phase
| VOLTAGE
230 V
---|---
CB2 – 2CPm 25/130| 2 x 6.3 A
CB2 – 2CPm 25/14B| 2 x 7.7 A
CB2 – 2CPm 25/16C| 2 x 7.7 A
CB2 – 2CPm 25/16B| 2 x 10.0 A
TYPE
Three- phase
| VOLTAGE
400 V
---|---
CB2 – 2CP 25/14B| 2 x 3.1 A
CB2 – 2CP 25/16C| 2 x 3.1 A
CB2 – 2CP 25/16B| 2 x 4.0 A
CB2 – 2CP 25/16A| 2 x 5.3 A
CB2 – 2CP 32/200C| 2 x 7.4 A
CB2 – 2CP 32/200B| 2 x 10.5 A
CB2 – 2CP 32/210B| 2 x 12.5 A
CB2 – 2CP 32/210A| 2 x 16.0 A
CB2 – 2CP 40/180C| 2 x 9.8 A
CB2 – 2CP 40/180B| 2 x 12.3 A
CB2 – 2CP 40/180A| 2 x 15.4 A
DIMENSIONS AND WEIGHT
TYPE | PORTS | DIMENSIONS mm | kg |
---|---|---|---|
Single- phase | Three- phase | DN1 | DN2 |
h1 | h2 | 1~ | 3~ |
CB2 – 2CPm 25/130 | – | **** |
2″
| ****
1½”
| 727| ****
530
| 337| ****
270
| ****
510
| ****
674
| 152| 390| 60.0| –
CB2 – 2CPm 25/14B| CB2 – 2CP 25/14B| ****
752
| ****
346
| ****
153
| ****
413
| 72.0| 73.0
CB2 – 2CPm 25/16C| CB2 – 2CP 25/16C| 73.0|
73.0
CB2 – 2CPm 25/16B| CB2 – 2CP 25/16B| ****
761
| ****
170
| ****
451
| 80.0| 80.0
–| CB2 – 2CP 25/16A| –| 86.0
–| CB2 – 2CP 32/200C| ****
3″
| ****
2″
| ****
972
| ****
700
| ****
453
| ****
370
| ****
712
| ****
192
| ****
516
| –| 129.0
–| CB2 – 2CP 32/200B| –| 135.0
–| CB2 – 2CP 32/210B| ****
977
| ****
456
| ****
199
| ****
546
| –| 161.0
–| CB2 – 2CP 32/210A| –| 171.0
–| CB2 – 2CP 40/180C| ****
DN 100
4″
| ****
DN 80
3″
| ****
1048
| ****
468
| ****
774
| ****
716
| ****
590
| –| 190.0
–| CB2 – 2CP 40/180B| –| 199.0
–| CB2 – 2CP 40/180A| –| 211.0
FIELD AND PERFORMANCE DATA
TYPE| POWER (P2)| Q| m³/h| 0| 0.6| 1.2| 2.4| 3.6| 4.8| 6|
7.2| 8.4| 9.6| 10.8| 12| 13.2| 14.4| 15.6
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 10| 20| 40| 60| 80| 100| 120|
140| 160| 180| 200| 220| 240| 260
CB2 – 5CRm 80| CB2 – 5CR 80| 2×0.75| 2×1|
H metres
| 67| 66| 64| 59| 53| 45.5| 37.5| 29.5| 20.5| 12| | | | |
CB2 – 4CRm 100| CB2 – 4CR 100| 2×0.75| 2×1| 50| 50|
49| 47| 45| 42| 39.5| 37| 34| 30.5| 26.5| 22| 17| 11| 5
CB2 – 5CRm 100| CB2 – 5CR 100| 2×0.90| 2×1.25|
63| 62| 61.5| 59.5| 57| 53.5| 50.5| 46.5| 42.5| 38| 33| 28| 22| 15| 8
Q = Flow rate H = Total manometric head Performance curves comply with EN ISO 9906 Grade 3B tolerance limits.
The data shown in the diagram and tables indicate performance with 2 pumps in operation
ABSORPTION
TYPE
Single- phase
| VOLTAGE
230 V
---|---
CB2 – 5CRm 80| 2 x 5.5 A
CB2 – 4CRm 100| 2 x 5.8 A
CB2 – 5CRm 100| 2 x 6.8 A
TYPE
Three- phase
| VOLTAGE
400 V
---|---
CB2 – 5CR 80| 2 x 2.5 A
CB2 – 4CR 100| 2 x 2.3 A
CB2 – 5CR 100| 2 x 2.5 A
PERFORMANCE CURVES
DIMENSIONS AND WEIGHT
TYPE | PORTS | DIMENSIONS mm | kg |
---|---|---|---|
Single- phase | Three- phase | DN1 | DN2 |
h1 | h2 | 1~ | 3~ |
CB2 – 5CRm 80 | CB2 – 5CR 80 | 1½” | 1½” |
760 | 530 | 370 | 270 |
CB2 – 4CRm 100 | CB2 – 4CR 100 | 2″ | 1½” |
803
| ****
530
| ****
408
| ****
270
| ****
510
| ****
674
| ****
192
| ****
373
| 54| 55
CB2 – 5CRm 100| CB2 – 5CR 100| 56| 55
FIELD AND PERFORMANCE DATA
TYPE| POWER P2| Q| m³/h| 0| 0.6| 1.2| 2.4| 4.8| 7.2| 9.6|
10.8| 12| 13.2| 14.4| 15.6
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 10| 20| 40| 80| 120| 160| 180|
200| 220| 240| 260
CB2 – FCRm 80/5| –| 2×0.75| 2×1|
H metres
| 67| 66| 64| 59| 45.5| 29.5| 12| | | | |
CB2 – FCRm 100/4| –| 2×0.75| 2×1| 50| 50| 49| 47| 42| 37| 30.5|
26.5| 22| 17| 11| 5
CB2 – FCRm 100/5| CB2 – FCR 100/5| 2×1.1| 2×1.5| 63|
62| 61.5| 59.5| 53.5| 46.5| 38| 33| 28| 22| 15| 8
CB2 – FCRm 90/5| CB2 – FCR 90/5| 2×1.1| 2×1.5| 81| 80|
79| 77| 71| 62.5| 51| 44| | | |
CB2 – FCRm 130/4| CB2 – FCR 130/4| 2×1.5| 2×2| 68.5|
68.5| 68| 67| 65| 62| 57.5| 55| 52| 48| 45| 41
–| CB2 – FCR 130/5| 2×1.8| 2×2.5| 86| 85| 85| 84| 81|
77| 72| 68.5| 65| 73| 67| 51.5
TYPE| POWER P2| Q| m³/h| 0| 6| 12| 24| 36| 42| 48
---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 100| 200| 400| 600| 700| 800
–| CB2 – FCR 15/3| 2×4| 2×5.5|
H metres
| 72| 70| 68.5| 61| 48| 38.5| 27
–| CB2 – FCR 15/4| 2×5.5| 2×7.5| 96| 94| 91| 81| 64|
51.5| 36
The data shown in the diagram and tables indicate performance with 2 pumps in operation
PERFORMANCE CURVES
ABSORPTION
TYPE
Single- phase
| VOLTAGE
230 V
---|---
CB2 – FCRm 80/5| 2 x 5.5 A
CB2 – FCRm 100/4| 2 x 5.8 A
CB2 – FCRm 100/5| 2 x 6.8 A
CB2 – FCRm 90/5| 2 x 9.0 A
CB2 – FCRm 130/4| 2 x 10.3 A
TYPE
Three- phase
| VOLTAGE
400 V
---|---
CB2 – FCR 100/5| 2 x 2.5 A
CB2 – FCR 90/5| 2 x 3.5 A
CB2 – FCR 130/4| 2 x 4.0 A
CB2 – FCR 130/5| 2 x 5.0 A
CB2 – FCR 15/3| 2 x 8.8 A
CB2 – FCR 15/4| 2 x 11.2 A
DIMENSIONS AND WEIGHT
TYPE | PORTS | DIMENSIONS mm | kg |
---|---|---|---|
Single- phase | Three- phase | DN1 | DN2 |
h1 | h2 | 1~ | 3~ |
CB2 – FCRm 80/5 | – | 1½” | 1½” |
530
| 364| ****
270
| ****
510
| ****
674
| ****
182
| ****
368
| 53| –
CB2 – FCRm 100/4| –| ****
2″
| ****
1½”
| ****
715
| ****
401
| 56| –
CB2 – FCRm 100/5| CB2 – FCR 100/5| 56| 56
CB2 – FCRm 90/5| CB2 – FCR 90/5| 805| ****
700
| ****
339
| ****
370
| ****
205
| ****
394
| 82| 83
CB2 – FCRm 130/4| CB2 – FCR 130/4| 779| 82| 83
–| CB2 – FCR 130/5| 805| –| 90
–| CB2 – FCR 15/3| DN 100
4″
| DN 80
3″
| 1058| ****
700
| 569| ****
490
| ****
774
| ****
704
| ****
211
| ****
565
| –| 179
–| CB2 – FCR 15/4| 1102| 613| –| 191
FIELD AND PERFORMANCE DATA
TYPE| POWER P2| Q| m³/h| 0| 1.2| 2.4| 4.8| 7.2| 9.6| 12.0|
14.4| 16.8| 19.2| 21.6
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 20| 40| 80| 120| 160| 200| 240|
280| 320| 360
CB2 – MKm 3/3| CB2 – MK 3/3| 2×0.75| 2×1|
H metres
| 52.5| 51.5| 50| 45| 38.5| 29| | | | |
CB2 – MKm 3/5| CB2 – MK 3/5| 2×1.1| 2×1.5| 87| 85| 83| 75| 64| 48|
| | | |
CB2 – MKm 3/6| CB2 – MK 3/6| 2×1.5| 2×2| 105| 103| 100| 90| 77| 58|
| | | |
CB2 – MKm 5/4| CB2 – MK 5/4| 2×0.75| 2×1| 57| –| 54| 50| 45| 37.5|
28.5| 17| | |
CB2 – MKm 5/5| CB2 – MK 5/5| 2×1.1| 2×1.5| 71| –| 67.5| 62.5| 56|
47| 35.5| 21.5| | |
CB2 – MKm 5/7| CB2 – MK 5/7| 2×1.5| 2×2| 99| –| 95| 88| 78| 66| 50|
30| | |
CB2 – MKm 5/8| CB2 – MK 5/8| 2×2.2| 2×3| 114| –| 108| 100| 90| 75|
57| 34| | |
CB2 – MKm 8/4| CB2 – MK 8/4| 2×1.1| 2×1.5| 56| –| –| 53.5| 51|
47.5| 43| 37.5| 30.5| 22.1| 12
CB2 – MKm 8/5| CB2 – MK 8/5| 2×1.5| 2×2| 70| –| –| 67| 64| 59.5|
54| 47| 38| 27.5| 15.5
CB2 – MKm 8/6| CB2 – MK 8/6| 2×2.2| 2×3| 84| –| –| 80| 77| 72|
64.5| 56| 45.5| 33| 18.5
- The data shown in the diagram and tables indicate performance with 2 pumps in operation
PERFORMANCE CURVES
ABSORPTION
TYPE
Single- phase
| VOLTAGE
230 V
---|---
CB2 – MKm 3/3| 2 x 5.7 A
CB2 – MKm 3/5| 2 x 7.8 A
CB2 – MKm 3/6| 2 x 9.5 A
CB2 – MKm 5/4| 2 x 5.7 A
CB2 – MKm 5/5| 2 x 7.1 A
CB2 – MKm 5/7| 2 x 9.3 A
CB2 – MKm 5/8| 2 x 10.0 A
CB2 – MKm 8/4| 2 x 7.8 A
CB2 – MKm 8/5| 2 x 9.7 A
CB2 – MKm 8/6| 2 x 11.1 A
TYPE
Three- phase
| VOLTAGE
400 V
---|---
CB2 – MK 3/3| 2 x 2.5 A
CB2 – MK 3/5| 2 x 3.0 A
CB2 – MK 3/6| 2 x 3.5 A
CB2 – MK 5/4| 2 x 2.5 A
CB2 – MK 5/5| 2 x 2.7 A
CB2 – MK 5/7| 2 x 3.5 A
CB2 – MK 5/8| 2 x 4.3 A
CB2 – MK 8/4| 2 x 3.0 A
CB2 – MK 8/5| 2 x 3.5 A
CB2 – MK 8/6| 2 x 4.5 A
DIMENSIONS AND WEIGHT
TYPE | PORTS | DIMENSIONS mm | kg |
---|---|---|---|
Single- phase | Three- phase | DN1 | DN2 |
h1 | h2 | 1~ | 3~ |
CB2 – MKm 3/3 | CB2 – MK 3/3 | **** |
2″
| ****
1½”
| ****
673
| ****
530
| ****
135
| ****
270
| ****
510
| ****
854
| ****
102
| 234| 75.0| 73.0
CB2 – MKm 3/5| CB2 – MK 3/5| 288| 76.0| 77.0
CB2 – MKm 3/6| CB2 – MK 3/6| 315| 80.0| 81.0
CB2 – MKm 5/4| CB2 – MK 5/4| 261| 76.0| 74.0
CB2 – MKm 5/5| CB2 – MK 5/5| 288| 76.0| 77.0
CB2 – MKm 5/7| CB2 – MK 5/7| 342| 81.0| 81.0
CB2 – MKm 5/8| CB2 – MK 5/8| 369| 82.0| 82.0
CB2 – MKm 8/4| CB2 – MK 8/4| ****
2½”
| ****
719
| ****
171
| 261| 80.0| 81.0
CB2 – MKm 8/5| CB2 – MK 8/5| 288| 81.0| 81.0
CB2 – MKm 8/6| CB2 – MK 8/6| 315| 87.0| 87.0
FIELD AND PERFORMANCE DATA
TYPE| POWER (P2)| Q| m³/h| 0| 0.6| 1.2| 2.4| 4.8| 7.2|
9.6| 10.8
---|---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 10| 20| 40| 80| 120| 160| 180
CB2 – HTm 3/4| CB2 – HT 3/4| 2×0.75| 2×1|
H metres
| 65| 65| 63.5| 62| 57| 50| 40.5| 35
CB2 – HTm 3/5| CB2 – HT 3/5| 2×1.1| 2×1.5| 81| 80| 79| 77| 71|
62.5| 51| 44
CB2 – HTm 3/6| CB2 – HT 3/6| 2×1.5| 2×2| 97| 96| 95| 93| 86| 75|
61| 52
–| CB2 – HT 3/7| 2×1.8| 2×2.5| 113| 112| 111| 108| 100| 88| 71| 61
TYPE| POWER (P2)| Q| m³/h| 0| 0.6| 1.2| 2.4| 4.8| 7.2|
9.6| 10.8| 12| 15.6
---|---|---|---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 10| 20| 40| 80| 120| 160| 180|
200| 260
CB2 – HTm 5/2| CB2 – HT 5/2| 2×0.75| 2×1|
H metres
| 35| 35| 32.7| 32.3| 32.5| 31| 25.5| 27.5| 26| 20.5
CB2 – HTm 5/3| CB2 – HT 5/3| 2×1.1| 2×1.5| 51.5| 51.5| 51| 50.5|
49| 46.5| 43| 41| 39| 31
CB2 – HTm 5/4| CB2 – HT 5/4| 2×1.5| 2×2| 68.5| 68.5| 68| 67| 65|
62| 57.5| 55| 52| 41
–| CB2 – HT 5/5| 2×1.8| 2×2.5| 86| 85| 85| 84| 81| 77| 72| 68.5|
65| 51.5
–| CB2 – HT 5/6| 2×2.2| 2×3| 103| 103| 102| 101| 98| 93| 86| 82|
78| 62
TYPE| POWER (P2)| Q| m³/h| 0| 2.4| 4.8| 7.2| 9.6| 12|
14.4| 16.8| 19.2| 21.6| 24
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 40| 80| 120| 160| 200| 240| 280|
320| 360| 400
CB2 – HTm 8/3| CB2 – HT 8/3| 2×1.1| 2×1.5|
H metres
| 47| 46.5| 45.5| 44| 42| 39.5| 36.5| 32.5| 28| 23.1| 17
CB2 – HTm 8/4| CB2 – HT 8/4| 2×1.5| 2×2| 62.5| 62| 60.5| 58.5| 56|
53| 48.5| 43.5| 37.5| 31| 23
–| CB2 – HT 8/5| 2×1.8| 2×2.5| 78| 77.5| 76| 73| 70| 66| 61| 54.5|
47| 38.5| 28.5
–| CB2 – HT 8/6| 2×2.2| 2×3| 94| 93| 91| 88| 84| 79| 73| 65.5|
56.5| 46| 34.5
–| CB2 – HT 8/7| 2×3| 2×4| 109| 108| 106| 103| 98| 92| 85| 76| 66|
54| 40
TYPE| POWER (P2)| Q| m³/h| 0| 3.6| 6| 7.2| 9.6| 14.4| 18|
20.4| 24| 26.4| 30
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 60| 100| 120| 160| 240| 300| 340|
400| 440| 500
CB2 – HTm 10/3| CB2 – HT 10/3| 2×1.5| 2×2|
H metres
| 47| 45.5| 44| 43.5| 42| 38| 33.5| 30.5| 24.7| 20.3| 13
CB2 – HTm 10/4| CB2 – HT 10/4| 2×1.8| 2×2.5| 62| 61| 59| 58| 56|
50.5| 45| 40.5| 33| 27| 18
–| CB2 – HT 10/5| 2×2.2| 2×3| 77| 75.5| 74| 73| 70| 63| 56| 50.5|
41| 34| 21.5
–| CB2 – HT 10/6| 2×3| 2×4| 93| 91| 88| 87| 84| 76| 67.5| 61| 49.5|
40.5| 26
–| CB2 – HT 10/7| 2×3| 2×4| 108| 106| 103| 102| 98| 88| 79| 71|
57.5| 47.5| 30
TYPE| POWER (P2)| Q| m³/h| 0| 6| 12| 24| 36| 42| 48
---|---|---|---|---|---|---|---|---|---|---
Single- phase| Three- phase| kW| HP| l/min|
0| 100| 200| 400| 600| 700| 800
–| CB2 – HT 15/3| 2×4| 2×5.5| H metres| 72| 70| 68.5| 61| 48|
38.5| 27
–| CB2 – HT 15/4| 2×5.5| 2×7.5| 96| 94| 91| 81| 64| 51.5| 36
PERFORMANCE CURVES
ABSORPTION
TYPE
Single- phase
| VOLTAGE
230 V
---|---
CB2 – HTm 3/4| 2 x 7.5 A
CB2 – HTm 3/5| 2 x 9.0 A
CB2 – HTm 3/6| 2 x 10.5 A
CB2 – HTm 5/2| 2 x 6.1 A
CB2 – HTm 5/3| 2 x 8.5 A
CB2 – HTm 5/4| 2 x 10.3 A
CB2 – HTm 8/3| 2 x 8.7 A
CB2 – HTm 8/4| 2 x 10.5 A
CB2 – HTm 10/3| 2 x 9.5 A
CB2 – HTm 10/4| 2 x 11.0 A
TYPE
Three- phase
| VOLTAGE
400 V
---|---
CB2 – HT 3/4| 3.0 A
CB2 – HT 3/5| 3.5 A
CB2 – HT 3/6| 4.0 A
CB2 – HT 3/7| 4.8 A
TYPE
Three- phase
| VOLTAGE
400 V
---|---
CB2 – HT 5/2| 2 x 2.8 A
CB2 – HT 5/3| 2 x 3.2 A
CB2 – HT 5/4| 2 x 3.8 A
CB2 – HT 5/5| 2 x 4.8 A
CB2 – HT 5/6| 2 x 5.2 A
CB2 – HT 8/3| 2 x 3.3 A
CB2 – HT 8/4| 2 x 4.0 A
CB2 – HT 8/5| 2 x 4.8 A
CB2 – HT 8/6| 2 x 5.4 A
CB2 – HT 8/7| 2 x 7.0 A
CB2 – HT 10/3| 2 x 3.4 A
CB2 – HT 10/4| 2 x 4.5 A
CB2 – HT 10/5| 2 x 5.2 A
CB2 – HT 10/6| 2 x 6.5 A
CB2 – HT 10/7| 2 x 7.2 A
CB2 – HT 15/3| 2 x 8.8 A
CB2 – HT 15/4| 2 x 11.2 A
DIMENSIONS AND WEIGHT
TYPE | PORTS | DIMENSIONS mm | kg |
---|---|---|---|
Single- phase | Three- phase | DN1 | DN2 |
h1 | h2 | 1~ | 3~ |
CB2 – HTm 3/4 | CB2 – HT 3/4 | **** |
2″
| ****
2″
| ****
732
| ****
530
| ****
614
| ****
270
| ****
510
| 674| ****
135
| 569| 99| 100
CB2 – HTm 3/5| CB2 – HT 3/5| 595| 100| 100
CB2 – HTm 3/6| CB2 – HT 3/6| 854| 621| 102| 102
–| CB2 – HT 3/7| 667| –| 112
CB2 – HTm 5/2| CB2 – HT 5/2| ****
2″
| ****
2″
| ****
779
| ****
530
| ****
661
| ****
270
| ****
510
| ****
674
| ****
135
| 517| 99| 100
CB2 – HTm 5/3| CB2 – HT 5/3| 543| 99| 100
CB2 – HTm 5/4| CB2 – HT 5/4| 569| 103| 104
–| CB2 – HT 5/5| 854| 615| –| 109
–| CB2 – HT 5/6| 641| –| 111
CB2 – HTm 8/3| CB2 – HT 8/3| ****
2½”
| ****
2½”
| ****
873
| ****
530
| ****
738
| | ****
270
| ****
521
| 674| ****
140
| 548| 106| 107
CB2 – HTm 8/4| CB2 – HT 8/4| 574| 110| 111
–| CB2 – HT 8/5| 854| 620| –| 119
–| CB2 – HT 8/6| 646| –| 120
–| CB2 – HT 8/7| 700| | 370| 674| 724| –| 145
CB2 – HTm 10/3| CB2 – HT 10/3| ****
2½”
| ****
2½”
| ****
873
| ****
530
| ****
738
| ****
270
| ****
521
| 674| ****
140
| 548| 107| 107
CB2 – HTm 10/4| CB2 – HT 10/4| 594| 111| 111
–| CB2 – HT 10/5| 854| 620| –| 119
–| CB2 – HT 15/3| 3″| 3″| 993| 700| 850| 370| 728| 674|
150| 693| –| 175
–| CB2 – HT 15/4| 737| –| 187
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>