Kaysun KHP-MO 26 DTP Thermo Comfort Instruction Manual
- July 20, 2024
- Kaysun
Table of Contents
- Kaysun KHP-MO 26 DTP Thermo Comfort
- Product Usage Instructions
- FAQs
- SAFETY PRECAUTIONS
- GENERAL INTRODUCTION
- SAFETY ZONE
- UNIT INSTALLATION
- HYDRAULIC INSTALLATION
- ELECTRICAL INSTALLATION
- INSTALLATION OF WIRED CONTROLLER
- CONFIGURATION
- COMMISSIONING
- MAINTENANCE
- TECHNICAL DATA
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Kaysun KHP-MO 26 DTP Thermo Comfort
Product Usage Instructions
Safety Precautions:
Before starting any work or operation, ensure to observe the basic safety regulations outlined in the manual.
System Design:
Understand the system design as detailed in the manual before proceeding with installation.
Unit Installation:
Follow the step-by-step instructions provided in sections 4 and 5 of the manual for proper unit installation.
Hydraulic Installation:
For hydraulic installation, refer to section 6 of the manual for detailed guidance.
Electrical Installation:
Section 7 of the manual contains instructions for electrical installation. Follow these carefully to ensure proper setup.
Installation of Wired Controller:
For installing the wired controller, follow the guidelines outlined in section 8 of the manual.
Maintenance:
Refer to section 13 of the manual for maintenance instructions to keep the product in optimal condition.
FAQs
- Q: Who is the target group for these instructions?
- A: The instructions are exclusively intended for qualified contractors and authorized installers. Ensure only those individuals handle the installation and setup process.
INSTALLATION MANUAL
Aquantia KHP-MO HT HP
KHP-MO 26 DTP
KHP-MO 30 DTP
KHP-MO 35 DTP
Please read this manual carefully and keep it for future reference. All the pictures in this manual are for illustrations purpose only.
SAFETY PRECAUTIONS
Observe the basic safety regulations before starting work and operation.
DANGER
It indicates a hazard with a high level of risk which, if not avoided, will
result in serious injury.
WARNING
It indicates a hazard with a medium level of risk which, if not avoided, could
result in serious injury.
CAUTION
It indicates a hazard with a low level of risk which, if not avoided, could
result in minor or moderate injury.
NOTE
Additional information.
Symbols on the unit
Flammable refrigerant
WARNING
is applied. A fire may occur due to unexpected
leakage of refrigerant.
Read the operation CAUTION manual carefully before
any further action.
Only a specialist is
CAUTION
allowed to take action under the instructions of
the installation manual.
The information is CAUTION available in the relevant
documentation.
Target group
DANGER
These instructions are exclusively intended for qualified contractors and
authorized installers.
· Work on the refrigerant circuit with flammable refrigerant in safety group
A3 may only be carried out by authorized heating contractors. These heating
contractors must be trained in accordance with EN 378 Part 4 or IEC
60335-2-40, Section HH. The certificate of competence from an industry
accredited body is required.
· Brazing/soldering work on the refrigerant circuit may only be carried out by
personnel certified in accordance with ISO 13585 and AD 2000, Datasheet HP
100R. And only contractors qualified and certified for the processes can
perform brazing/ soldering work. The work must fall within the range of
applications purchased and be carried out in accordance with the prescribed
procedures. Soldering/brazing work on accumulator connections requires
certification of personnel and processes by a notified body according to the
Pressure Equipment Directive (2014/68/EU).
· Work on electrical equipment may only be carried out by a qualified
electrician.
· Before initial commissioning, all safetyrelated points must be checked by
the particular certified heating contractors. The system must be commissioned
by the system installer or a qualified person authorized by the installer.
Intended use
There is a risk of injury to the user or others, or of damage to the product
and other property in the event of improper or unintended use.
The product is the outdoor unit of an air-to-water heat pump with monoblock
design.
The product uses the outdoor air as a heat source and can be used to heat a
residential building and generate domestic hot water.
The air that escapes from the product must be able to flow out freely, and
must not be used for any other purposes.
The product is only intended for outdoor installation.
The product is intended exclusively for domestic use, which means that the
following places are not appropriate for installation:
· Where there is mist of mineral oil or oil spray or vapors. Plastic parts may
deteriorate, and cause joint loose and leakage of water.
· Where corrosive gases (such as sulfurous acid gas) are produced, or
corrosion of copper pipes or soldered parts may cause leakage of refrigerant.
· Where there is machinery which emits massive electromagnetic waves. Enormous
electromagnetic waves can disturb the control of the system and cause
equipment malfunction.
· Where flammable gases may leak, carbon fiber or ignitable dust is suspended
in the air or volatile flammables such as paint thinner or gasoline are
handled. These types of gases might cause a fire.
· Where the air contains high levels of salt such as a location near the
ocean.
· Where voltage fluctuates a lot, such as a location in a factory.
· In vehicles or vessels.
· Where acidic or alkaline vapors are present.
Intended use includes the following:
· Observance of the operating instructions included for the product and any
other installation components.
· Compliance with all inspection and maintenance conditions listed in the
instructions.
· Installing and setting up the product in accordance with the product and
system approval.
· Installation, commissioning, inspection, maintenance and troubleshooting by
qualified contractors and authorized installers.
Intended use also covers installation in accordance with the IP code.
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge provided that they have been given supervision or instruction
concerning the use of the appliance in a safe way and understand the hazards
involved. Children should not play with the appliance. Cleaning and
maintenance should not be made by children without supervision
Any other use that is not specified in these instructions, or use beyond that
specified in this document, should be considered as improper use. Any direct
commercial or industrial use is also deemed to be improper.
CAUTION
Improper use of any kind is prohibited. · Do not rinse the unit. · Do not
place any object or equipment on top of
the unit (top plate). · Do not climb, sit or stand on top of the unit.
01
Regulations to be observed
· National installation regulations. · Statutory regulations for the
prevention of accidents. · Statutory regulations for environmental protection.
· Statutory requirements for pressure equipment: Pressure Equipment Directive
2014/68/EU. · Codes of practice of the relevant trade associations. · Relevant
country-specific safety regulations. · Applicable regulations and guidelines
for operation, service, maintenance, repair and safety of cooling, air
conditioning and heat pump systems containing flammable and explosive
refrigerant.
Safety instructions for working on the system
The outdoor unit contains flammable refrigerant R290 (propane C3H8). In case
of a leak, the escaping refrigerant may form a flammable or explosive
atmosphere in the ambient air. A safety zone is defined in the immediate
vicinity of the outdoor unit, in which special rules apply when work is
performed on the appliance. See section “Safety zone”.
Working in the safety zone
DANGER
Risk of explosion: Refrigerant leak may form a flammable or explosive
atmosphere in the ambient air.
· Take the following measures to prevent fire and explosion in the safety
zone:
· Keep ignition sources away, including naked flames, plug sockets, hot
surfaces, light switches, lamps, electrical devices not free of ignition
sources, mobile devices with integrated batteries (such as mobile phones and
fitness watches).
· Do not use any sprays or other combustible gases in the safety zone.
CAUTION
Permissible tools: All tools for working in the safety zone must be designed
and explosion-protected in accordance with the applicable standards and
regulations for refrigerant in safety groups A2L and A3, such as brushless
machines (cordless disposal containers, installation aids, and screwdrivers),
extraction equipment, vacuum pumps, conductive hoses, and mechanical tools of
non-sparking material.
CAUTION
The tools must also be suitable for the pressure ranges in use. Tools must be
in perfect maintenance conditions.
· The electrical equipment must meet the requirements for areas at risk of
explosion, zone 2.
· Do not use flammable materials such as sprays or other flammable gases.
· Before starting work, discharge static electricity by touching earthed
objects, such as heating or water pipes.
· Do not remove, block or bridge safety equipment.
· Do not make any changes: Do not modify the outdoor unit, inlet/ outlet
lines, electrical connections/ cables or the surroundings. Do not remove any
components or seals.
Working on the system
Switch off the power supply for the unit (including all affiliated parts) at a
separate fuse or mains isolator. Check and ensure that the system is no longer
live.
CAUTION
In addition to the control circuit there may be several power circuits.
DANGER
Contact with live components can result in severe injuries. Some components on
PCBs remain live even after the power supply has been switched off. Prior to
removing covers from the appliances, wait at least 4 minutes until the voltage
has completely dropped out.
· Safeguard the system against re-connection. · Wear suitable personal
protective equipment when carrying out any work. · Do not touch any switch or
electrical parts with wet fingers. It may cause electrical shock and
compromise the system.
DANGER
Hot surfaces and fluids can result in burns or scalding. Cold surfaces may
cause frostbite.
· Prior to servicing or maintenance tasks, switch off and allow the equipment
to cool down or warm up.
· Do not touch hot or cold surfaces on the appliance, fittings or pipework.
NOTE
Electronic assemblies can be damaged by electrostatic discharge. Before
beginning work, touch earthed objects, such as heating or water pipes, to
discharge any static.
Safety work area and temporary flammability zones.
CAUTION
When working on systems using flammable refrigerants, the technician should
consider certain locations as “temporary flammable zones”. These are normally
regions where at least some emission of refrigerant is anticipated to occur
during the normal working procedures, such as recovery, charging and
evacuation, typically where hoses may be connected or disconnected. The
technician should ensure three meters safety working area (radius of the unit)
in case of any accidental release of refrigerant that forms a flammable
mixture with air.
Working on the refrigerant circuit
R290 refrigerant (propane) is an air displacing, colorless, flammable,
odorless gas which forms explosive mixtures with air. Refrigerant drained must
be properly disposed of by authorized contractors.
· Perform the following measures before beginning work on the refrigerant
circuit:
· Check the refrigerant circuit for leaks. · Ensure very good ventilation
especially in the floor area and maintain this for the duration of the work. ·
Secure the area surrounding the work area.
02
· Inform the following persons of the type of work to be carried out: All
maintenance personnel All persons in the vicinity of the system.
· Inspect the area immediately around the heat pump for flammable materials
and ignition sources: Remove all flammable materials and ignition sources.
· Before, during and after the work, check the surrounding area for escaping
refrigerant using an explosion-proof refrigerant detector suitable for R290.
This refrigerant detector must not generate any sparks and must be suitably
sealed.
· A CO2 or powder extinguisher must be available in the following cases:
Refrigerant is being drained. Refrigerant is being topped up. Soldering or
welding work is in progress.
· Display signs prohibiting smoking.
DANGER
Escaping refrigerant can lead to fires and explosions that result in very
serious injuries.
· Do not drill or apply heat to a refrigerant circuit filled with refrigerant.
· Do not operate Schrader valves unless a fill valve or extraction equipment
is attached.
· Take measures to prevent electrostatic charge. · Do not smoke. Avoid naked
flames and sparks. Never switch lights or electrical appliances on or off in
environments with naked flames or sparks. · Components that contain or
contained refrigerant must be labeled, and stored in well ventilated areas in
accordance with the applicable regulations and standards.
DANGER
Direct contact with liquid or gaseous refrigerant can cause serious damage to
health such as frostbite and/or burns. There is a risk of asphyxiation if
liquid or gaseous refrigerant is breathed in.
· Prevent direct contact with liquid or gaseous refrigerant.
· Wear personal protective equipment when handling liquid or gaseous
refrigerant.
· Never breathe in any refrigerant vapor.
DANGER
Refrigerant is under pressure: Mechanical loading of lines and components can
cause leaks in the refrigerant circuit. Do not apply loads to the lines or
components, such as supporting or placing tools.
DANGER
Hot or cold metallic surfaces of the refrigerant circuit may cause burns or
frostbite in case of skin contact. Wear personal protective equipment to
protect against burns or frostbite.
NOTE
Hydraulic components may freeze during refrigerant removal. Drain heating
water from the heat pump beforehand.
DANGER
Damage to the refrigerant circuit can cause refrigerant to enter the hydraulic
system. After completion of the work, vent the hydraulic system correctly.
When doing so, ensure the area is sufficiently ventilated.
Installation General
Be sure to use only specified accessories and parts for installation. Failure
to use specified parts may result in water leakage, electric shocks, fires, or
the unit falling from its mount.
Install the unit on a foundation that can withstand its weight. Insufficient
physical strength may cause the unit to fall and possible injury.
Perform specified installation work with full consideration of strong wind,
hurricanes, or earthquakes. Improper installation may result in accidents due
to equipment falling.
Earth the unit and install a ground fault circuit interrupter in accordance
with local regulations. Operating the unit without a proper ground fault
circuit interrupter may cause electric shocks and fires.
Install the power cable at least 3 feet (1 meter) away from televisions or
radios to prevent interference or noise. (Depending on the radio waves, a
distance of 3 feet (1 meter) may not be sufficient to eliminate the noise.)
Any damaged power cord must be replaced by the manufacturer or its service
agent or a similarly qualified person in order to avoid a hazard.
CAUTION
Do not install any air vent valve in the indoor side. Make sure the outlet of
the indoor safety valve leads to the outdoor side. Two situations should be
considered for outdoor installations to prevent damage to the system,
releases, and undesirable consequences:
· Where the equipment is located in an area accessible by members of the
public, and.
· Where the equipment is located in a restricted area, with access to
authorized persons only.
DANGER
Open flames, fires, open ignition sources and smoking are prohibited.
DANGER
Inflammable matters are prohibited.
Frost protection
CAUTION
Freezing can cause damage to the heat pump. · Thermally insulate all the
hydraulic lines. · Antifreeze can be filled in the secondary circuit
in accordance with local regulations and standards.
03
Connecting cables
DANGER
With short electrical cables, should there be leakage in the refrigerant
circuit, gaseous refrigerant may reach the inside of the building. Min. length
of the electrical connecting cables between the indoor and the outdoor unit: 3
m.
Repair work
CAUTION
Repairing components that fulfil a safety function can compromise the safe
operation of the system.
· Replace faulty components only with genuine spare parts from the
manufacturer.
· Do not undertake any repairs on the inverter. Replace the inverter if there
is a defect.
· Repair work should not be performed in the field. Repair the unit in a
specified location.
Auxiliary components, spare and wearing parts
CAUTION
Spare and wearing parts that have not been tested together with the system can
compromise the function of the system. Installing nonauthorized components and
making non-approved modifications or conversions can compromise the safety and
may invalidate our warranty. Only use original spare parts supplied or
approved by the manufacturer for replacement.
Safety instructions for operating the system What to do if refrigerant leaks
WARNING
To avoid potential risk from refrigerant leak, always keep 2 meters away from
the unit, especially for kids, no matter the unit is in operation or not.
DANGER
Refrigerant leak can lead to fires and explosions that result in very serious
injuries. Breathing in refrigerant may cause asphyxiation.
· Ensure very good ventilation especially in the floor area of the outdoor
unit.
· Do not smoke. Avoid naked flames and sparks. Never switch lights or
electrical appliances on or off in environments with naked flames or sparks.
· Evacuate any people from the dangerous zone. · From a safe position, switch
off the power supply for all system components. · Remove ignition sources from
the dangerous zone. · The system user should know that no ignition source may
be brought into the dangerous zone during the repair. · Repair work must be
carried out by an authorized contractor. · Do not recommission the system
until it is repaired.
CAUTION
Direct contact with liquid or gaseous refrigerant can cause serious damage to
health, e.g. frostbite and/ or burns. Breathing in liquid or gaseous
refrigerant may cause asphyxiation.
· Prevent direct contact with liquid or gaseous refrigerant.
· Never breathe in refrigerant vapors.
What to do if water leaks
DANGER
If water leaks from the appliance, an electric shock may occur. Switch off the
heating system at the external isolator (e.g. fuse box, domestic distribution
board).
CAUTION
If water leaks from the appliance, scalding may occur. Never touch hot water.
What to do if the outdoor unit ices up
CAUTION
A build-up of ice in the condensate pan and in the fan area of the outdoor
unit can cause damage to the equipment.
· Do not use mechanical items/aids to remove ice.
· Before using electrical heating appliances, check the refrigerant circuit
for leaks with a suitable measuring device. The heating appliance should not
be a source of ignition, and must meet the requirements of EN 60335-2-30.
· If ice regularly builds up on the outdoor unit (e.g. in areas where frost
and heavy fog occur frequently), install a fan ring heater (accessory) that is
suitable for refrigerant R290 and/or an electric ribbon heater in the
condensate pan (accessory or factory-fitted device).
Safety instructions for storage of the outdoor unit
The outdoor unit is charged at the factory with refrigerant R290 (propane).
DANGER
Refrigerant leak can lead to fires and explosions that result in very serious
injuries. Breathing in refrigerant may cause asphyxiation. Store the outdoor
unit in the following conditions:
· An explosion prevention plan must be in place for storage.
· Ensure the storage location is well ventilated. · Keep away from ignition
sources (avoid exposure to heat and smoking). · Temperature range for storage:
25 °C to 70 °C · Only store the outdoor unit in its exfactory protective
packaging. · Protect the outdoor unit against damage. · The maximum number of
outdoor units that may be stored in one place is determined according to local
conditions.
04
WARNING
A fire with R290 should only be fought with CO2 or dry powder extinguishers.
About the refrigerant
WARNING
· The following applies to R290 refrigerant systems.
· Prior to work on systems containing flammable refrigerants, safety checks
are necessary to minimize the risk of ignition.
For repair of the refrigerating system, the following precautions should be
complied with prior to conducting work on the system.
Work should be undertaken under a controlled procedure so as to minimize the
risk of a flammable gas or vapor being present while the work is being
performed.
All maintenance staff and others working in the local area should be
instructed on the nature of work being carried out. Work in confined spaces
should be avoided. The area around the workspace should be sectioned off.
Ensure that the area is safe through control of flammable materials.
The area should be checked with an appropriate refrigerant detector prior to
and during work, to ensure the technician is aware of potentially flammable
atmospheres.
Ensure that the leak detection equipment being used is suitable for use with
flammable refrigerants, i.e., the equipment should be non-sparking, adequately
sealed or intrinsically safe. If any hot work is to be conducted on the
refrigeration equipment or any associated parts, appropriate fire
extinguishing equipment should be available to hand. Have a dry powder or CO2
fire extinguisher adjacent to the charging area.
No person carrying out work in relation to a refrigeration system which may
expose any pipe that contains or has contained flammable refrigerant should
use any sources of ignition in such a manner that it may lead to the risk of
fires or explosions. All possible ignition sources, including lighted
cigarettes, should be kept sufficiently far away from the site of
installation, repair, removal and disposal, during which flammable refrigerant
can possibly be released into the surrounding space.
Prior to work, the area around the equipment should be checked to make sure
that there are no flammable hazards or ignition risks. “No Smoking” signs
should be displayed.
Ensure that the area is in the open or adequately ventilated before breaking
into the system or conducting any hot work. A degree of ventilation should
continue during the work. The ventilation should safely disperse any released
refrigerant and preferably expel it externally into the atmosphere.
For any change of the electrical components, they should be fit for the
intended purpose and comply with the correct specifications. Always follow the
manufacturer’s maintenance and service guidelines. In case of any doubt,
consult the manufacturer’s technical department for assistance.
The following checks should be applied to installations using flammable
refrigerants:
· The charge size should depend on the size of the room within which
refrigerant containing components are installed;
· The ventilation machinery and outlets should operate adequately and not be
obstructed;
· If an indirect refrigerating circuit is used, the secondary circuit should
be checked for any refrigerant;
· Marking to the equipment should remain visible and legible. Illegible
markings and signs should be corrected;
· Refrigeration pipes or components should be installed in positions where
they are unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials that
are inherently resistant to corrosion or are suitably protected against
corrosion.
Repair and maintenance of electrical components should include initial safety
checks and component inspection procedures.
In the event of a fault that could compromise safety, no power supply should
be connected to the circuit until it is satisfactorily dealt with. If the
fault cannot be corrected immediately but it is necessary to continue
operation, an adequate temporary solution should be used. This should be
reported to the owner of the equipment to give advises to all parties
involved.
Initial safety checks should include the following:
· Capacitors should be discharged in a safe manner to avoid possibility of
sparking;
· No live electrical components and wiring should be exposed while charging,
recovering or purging the system;
· The earth bonding should be continuous.
During repairs of sealed components, all power supplies should be disconnected
from the equipment where work is in progress prior to any removal of sealed
covers or other components. If it is absolutely necessary to keep a power
supply connected with the equipment during servicing, a permanent leak
detection should be performed at the most critical point to avoid a potential
hazard.
Particular attention should be paid to the following to ensure that the casing
is not altered in such a way that the level of protection is affected by
working on electrical components. This includes damage to cables, an excessive
number of connections, terminals not compliance with original specifications,
damage to seals, and incorrect fitting of glands. Ensure that seals or sealing
materials have not degraded in such a manner that they no longer serve for the
purpose of preventing the ingress of flammable atmospheres. Parts for
replacement should be in accordance with the manufacturer’s specifications. Do
not apply any permanent inductive or capacitance loads that exceed the
permissible voltage or current of the equipment in use to the circuit.
Intrinsically safe components are the only types that can be worked on while
live in the presence of a flammable atmosphere. The test apparatus should be
provided with the correct rating.
Replace components only with parts specified by the manufacturer. Other parts
may result in the ignition of refrigerant in the atmosphere due to a leak.
05
Check and ensure that cabling is free from wear, corrosion, excessive
pressure, vibration, sharp edges or any other adverse environmental effects.
The check should also take into account the effects of ageing or continual
vibration from sources such as compressors or fans.
When breaking into the refrigerant circuit for repair or for any other
purpose follow the conventional procedures. However, it is important to
follow the best practice.
Since flammability is a consideration, the following procedure should be
adhered to:
· Remove the refrigerant;
· Purge the circuit with inert gas;
· Evacuate;
· Purge the circuit again with inert gas;
· Open the circuit by cutting or brazing.
The refrigerant should be recovered into correct recovery cylinders. The
system should be “flushed” with OFN to guarantee the unit safety. This process
may need to be repeated several times. Compressed air or oxygen should not be
used for this task.
Flushing should be achieved by breaking the vacuum in the system with OFN and
continuing to fill until the working pressure is achieved before venting to
the atmosphere and pulling down to a vacuum. This process should be repeated
until no refrigerant exists in the system. When the final OFN charge is used,
the system should be vented down to the atmospheric pressure so that the work
can start.
This operation is absolutely vital if brazing operations on the pipe-work are
to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition
sources and adequate ventilation is available.
Ensure that contamination of different refrigerants does not occur when using
charging equipment. Hoses or lines should be as short as possible to minimize
the amount of refrigerant contained in them. Prior to recharging the system,
it should be pressure tested with OFN.
DD.12 Decommissioning:
Before this procedure starts, it is necessary for the technician to be
completely familiar with the equipment and all its details. It is recommended
that all refrigerants be recovered safely. Prior to the task, an oil and
refrigerant sample should be taken in case analysis is required prior to re-
use of reclaimed refrigerant. It is essential that electrical power is
available before the task is commenced.
a) Be familiar with the equipment and its operation.
b) Isolate the system electrically.
c) Before attempting the procedure, ensure that:
· Mechanical handling equipment is available, if required, for handling
refrigerant cylinders;
· All personal protective equipment is available and being used correctly;
· The recovery process is supervised at all times by a competent person;
· The recovery equipment and cylinders should conform to the appropriate
standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that
refrigerant can be removed from various parts of the system.
f) Make sure that the cylinders are situated on the scales before recovery.
g) Start the recovery machine and operate it in accordance with manufacturer’s
instructions.
h) Do not overfill the cylinders. (No more than 80 % of volume for liquid
charge).
i) Do not exceed the maximum working pressure of the cylinders, even
temporarily.
j) When the cylinders have been filled correctly, make sure that the cylinders
and the equipment are removed from the site promptly and all isolation valves
on the equipment are closed off. k) Recovered refrigerant should not be
charged into another refrigeration system unless it has been cleaned
and checked.
Equipment should be labeled stating that it has been de-commissioned and
emptied of refrigerant. The label should be dated and signed. Ensure that the
equipment is provided with a label stating the existence of flammable
refrigerant in the equipment.
When removing refrigerant from a system, either for servicing or
decommissioning, it is recommended that all refrigerants be removed safely.
Always transfer refrigerant into appropriate cylinders. Ensure that a correct
number of cylinders are available for supporting the total system charge. All
cylinders to be used should be designated for the recovered refrigerant and
labeled for that refrigerant (i.e. special cylinders for the recovery of
refrigerant). The cylinders should be complete with pressure relief valves and
associated shut-off valves in good working conditions. Empty recovery
cylinders should be evacuated and, if possible, cooled down before recovery
occurs.
The recovery equipment should be in good working conditions with a set of
instructions concerning the equipment that is at hand and should be suitable
for the recovery of flammable refrigerants. In addition, a set of calibrated
weighing scales should be available and work properly. Hoses should be
complete with leak-free disconnect couplings and work properly. Before using
the recovery machine, check and ensure that it is in satisfactory working
conditions and has been properly maintained, and that all associated
electrical components are sealed to prevent ignition in the event of a
refrigerant leak. Consult the manufacturer if in in case of any doubt.
The recovered refrigerant should be returned to the refrigerant supplier in
correct recovery cylinders, with the relevant Waste Transfer Note arranged. Do
not mix refrigerants in recovery units and especially not in cylinders. If any
compressor or compressor oils is to be removed, ensure that it has been
evacuated to an acceptable level to ensure that flammable refrigerant does not
remain within the lubricant. The evacuation process should be carried out
prior to returning the compressor to the supplier. To accelerate this process,
you can only heat the compressor body with an electric heater. Draining oil
from the system should ensure the safety.
Warning: Disconnect the appliance from its power source during servicing and
parts replacement.
These units are partial unit air conditioners, complying with partial unit
requirements of this International Standard, and must only be connected to
other units that have been confirmed as complying to corresponding partial
unit requirements of this International Standard.
Leak detection
The following leak detection methods are deemed acceptable for systems
containing flammable refrigerants. Electronic leak detectors should be used to
detect flammable refrigerants, but the sensitivity may not be adequate, or may
need re-calibration. (Detection equipment should be calibrated in a
refrigerant-free area.) Ensure that the detector is not a potential source of
ignition and is suitable for the refrigerant.
06
Leak detection equipment should be set at a percentage of the LFL of the
refrigerant and should be calibrated to be suitable for the refrigerant
employed, with the appropriate percentage of gas (25% maximum) confirmed. Leak
detection fluids should be suitable for most refrigerants but the use of
detergents containing chlorine should be avoided as the chlorine may react
with the refrigerant and corrode the copper pipes. If a leak is suspected, all
naked flames should be removed or extinguished. If a leakage of refrigerant is
found and brazing is required, all of the refrigerant should be recovered from
the system, or isolated (by means of shut off valves) in a part of the system
that is far from the leak. The system should be purged with oxygen free
nitrogen (OFN) both before and during the brazing process.
Disposal
This equipment uses flammable refrigerants. The disposal of the equipment must
comply with national regulations. Do not dispose this product as unsorted
municipal waste. Collection of such waste separately for special treatment is
necessary.
· Do not dispose of electrical appliances as unsorted municipal waste, and use
separate collection facilities. · Contact your local government for
information regarding the collection systems available. If electrical
appliances are disposed of in landfills or dumps, hazardous substances can
leak into the groundwater and get into the food chain, damaging your health
and well-being.
Caution: Risk of fire
GENERAL INTRODUCTION
2.1 Documentation
· Always observe all the operating and installation instructions included with
the system components.
· Hand these instructions and all other applicable documents to the end user.
This document is part of a documentation set. The complete set consists of:
Document
Content
Format
Installation Manual (this manual)
Brief installation instructions
Installation, Operation
and Maintenance Manual
Preparation for the installation, good practices… (more information contained, for installers and advanced users only)
Operation Manual (wired controller)
Quick guide for basic usage
Technical Data Manual
Performance data and ERP information
Paper (in the box next to the outdoor unit)
Digital files..
Paper (in the box next to the outdoor unit) Paper (in the box next to the
outdoor unit)
Online Tools (APP and websites) Refer to the OPERATION MANUAL for more information For the terms and abbreviation, see Annex 3.
2.2 Validity of the Instructions
These instructions apply only to:
3-phase
Unit
26
30
35
Net weight (kg)
260
Wiring specification (mm2) – main power
supply
6-10
6-10
6-10
Minimum flow rate 1.2
1.2
1.2
required (m3/h)
07
2.3 Unpacking
For the accessories box, see 2.4.1 Accessories supplied with the unit for more details.
2.4 Accessories of the Unit
Accessories of the unit
Name
Illustration Quantity Specification
Installation Manual
1
–
Thermistor (T5, Tw2, Tbt)
Drain joint
Technical Data Manual
Operation Manual
Y-shape strainer
Wired controller box
1
–
1
–
1
G1 1/4″
1
–
Energy label
Tie wrap
Paper edge protector
Network matching line
Extension wire for T5, Tw2, Tbt
Harness buckle
Wrench
1
10m
2
32
1
–
13
–
2
–
1
–
1
–
4
–
1
–
08
2.5 Transportation 2.5.1 Dimensions and barycenter
The illustrations below are for 26&30&35 kW units. A, B, and C indicate the
locations of barycenter.
Pass the transport straps through the holes on the left and right sides of the
pallet properly.
No pallet under the unit:
The transport straps can be fitted into foreseen sleeves at the base frame
that are made specifically for this purpose. Using corner protectors under the
unit when lifting the unit.
C E(F)
I
J
M
D A B K LN
H
Model 26 & 30 &35 kW
G (mm)
ABCDE 937 646 985 1816 723
FGH I J K LMN 723 1384 523 193 656 363 117 453 116
2.5.2 Manual transportation
WARNING
Risk of injury from lifting a heavy weight. Lifting weights that are too heavy
may cause injury to the spine, for example.
· Note the weight of the product. · Have four people lift the product.
1. Take into consideration the weight distribution during transportation. The
product is significantly heavier on the compressor side than on the fan motor
side. (see content above for the barycenter) 2. Protect the casing sections
from damage. Using corner protectors under the unit when lift the unit. 3.
After transportation, remove the transport straps. 4. During transportation,
do not tilt the product to an angle larger than 45°.
2.5.3 Lifting
Use lifting tools with transport straps or a suitable hand truck. Unit on the
pallet:
CAUTION
The barycenter of the product and the hook should be kept in a straight line
in the vertical direction to prevent excessive tilting.
09
2.6 About the Unit
2.6.1 Overview
The unit applies to heating, cooling, and DHW scenarios. It can be used
together with fancoil units, floor heating devices, low-temperature high-
efficiency radiators, domestic hot water tanks, and solar kits. The backup
heater can increase the heating capacity at extremely low ambienttemperatures.
It serves as a backup heating source in case of heat pump failureorfreeze
protection of the water pipingoutsidein winter.
2.6.2 Layout
A
B
C
A Fan chamber B Mechanical chamber C Hydraulic module
Fan Main control box Compressor
Inverter control box Hydraulic module
10
2.6.3 Hydraulic module
3
4
12
10
8
1
1 11
5.1 7
6
9
5.2
Code 1
2
3 4 5 6 7 8 9 10 11 12
Assembly Unit
Explanation
Automatic air purge valve Automatically removes the remaining air from the water loop.
Provides additional heating capacities when the heating capacity of the heat
pump
Backup heater (optional) is insufficient due to low outdoor temperature, and
protects the external water pipes from freezing.
Expansion vessel
Balances the water system’s pressure.
Refrigerant gas pipe
/
Temperature sensor
Four temperature sensors determine the water and refrigerant temperature at various points in the water loop: 5.1-TW_out, and 5.2-TW_in
Refrigerant liquid pipe
/
Flow switch
Detects the water flow rate to protect the compressor and water pump in the event of insufficient water flow.
Pump
Circulates water in the water loop.
Plate heat exchanger
Transfers heat from the refrigerant to the water.
Water outlet pipe
/
Pressure relief valve
Prevents excessive water pressure by opening when the pressure reaches 3 bar and discharging water from the water loop.
Water inlet pipe
/
11
2.6.4 Operating range
In cooling mode, the product works at an outdoor temperature of -15 to 48°C.
T4
50
45
40
35
30
25
20
15
10
5
0
-5
-10
-15
-20
5 10 15 20 25 30 35 10 40 45 50 55 60 TW_OUT
Operating range of heat pump with possible limitation and protection.
TW_OUT leaving water temperature
T4 outdoor ambient temperature
In heating mode, the product works at an outdoor temperature of -25 to 43°C
T4
45 40 35 30 25 20 15 10 5 0 -5 -10 -15 -20 -25
5 10 15 20 25 30 35 10 40 45 50 55 60 65 70 75 80 85 90 T1 In case of valid
IBH/AHS settings, only the IBH/AHS turns on; In case of invalid IBH/AHS
settings, only the heat pump turns on. Limitation and protection may occur
during heat pump operation. Operating range of heat pump with possible
limitation and protection. The heat pump remains off, and only the IBH/AHS
turns on.
The water system flow in this area should reach 1.2m³/h. Maximum inlet water
temperature line for heat pump operation.
T1 leaving water temperature T4 outdoor ambient temperature
In DHW mode, the product works at an outdoor temperature of -25 to 43°C
T4
45 40 35 30 25 20 15 10 5 0 -5 -10 -15 -20 -25
5 10 15 20 25 30 35 10 40 45 50 55 60 65 70 75 80 T5
In case of valid TBH/IBH/AHS settings, only the TBH/IBH/AHS turns on; In case
of invalid TBH/IBH/AHS settings, only the heat pump turns on. Limitation and
protection may occur during heat pump operation. Operating range of heat pump
with possible limitation and protection. The heat pump remains off, and only
the TBH/IBH/AHS turns on.
T5 DHW tank temperature T4 outdoor ambient temperature
12
SAFETY ZONE
The refrigerant circuit in the outdoor unit contains easily flammable
refrigerant in safety group A3 as described in ISO 817 and ANSI/ASHRAE
Standard 34. Therefore, a safety zone is defined in the immediate vicinity of
the outdoor unit, in which special requirements apply. Note that this
refrigerant has a higher density than air. In the event of a leak, escaping
refrigerant may be collected near the earth. The following conditions must be
avoided within the safety zone:
· Building openings such as windows, doors, light wells, and flat roof
windows;
· Outdoor air and exhaust air apertures of ventilation and air conditioning
systems;
· Property boundaries, neighboring properties, footpaths, and driveways;
· Pump shafts, inlets to waste water systems, downpipes, and waste water
shafts, etc.;
· Other slopes, troughs, depressions, and shafts; · Electrical house supply
connections; · Electrical systems, sockets, lamps, and light switches;
Snowfall from roofs. Do not introduce ignition sources into the safety zone: ·
Naked flames or burner gauze assemblies. · Grills. · Tools that generate
sparks. · Electrical devices not free of ignition sources, mobile devices with
integrated batteries (such as mobile phones and fitness watches). · Objects
with a temperature of above 360°C.
NOTE
The particular safety zone is dependent on the surroundings of the outdoor
unit.
· The safety zones below are shown with floor standing installation. These
safety zones also apply to other types of installation.
Freestanding positioning of the outdoor unit
A
A Safety zone Corner positioning of the outdoor unit, left
2400mm
A
2900mm
300mm 500mm 500mm 500mm
1800mm
1000mm
A Safety zone Siting the outdoor unit in front of an external wall
2400mm
A
3400mm
300mm
1000mm
13
UNIT INSTALLATION
For ground installation and flat roof clearance single unit General
A B
Obstacle over the top
E D
F
E D
C
G
H
No obstacle over the top
C F
C
F
X(X<A) Wall height unrestricted
I
H
26-35 kW
A Unit height + B D 500
B 100* C 1000
E 500 F 300
(mm)
G 500 H 500 I 500
- In case of cold weather, take into account of snow on the ground. For more information, refer to 5.5 In Cold Climates.
For cascade application installation clearance, refer to the INSTALLATION, OPERATION AND MAINTENANCE MANUAL.
14
UNIT INSTALLATION
5.1 General Rules
In addition to “Safety zone”, the following conditions should be observed.
Environment · For the sake of safety and unit performance, the
installation site must be with sufficient air flow. · For maintenance and
service purposes, the
installation site should be highly accessible. · Impact protection measures
should be taken, if the
installation site has high impact risks, such as a vehicle shunting area.
· Keep the unit away from flammable substances or flammable gases.
· Keep the unit away from heat sources. · Keep the unit as far away from
raindrops as possible. · Do not expose the outdoor unit to any dirty, dusty or
corrosive atmosphere. · Keep the unit away from ventilation openings or
ventilation ducts.
Nature Be ware of the impact from the nature:
· Plants with vines could block the air inlet and outlet of the unit as they
grow.
· Fallen leaves could block the unit air inlet or stuck the air channel.
· Insects, snakes or some small animals might enter the unit. Wild animals
might bite or damage the piping and wiring of the unit.
NOTE
In case of any evidence of animal effects, ask professionals for inspection
and maintenance.
Strong wind · When installing the unit in a place exposed to strong
wind, pay special attention to the following: A wind speed of 5 m/s or higher
against the unit’s air outlet could cause a short circuit (suction of
discharge air), which may have the following consequences: – Deterioration of
the operational capacity. – Frequent frosting in heating operation. –
Disruption of operation due to pressure rise. – When strong wind blows
continuously on the front of the unit, the propeller could start rotating very
fast until it breaks.
Noise impact · Select an installation site that is as far away from
living rooms and bedrooms as possible. · Please note the noise emissions.
Select an
installation site that is as far away from the windows of adjacent buildings
as possible. Installation by the sea
· If the installation site is in the immediate vicinity of a coastline, ensure
that the product is protected against spraying water by an additional
protection device.
· Wind from the sea brings saline substances to the land. This could have
negative impacts on the unit due to long-time exposure to the saline
substances. To prolong the lifetime of the unit, ask professionals for a
customized maintenance proposal, and follow the proposal. Altitude
· The unit is designed to be used below 2000 m of altitude. If it is installed
above this level, its performance and reliability cannot be guaranteed.
5.2 Installation Site
The product is suitable for installation on a ground, wall or flat roof.
NOTE
Installation on a pitched roof (inclined place) is not permitted.
B
(A) Installation on a ground (B) Installation on a flat roof
5.2.1 Precautions for installation on a ground
· Avoid any installation site that is in the corner of a room, between walls
or between fences.
· Prevent the return intake of air from the air outlet. · Ensure that water
cannot accumulate on the subsoil. · Ensure that the subsoil can absorb water
well. · Plan a bed of gravel and rubble for the condensate discharge. · Select
an installation site that is free from significant accumulations of snow in
winter. · Select an installation site at which the air inlet is not affected
by strong wind. Position the unit crosswise to the wind direction whenever it
is possible. · If the installation site is not protected against wind, a
protective wall is required. · Please note the noise emissions. Avoid corners
of rooms, recesses or sites between walls. · Select an installation site with
excellent sound absorption performance such as those with grass, hedges or
fencing. · Route the hydraulic lines and electrical wires underground. ·
Provide a safety pipe that leads from the outdoor unit through the wall of the
building.
15
5.2.2 Precautions for installation on a flat roof
· Only install the product in a building with a solid construction structure
and that has cast concrete ceilings throughout.
· Do not install the product in any building with a wooden structure or with a
lightweight roof.
· Select an installation site that is easily accessible so that foliage or
snow can be regularly removed from the product.
· Select an installation site at which the air inlet is not affected by strong
wind. Position the unit crosswise to the wind direction whenever it is
possible.
· If the installation site is not protected against wind, a protective wall is
required.
· Please note the noise emissions. Maintain a sufficient clearance from
adjacent buildings.
· Route the hydraulic lines and electrical wires. · Provide a wall duct.
5.2.3 Occupational safety
Installation on a flat roof · Ensure that the flat roof can be safely
accessed. · Maintain a safety area that is 2 m from falling edges,
and a clearance that is required for working on the product. The safety area
must be inaccessible.
· If this is not possible, install technical falling protections at the
falling edges such as reliable railings. Alternatively, set up technical
safety equipment such as scaffolding or safety nets.
· Maintain a sufficient clearance from any roof escape hatches and flat-roof
windows. Use suitable protective equipment (e.g. barriers) to prevent people
from stepping on or falling through any escape hatches and flat-roof windows.
5.3 Foundation and Unit Installation
5.3.1 Installation on a ground
Installation on a soft ground In case of installation on a soft ground such as
lawn and soil, create a foundation as shown in the figure below.
1
Ø100
2
B
4
300
3
A
100
1400
- Downpipe for drainage 2) Strip foundations 3) Water-permeable coarse rubble
- Concrete strip foundations
· Dig a hole in the ground. For the location of the downpipe, refer to 5.4.1 Drain hole position.
· Insert a downpipe (1) to divert the condensate. · Add a layer of water- permeable coarse rubble (3). · Calculate the depth (A) in accordance with local conditions. · Region with ground frost: minimum depth: 900 mm · Region without ground frost: minimum depth: 600 mm
· Calculate the height (B) in accordance with local conditions. Such height
should not be smaller than 100 mm.
· Create three concrete strip foundations (4). The recommended dimensions can
be found in the figure.
· Make sure the three foundations are level. · There are no restrictions on
the width or length of the foundations, provided that the unit can be mounted
on the foundation properly and the downpipe for drainage is not blocked. · Add
a gravel bed between and beside the strip foundations (2) to divert the
condensate.
Installation on a solid ground In case of installation on a solid ground such
as concrete, create a concrete strip foundation comparable to what is
described in the section above. The height of the strip foundation should not
be smaller than 100 mm.
Unit mounting Installation with foundation: Fix the unit with foundation
bolts. (Six sets of 10 expansion bolts, nuts and washers are needed, which are
provided by the user). Screw the foundation bolts to a depth of 20 mm into the
foundation. Installation without foundation: Install proper antivibration pads
and level the unit.
Anti-vibration pad
5.3.2 Installation on a flat roof
In case of installation on a flat roof, create a concrete strip foundation
comparable to what is described in 5.3.1 Installation on a ground. The height
of the strip foundation should not be smaller than 100 mm.
· Take drainage layout into consideration, and install the unit close to the
drainage.
Unit mounting Same as 5.3.1 Installation on a ground.
5.4 Drainage
5.4.1 Drain hole position
Drain hole
16
This drain hole is covered by a rubber plug. If the small drain hole cannot
meet the drainage requirements, the big drain hole can be used instead.
CAUTION
· Watch the condensate when removing the rubber plug of the additional drain
hole.
· Make sure the condensate is drained properly. Collect and direct the
condensate that can drip from the base of the unit to a drain tray. Prevent
water dripping onto the floor that may generate a slip hazard, especially in
winter.
· For cold climate with high humidity, it is highly recommended that a bottom
plate heater be installed to avoid damage to the unit due to the drain water
freezing in case of a low drainage rate.
· Collect and direct the condensate that can drip from the base of the unit to
a drain tray.
· Prevent water dripping onto the floor that may generate a slip hazard,
especially in winter.
5.4.2 Drainage layout (installation on a ground)
Drain joint
90°
The downpipe must flow into a sufficiently large gravel bed so that the
condensate can trickle away freely.
NOTE
To prevent the condensate from freezing, the heating wire must be threaded
into the downpipe through the condensate discharge.
Draining condensate through a pump sump/ soakaway
a
b
c
d
e
a Outdoor unit b Concrete strip foundations c Foundation (See 5.3.1
Installation on a ground) d Drain pipe(at least DN 40) e Pump
sump/soakaway Sewer
a Drain joint (plastic, Pagoda connection, 1″) b Drain hose (field supply)
Installation on a soft ground
Draining condensate into a gravel bed For installation on a ground, the
condensate must be discharged through a downpipe into a gravel bed that is
located in a frost-free area.
a
b
c
100mm
100mm
d
e
f
17
a Outdoor unit b Concrete strip foundations c Foundation (See 5.3.1
Installation on a ground) d Drain pipe (at least DN 40) e Sewer f Stench
trap in an area free from frosting risks Installation on a solid ground Guide
the condensation pipe to a sewer, pump sump or soakaway. The drain plug in the
accessory pack cannot bend to another direction. For this, use a hose to guide
the condensate into a sewer, pump sump or soakaway through a gully, balcony
run-off or roof run-off. Open gullies within the safety zone do not pose any
safety risk. Installation on a flat roof Refer to Installation on a solid
ground.
NOTE
For all installation types, ensure that any accumulated condensate is
discharged in a frostfree manner. To prevent the condensate from freezing, the
heating tape can be threaded into the downpipe through the condensate
discharge.
5.5 In Cold Climates
It is recommended that the unit be placed with the rear side against the wall.
Install a lateral canopy on top of the unit to prevent lateral snowfall in
extreme weather conditions. Install a high pedestal or wall mount the unit to
keep a proper clearance (at least 100 mm) between the unit and snow.
Canopy or alike Pedestal in case of installation on a ground
5.6 Exposure to Strong Sunlight
Long time of exposure of the ambient temperature sensor of the unit to
sunlight might impact the sensor negatively, and cause undesirable impacts on
the unit. Shade the unit with a canopy or alike.
HYDRAULIC INSTALLATION
6.1 Preparations for Installation
NOTE
· In case of plastic pipes, make sure they are fully oxygen-tight according to
DIN 4726.
· The diffusion of oxygen into the piping can lead to excessive corrosion.
System water volume Check the total water volume in the installation according
to the expansion vessel. For the selection of expansion vessel, refer to
INSTALLATION, OPERATION AND MAINTENANCE MANUAL.
Flow rate range The operation flow rate range of the unit is shown as below.
Check and ensure that the flow rate in the installation is guaranteed in all
conditions.
Unit 26kW 30kW 35kW
Flow rate range(m3/h) 1.2-5.4 1.2-6.2 1.2-7.2
6.2 Water Loop Connection
Typical workflow Connecting the water loop typically consists of the following
steps: 1) Connect the water piping to the outdoor unit. 2) Connect the drain
hose to the drain. 3) Fill the water loop. 4) Fill the domestic hot water tank
(if available). 5) Insulate the water piping.
Requirements
NOTE
· The pipe inside must be clean. · Hold the pipe end downwards when removing
burrs. · Cover the pipe end when inserting the pipe through a wall to prevent
dust and dirt from entering the pipe. · Use proper thread sealant to seal the
connections. The sealing must be able to withstand the pressure and
temperature of the system. · When using non-copper metallic piping, be sure to
insulate two kinds of materials from each other to prevent galvanic corrosion.
· Copper is soft. Use appropriate tools to avoid damage. · Zn-coated parts
cannot be used. · Always use materials that do not react with the water used
in the system and with the materials used in the unit. · Ensure that
components installed in the field piping can withstand the water pressure and
temperature.
18
CAUTION
Incorrect orientation of water outlet and inlet could cause unit malfunction.
Do NOT apply excessive force when connecting the field piping and make sure
the piping is aligned properly. Water piping deformation could cause unit
malfunction. The unit is only to be used in a closed water system (See 3.9
Typical Applications). 1) Connect the Y-shaped strainer to the water inlet of
the unit, and seal the connection with thread sealant. (To provide access to
the Y-shaped strainer for cleaning, an extension pipe can be connected between
the strainer and the water inlet depending on the field conditions) 2) Connect
the pipe provided on the site to the water outlet of the unit. 3) Connect the
outlet of the safety valve with a hose with a suitable size and length, and
guide the hose to the condensate 5.4.2 Drainage layout.
a Water OUTLET (connection with screws, male)
b Water INLET (connection with screws, male) c Y-shaped strainer (delivered
with the unit)
(2 screws for connection, female) d Thread seal tape e Extension pipe
(recommended, with the
length depending on the field conditions) f Safety valve outlet (hose, 16mm) g
Drain hose (supplied on the site)
Domestic hot water For the installation of the domestic hot water tank
(supplied on the site), refer to the specific manual of the domestic hot water
tank.
Others
NOTE
· Air vent valves must be installed at high points of the system.
· Drain taps must be installed at low points of the system.
6.3 Water
Checking and treating the water/filling and supplementing water
· Before filling or topping up the installation, check the quality of the
water.
NOTE
· Risk of material damage due to poor-quality water.
· Ensure that the water is of sufficient quality. · Water quality should be
complied with EN 98/83 EC Directives.
Checking the filling and supplementary water · Before filling the
installation, measure the hardness
of the filling and supplementary water. Checking the quality of the water 1)
Remove a little water from the heating circuit. 2) Check the appearance of the
water.
· If it is determined that the water contains sedimentary materials, be sure
to desludge the installation. 3) Use a magnetic rod to check whether the water
contains magnetite (iron oxide).
· If you ascertain that it contains magnetite, clean the installation and take
suitable corrosion-inhibition measures, or install a magnetite separator. 4)
Check the pH value of the removed water at 25 °C.
· If the value is below 8.2 or above 10.0, clean the installation and treat
the water.
NOTE
Ensure that oxygen cannot get into the water.
Treating the filling and supplementary water · Observe all applicable national
regulations
and technical rules when treating the filling and supplementary water.
Provided the national regulations and technical rules do not stipulate more
stringent requirements, the following applies: You must treat the water in the
following cases.
· If the entire filling and supplementary water quantity during the service
life of the system exceeds three times the nominal value of the water loop, or
· If the guideline values listed in the following table are not met, or
· If the pH value of the water is smaller than 8.2 or larger than 10.0.
19
Validity: Denmark or Sweden
Total heating output
Water hardness at specific system volume1)
20 l/kW
20 l/kW and 50 l/kW
50 l/kW
kW
°dH mol/m3 °dH mol/m3 °dH mol/m3
<50
< 16.8 < 3
11.2 2
0.11 0.02
50 and 200
11.2
2
8.4 1.5 0.11 0.02
200 and 600
8.4
1.5
0.11 0.02 0.11 0.02
600
0.11 0.02
0.11 0.02 0.11 0.02
- Nominal capacity in liters/heat output; In the case of multiboiler systems, the smallest single heat output is to be used.
Validity: Great Britain
Total heating output
Water hardness at specific system volume1)
20 l/kW
20 l/kW and 50 l/kW
50 l/kW
kW
ppm CaCO3
mol/m3
ppm CaCO3
mol/m3
ppm CaCO3
mol/m3
<50
< 300 < 3
200 2
2 0.02
50 and 200
200
2
150 1.5
2 0.02
200 and 600
150
1.5
2
0.02
2 0.02
600
2
0.02
2
0.02
2 0.02
- Nominal capacity in liters/heating output; In the case of multiboiler systems, the smallest single heating output is to be used.
Validity: Finland or Norway
Total heating output
Water hardness at specific system volume1)
20 l/kW
20 l/kW and 50 l/kW
50 l/kW
mg
mg
mg
kW
CaCO3/ mol/m3 CaCO3/ mol/m3 CaCO3/ mol/m3
l
l
l
<50
< 300 < 3
200 2
2 0.02
50 and 200
200
2
150 1.5
2 0.02
200 and 600
150
1.5
2
0.02
2 0.02
600
2
0.02
2
0.02
2 0.02
- Nominal capacity in liters/heating output; In the case of multiboiler systems, the smallest single heating output is to be used.
6.4 Filling Water Loop with Water
NOTE
Before filling with water, please check 6.3 Water for the water quality
requirements. Pumps and valves may become stuck as a result of poor water
quality.
· Connect the water supply to the filling valve and open the valve. Follow
applicable regulations.
· Make sure the automatic air vent valve is open.
· Ensure a water pressure of approximately 2.0 bar. Remove the air in the loop
as much as possible using the air vent valves. Air in the water loop could
lead to malfunction of the backup electric heater.
Do not fasten the black plastic cover on the vent valve at the topside of the
unit when the system is running. Open the air vent valve, and turn it
anticlockwise at least 2 full turns to release air from the system.
1 full turn
NOTE
During filling, it might not be possible to remove all air from the system.
Remaining air will be removed through the automatic air purge valves during
the first operation of the system. Topping up with water afterwards might be
required.
· The water pressure will vary with the water temperature (a higher pressure
at a higher water temperature). Always keep the water pressure above 0.3 bar
to prevent air from entering the loop.
· The unit might drain off too much water through the pressure relief valve.
Maximum water pressure
3 bar
6.5 Filling Domestic Hot Water Tank with Water
See the specific manual of the domestic hot water tank.
6.6 Water Pipe Insulation
The complete water loop including all pipes, must be insulated to prevent
condensation during cooling operation, heating and cooling capacity reduction,
and freezing of the outside water pipes in winter.
NOTE
· The insulation material should be provided with a fire resistance rating of
B1 or above and comply with all applicable regulations.
· The thermal conductivity of the sealing material should be below 0.039 W/mK.
Recommended thickness of the sealing material is shown as below.
Piping length (m) between the unit and the terminal device
< 20 20~30 30~40 40~50
Minimum insulation thickness(mm)
19 32 40 50
If the outdoor ambient temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the sealing materials should be at least 20 mm to avoid condensation on the surface of the seal.
20
6.7 Freeze Protection
6.7.1 Protected by software
The software is equipped with specific functions to protect the entire system
from freezing by using the heat pump and the backup heater (if available).
· When the temperature of the water flow in the system drops to a certain
value, the unit will heat the water using the heat pump, electric heating
tape, or backup heater.
· The anti-freeze function is enabled only when the temperature increases to a
certain value.
CAUTION
· In the event of power failure, the above features would fail to protect the
unit from freezing. Therefore, always keep the unit powered on.
· If the power supply for the unit is to be switched off for a long time, the
water in the system pipe needs to be drained to avoid damage to the unit and
pipeline system due to freezing.
· In case of power failure, add glycol to the water. Glycol lowers the
freezing point of the water.
6.7.2 Protected by glycol
Glycol lowers the freezing point of water.
CAUTION
Ethylene glycol and propylene glycol are toxic.
CAUTION
Glycol can corrode the system. When uninhibited glycol comes into contact with
oxygen, it becomes acidic. This corrosion process is accelerated by copper and
high temperature. The acidic uninhibited glycol attacks metal surfaces,
forming galvanic corrosion cells that can cause severe damage to the system.
Therefore, it is important to follow these steps:
· Let a qualified specialist treat the water correctly;
· Select a glycol with corrosion inhibitors to counteract acids formed by the
oxidation of glycols;
· Do not use any automotive glycol because its corrosion inhibitors have a
limited lifetime and contain silicates which can contaminate or block the
system;
· Do not use galvanized pipes in glycol systems as such pipes may lead to the
precipitation of certain components in the glycol’s corrosion inhibitor.
NOTE
Glycol absorbs moisture from the environment, so it is important to avoid
using glycol exposed to air. If glycol if left uncovered, the water content
increases, lowering the glycol concentration and potentially causing hydraulic
components to freeze. To prevent this, take precautions and minimize glycol’s
exposure to air.
Types of glycol
The types of glycol that can be used depend on whether the system contains a
domestic hot water tank:
If
The system contains a domestic hot water tank
The system does NOT contain a domestic hot water tank
Then
Only use propylene glycol (a)
Either propylene glycol(a) or ethylene glycol can be used
(a) Propylene glycol, including the necessary inhibitors, falls in Category
III according to EN1717.
Required concentration of glycol
The required concentration of glycol depends on the lowest expected outdoor
temperature, and on whether you want to protect the system from bursting or
from freezing. To prevent the system from freezing, more glycol is required.
Add glycol according to the table below.
Lowest expected outdoor temperature
5°C 10°C 15°C 20°C 25°C 30°C
Prevention from bursting
10% 15% 20% 25% 30% 35%
Prevention from freezing
15% 25% 35% N/A N/A N/A*
- Additional action is needed to prevent freezing. · Protection from bursting: Glycol can prevent the
piping from bursting, but cannot prevent the liquid inside the piping from freezing.
· Protection from freezing: Glycol can prevent the liquid inside the piping from freezing.
NOTE
· The required concentration might vary depending on the type of glycol used.
ALWAYS compare the requirements from the table above with the specifications
provided by the glycol manufacturer. If necessary, meet the requirements set
by the glycol manufacturer.
· The added concentration of glycol should NEVER exceed 35%.
· If the liquid in the system is frozen, the pump will NOT be able to start.
Please note that solely preventing the system from bursting may not prevent
the liquid inside from freezing.
· If water remains stagnant within the system, it is highly likely to freeze
and result in system damage.
Glycol and the maximum allowed water volume
Adding glycol to the water loop reduces the maximum allowed water volume of
the system. For more information, see 6.1.2 Maximum water volume.
6.7.3 About freeze protection valves (supplied by the user)
21
NOTE
Do NOT install freeze protection valves, if glycol is added to the water.
Otherwise, glycol may leak from the freeze protection valves.
When no glycol is added to the water, you can use freeze protection valves to
drain the water from the system before it freezes.
· Install freeze protection valves (supplied by the user) at all lowest points
of the field piping.
· Normally closed valves (located indoors near the piping entry/exit) can
prevent drainage of water from indoor piping when the freeze protection valves
are open.
NOTE
When freeze protection valves are installed, ensure the minimum cooling set
point is 7°C (7°C=default). Otherwise, freeze protection valves can open
during cooling operation.
6.7.4 Measure without freeze protection
In cold environments, if there is no antifreeze (e.g. glycol) in the system or
lasting power failure or pump failure is foreseen, drain the system (as shown
in the figure below).
Keep dry
NOTE
· Rotate the flow switch counterclockwise to remove it.
· Dry the flow switch completely.
6.8 Check of Water Loop
The conditions below should be met before installation: · The maximum water
pressure is smaller than or
equal to 3 bar. · The maximum water temperature is smaller than or
equal to 85°C according to safety device setting. · Drain taps must be
installed at all low points of the
system to ensure complete drainage of the circuit during maintenance.
· Air purge valves must be installed at all high points of the system. The
vents should be located at points that are easily accessible for service. An
automatic air purge valve is provided inside the unit. Verify that this air
purge valve is not tightened so that automatic release of air from the water
loop is possible.
NOTE
If water is not removed from the system in freezing weather when the unit is
not in use, the frozen water may damage the water circle parts.
6.7.5 Freeze protection for water loop
All internal hydronic parts are insulated to reduce heat loss. The field
piping must also be insulated. In the event of a power failure, the above
features would not protect the unit from freezing. The software contains
special functions using the heat pump and backup heater (if optional and
available) to protect the entire system from freezing. When the temperature of
the water flow in the system drops to a certain value, the unit will heat the
water, either using the heat pump, the electric heating tap, or the backup
heater. The anti-freeze function will be disabled only when the temperature
increases to a certain value. Water may enter the flow switch and cannot be
drained out, and may freeze when the temperature is low enough. The flow
switch should be removed and dried before being installed in the unit.
22
ELECTRICAL INSTALLATION
DANGER
Risk of electrocution.
7.1 Opening the Electrical Box Cover
To access the unit for installation and maintenance, follow the instructions
below.
WARNING
Risk of electrocution. Risk of burning.
NOTE
Keep the screws properly for later use.
Refer to the INSTALLATION, OPERATION AND MAINTENANCE MANUAL for more practical
instructionsRefer to the INSTALLATION, OPERATION AND MAINTENANCE MANUAL for
more practical instructions.
14x
7.2 Back plate layout for wiring
4 3
For main power wiring.
For high voltage wiring.
For low voltage wiring.
Safety valve drain.
Tightening torques
Item
Tightening torque (N·m)
M6 (power terminal)
2.8-3.0
M6 (earthing)
2.8-3.0
M4 (electric control board terminal)
1.2-1.5
8x
23
7.3 Electrical Wiring Guidelines
7.3.1 Operating current and wire diameter
- Select the wire diameter ( minimum value) individually for each unit based on Table 7-1 and Table 7-2. The rated current in Table 7-1 means MCA in Table 7-2. In case the MCA exceeds 63 A, the wire diameters should be selected according to the local wiring regulation.
- The maximum allowable voltage deviation between phases is 2%. 3) Select circuit breakers that have a contact separation of at least 3 mm in all poles for full disconnection. MFA is used to select the current circuit breakers and residual current operation breakers. 4The drive electronic control box is equipped with an overcurrent protector (fuse). In case any additional overcurrent protector is needed, refer to the TOCA in Table 7-2.
(a) Minimum cable section AWG18 (0.75 mm2). (b) The thermistor cable is delivered with the unit.
NOTE
Table 7-1 Table 7-2
Rated current (A)
3 >3 and 6 >6 and 10 >10 and 16 >16 and 25 >25 and 32 >32 and 50 >50 and 63
Nominal cross-sectional area (mm2)
Flexible cord 0.5 and 0.75
Cable for fixed wiring 1 and 2.5
0.75 and 1
1 and 2.5
1 and 1.5
1 and 2.5
1.5 and 2.5
1.5 and 4
2.5 and 4
2.5 and 6
4 and 6
4 and 10
6 and 10
6 and 16
10 and 16
10 and 25
3-phase 26-35kW
System
Outdoor unit
Power current
Voltage (V)
Hz
Min. Max. MCA TOCA MFA (V) (V) (A) (A) (A)
26kW 3-PH 380-415 50 342 456 28
35
40
30kW 3-PH 380-415 50 342 456 30
35
40
35kW 3-PH 380-415 50 342 456 32
35
40
MCA: max. circuit current. (A) TOCA: total over current (A) MFA: max. fuse current (A)
24
7.4 Connection with Power Supply 7.4.1 Wiring of main power supply
CAUTION
· Use a round crimp-style terminal for connection to the power supply terminal
board.
· The power cord model is H05RN-F or H07RN-F. · Illustrations below are for
3-phase units. · Illustrations below are for units with a backup heater.
Refer to the INSTALLATION, OPERATION AND MAINTENANCE MANUAL for more
information.Refer to the INSTALLATION, OPERATION AND MAINTENANCE MANUAL for
more information.
3 phase without backup heater.
L1 L2 L3 N
NOTE
· If the current of load is smaller than 0.2 A, load can connect to the port
directly. If the load current is larger than or equal to 0.2sA, it is
necessary to connect the AC contactor to the load.
· Illustrations below are for 3-phase units. The principle is the same for 1
-phase units.
· Illustrations below are based on units with a backup heater.
CN11
L1 L2 Main power supply L3 N
CAUTION
Leakage protection switch must be installed.
NOTE
· The installation of the Y-shaped strainer at the water inlet is mandatory
· Pay attention to the correct flow direction of the Y-shaped strainer.
7.5 Connection of Other Components
The port provides the control signal to the load. Two kinds of control signal
ports:
· Type 1: dry contactor without voltage. · Type 2: The port provides the
signal with 220-240V~50Hz voltage.
25
FUSE Load Type 1
CN11
Power supply
7 5 3 1 A1 A2
8 6 4 2 Contactor
MCO ATCO
Type 2
Load
Control signal port of hydraulic module: The CN11 contains terminals for the
3-way valve, pump, booster, and heater, etc. Connect the cable to an
appropriate terminal as shown in the figure and fix the cable reliably.
7.5.1 Wiring of additional heat source control (AHS)
AHS1 AHS2
12
CN11
7.5.2 Wiring of 3-way valves SV1, SV2 and SV3
NOTE
Refer to the 3.9 Typical applications for the installation locations of SV1,
SV2 and SV3.
SV1:
1ON 1OFF
34 17
C1 CN11
3 17 4
FUSE L
Power supply
7 5 3 1 A1
KM1
A2 N
86 42
Additional heat source
The wiring between the switch box and the back plate is shown in 7.5.2 Wiring of main power supply.
L-N Voltage Maximum running current (A) Minimum wire size (mm2) Control port signal type
220-240VAC 0.2 0.75 Type 1
NOTE
This part only applies to basic units (without a backup heater). For
customized units (with a backup heater), the hydraulic module should not be
connected to any additional heat source as there is an interval backup heater
in the unit.
SV2:
SV1
2ON 2OFF
56
18
CN11
C1
SV2
26
5 18 6
SV3:
3ON 3OFF
78
19
CN11
C1
Additional circulation pump P_o:
P_0
10
21
CN11
C1
SV3
Voltage Maximum running current (A) Minimum wire size (mm2) Control port signal type
220-240VAC 0.2 0.75 Type 2
7.5.3 Wiring of additional pumps
Zone 2 pump P_c:
P_c
9
20
CN11
C1
7 19 8
Power supply
7 5 3 1 A1
KM3
A2
86 42
Solar energy pump P_s:
CN11
P_s
11 22
C1
Power supply
7 5 3 1 A1
KM2
A2
86 42
27
Power supply
7 5 3 1 A1
KM4
A2
86 42
DHW pipe pump P_d:
P_d
12
CN11
23 C1
Voltage Maximum running current (A) Minimum wire size (mm2) Control port signal type
220-240VAC 0.2 0.75 Type 2
7.5.5 Wiring of tank booster heater (TBH)
13 16
TBH C1 CN11
Power supply
7 5 3 1 A1
KM5
A2
86 42
Voltage Maximum running current (A) Minimum wire size (mm2) Control port signal type
220-240VAC 0.2 0.75 Type 2
7.5.4 Wiring of alarm or defrost run (P_x)
2324
CN11 C1
P_x
Power supply
7 5 3 1 A1
KM7
A2
86 42 MCO
ATCO
TBH
NOTE
MCO: Manual reset thermal protector ATC: Auto reset thermal protector
Power supply
7 5 3 1 A1
KM6
A2
86 42
Alarm or Defrost
28
7.5.6 Wiring of external IBH
NOTE
· The unit only sends an ON/OFF signal to the heater.
· IBH cannot be wired independently.
7.5.7 Wiring of room thermostat (RT)
Room thermostat (low voltage): “POWER IN” provides the voltage to the RT.
NOTE
The room thermostat must be low-voltage.
15 17
IBH1
C1 CN11
COM CL HT
CN61CN63 CN31 CN66
Power supply
7 5 3 1 A1
KM8
A2
86 42 MCO
ATCO
IBH
Voltage Maximum running current (A) Minimum wire size (mm2) Control port signal type
220-240VAC 0.2 0.75 Type 2
NOTE
MCO: Manual reset thermal protector ATC: Auto reset thermal protector
Method A
RT1
(Mode setting control)
POWER IN
HT COM
CL
29
Method B
RT1
(Single-zone control)
POWER IN
HT COM
COM CL HT
CN61CN63 CN31 CN66
COM HT
CN61 CN63 CN31 CN66
The thermostat cable can be connected in three ways (as described in the
figures above) and the specific connection method depends on the application.
Method A (Mode setting control)
RT can control heating and cooling individually, like the controller for
4-pipe FCU. When the hydraulic module is connected with the external
temperature controller, ROOM THERMOSTAT is set to MODE SET on the wired
controller:
A.1 When the unit detects a voltage of 230VAC between CL and COM, it operates
in cooling mode.
A.2 When the unit detects a voltage of 230VAC between HTand COM, it operates
in heating mode.
A.3 When the unit detects a voltage of 0VAC for both sides (CL-COM and HT-
COM), it stops working for space heating or cooling.
A.4 When the unit detects a voltage of 230VAC for both sides (CL-COM and HT-
COM), it operates in cooling mode.
Method B (single-zone control)
RT provides the switch signal to the unit. ROOM THERMOSTAT is set to ONE ZONE
on the wired controller:
B.1 When the unit detects a voltage of 230VAC between HT and COM, it turns on.
B.2 When the unit detects a voltage of 0VAC between HT and COM, it turns off.
Method C (double-zone control)
The hydraulic module is connected with two room thermostats, and ROOM
THERMOSTAT is set to DOUBLE ZONE on the wired controller:
C.1 When the unit detects a voltage of 230VAC between HT and COM, zone1 turns
on. When the unit detects a voltage of 0VAC between HT and COM, zone1 turns
off. C.2 When the unit detects a voltage of 230VAC between CL and COM, zone2
turns on according to the climate temp curve. When the unit detects a voltage
of 0V between CL and COM, zone2 turns off. C.3 When the voltage between HT-COM
and CL-COM is detected as 0VAC, the unit turns off. C.4 When the voltage
between HT-COM and CL-COM is detected as 230VAC, both zone1 and zone2 turn on.
NOTE
· The wiring of the thermostat should correspond to the settings of the wired
controller. Refer to 9.2 Configuration.
· Power supply of the device and room thermostat must be connected to the same
neutral line.
· When ROOM THERMOSTAT is not set to NON, the indoor temperature sensor Ta
cannot be set to VALID.
· Zone 2 can only operate in heating mode. When cooling mode is set on the
wired controller and zone 1 is OFF, “CL” in Zone 2 closes, and system still
remains `OFF’. For installation, the wiring of thermostats for Zone 1 and Zone
2 must be correct.
HT
COM
CL
Method C (Double-zone control)
RT1 zone1
POWER IN
RT2 zone2
POWER IN
30
7.5.8 Wiring of solar energy input signal (low voltage)
7.5.10 Wiring of smart grid
The unit has a smart grid feature, and there are two ports on the PCB to
connect SG signals and EVU signals as below:
S2S1 CN61CN63 CN31 CN66 EVU SG CN61 CN63 CN31 CN66
CLOSE: SHUT DOWN
7.5.9 Wiring of remote shutdown
CLOSE: SHUT DOWN
M1M2 CN61 CN63 CN31 CN66
SMART GRID
- SG=ON, EVU=ON. If DHW mode is set available:
· The heat pump will operate in DHW mode firstly. · When TBH is set available, if T5 is lower than 69°C, the TBH will be turned on forcibly (The heat pump and TBH can operate at the same time.); if T5 is higher than or equal to 70°C, the, TBH will be turned off. (DHW: Domestic Hot Water; T5S is the set temperature of the water tank.) · When TBH is set unavailable and IBH is set available for DHW mode, if T5 is lower than 69°C, the IBH will be turned on forcibly (The heat pump and IBH can operate at the same time.); if T5 is higher than or equal to 70°C, the IBH will be turned off. - SG=OFF, EVU=ON. If DHW mode is set available and DHW mode is set to ON:
· The heat pump will operate in DHW mode firstly. · When TBH is set available and DHW mode is set ON, if T5 is lower than T5S-2, the TBH will be turned on (The heat pump and TBH can operate at the same time.); If T5 is higher than or equal to T5S+3, the TBH will be turned off. · When TBH is set unavailable and IBH is set available for DHW mode, if T5 is lower than T5S-dT5_ON, the IBH will be turned on ( The heat pump and IBH can operate at the same time.); If T5 is higher than or equal to Min (T5S+3,70), the IBH will be turned off. - SG=OFF, EVU=OFF. The unit will operate properly.
- SG=ON, EVU=OFF. The heat pump, IBH, and TBH will be turned off immediately.
31
7.6 Cascade Function
See the INSTALLATION, OPERATION AND MAINTENANCE MANUAL.
7.7 Connection for Other Optional Components 7.7.1 Wiring of drainage pipe
heating tape
CN68
The maximum power is 100W.
Use tie wraps
After wiring, the sleeve
Heating tape
NOTE
should be fastened with a tie wrap (accessory)
32
INSTALLATION OF WIRED CONTROLLER
CAUTION
· The general instructions on wiring in previous chapters should be observed.
· The wired controller must be installed indoors and kept away from direct
sunlight. · Keep the wired controller away from any ignition source, flammable
gas, oil, water vapor, and sulfide gas. · To avoid electromagnetic
disturbance, keep the wired controller at a proper distance from electric
appliances, such as lamps. · The circuit of the remote wired controller is a
low-voltage circuit. Never connect it with a standard 220V/380V circuit or
place it into a same wiring tube with the circuit. · Use a terminal connection
block to extend the signal wire if necessary. · Do not use a megger to check
insulation of the signal wire upon completion of connection.
8.1 Materials for Installation
Verify that the accessory bag contains the following items:
No.
Name
1 Wired controller
2 Round head screw, ST4 x 20
3 Cross round head mounting screw
4 Phillips head screw, M4 x 25
5 Plastic support bar
Qty.
Remarks
1
4 For mounting on a wall
2 For mounting on an 86-type box
2 For mounting on an 86-type box
4 For mounting on a wall
8.2 Dimensions
120mm
18mm
21mm
84mm
120mm
46mm
8.3 Wiring
L1 A B X/HA Y/HB E
T1 T2 E1 H1 H2 Hydraulic module
D1 D2
E D
X1/ HB
X2/ HA
H1
H2 E_H
46mm 60mm
A+ B- Modbus E
Input voltage (HA/HB) Wire size Wire type Wire length
18VDC 0.75 mm2 2-core shielded twisted pair cable L1<50 m
The maximum length of the communication wire between the unit and the controller is 50 m.
33
Route
Bottom-side wiring out
D1 D2
E D
X1/ HB
X2/ HA
H1
H2 E_H
Place of lower-side wire outlet
DETAIL A SCALE 2:1
Inside wall wiring (with an 86-type box)
Lower-side wire outlet
Inside wall wiring (without an 86-type box)
21mm
46mm Electrician box
84mm
46mm 60mm
Wiring hole
Wall hole and wiring hole Diameter: 8-10
8.4 Mounting
NOTE
Only wall-mount the wired controller, instead of embedded, otherwise
maintenance will not be possible.
Mounting on a wall (without an 86-type box)
Directly install the back cover on the wall with four ST4 x 20 screws.
Signal switching wires
Mounting on a wall (with an 86-type box)
Install the back cover on an 86-type box with two M4 x 25 screws, and fixing
the box on the wall with two ST4 x 20 screws.
34
· Adjust the length of the plastic bolt in the accessory box to make it
suitable for installation. · Fix the wired controller’s bottom cover to the
wall through the screw bar by using cross head screws. Make sure the bottom
cover is set flush on the wall.
Screw hole on the wall; Use two ST4 x 20 mm screws
Electrician box
Signal switching wire
Screw hole on 86 electrical box; Use two M4 x 25 mm screws · Buckle the front cover, and fit the front cover to the back cover properly, leaving the wire unclamped during the installation.
Sensor cannot be affected with damp
NOTE
To prevent water from entering the remote wired controller, use traps and
plugs to seal the wire connections during wiring.
Plug Trap
Plug Trap
Avoid the water enter into the wired remote controller, use trap and putty to seal the connectors of wires during wiring installation.
NOTE
Over-tightening the screw can cause deformation of the back cover.
35
COMPLETION OF INSTALLATION
Risk of electrocution. Risk of burning.
DANGER
Tightening torque
4.1 N·m
8x
14x
CONFIGURATION
The unit should be configured by an authorized installer to match the installation environment (outdoor climate, installed options, etc.) and meet the user demand. Follow the instructions below for the next step.
10.1 Check Before Configuration
Before powering on the unit, check the following items:
Field wiring: Make sure all wiring connections observe the instructions mentioned in the 7. Electrical installation
Fuses, circuit breakers, or protection devices: Check the size and type
according to the instructions mentioned in the 7.4 Electrical wiring
guidelines. Make sure that no fuses or protection devices have been
bypassed.
Backup heater’s circuit breaker: Ensure the backup heater’s circuit breaker in the switch box is closed (It varies with the backup heater type). Refer to the wiring diagram.
Booster heater’s circuit breaker: Ensure the booster heater’s circuit breaker is closed (applicable only to units with an optional domestic hot water tank).
Internal wiring: Check the wiring and connections inside the switch box for loose or damaged parts, including earth wiring.
Mounting: Check and ensure that the unit and the water loop system are properly mounted to avoid water leakage, abnormal noises and vibrations during the unit startup.
Damaged equipment: Check the components and piping inside the unit for any damage or deformation.
Refrigerant leak: Check the inside of the unit for any refrigerant leakage. In case of refrigerant leakage, follow the relevant content in the “Safety Precautions”.
Power supply voltage: Check the voltage of the power supply. The voltage must be consistent with the voltage on the identification label of the unit.
Air vent valve: Make sure the air vent valve is open (at least 2 turns).
Shut-off valve: Make sure that the shut-off valve is fully open.
Sheet metal: Make sure all the sheet metal of the unit is mounted properly.
36
After powering on the unit, check the following items:
Upon power-on of the unit, nothing is displayed on the wired controller: Check
the following abnormalities before diagnosing possible error codes. – Wiring
connection issue (power supply or communication signal). – Fuse failure on
PCB.
Error code “E8” or “E0” is displayed on the wired controller: – Residual air
exists in the system. – The water level in the system is insufficient. Before
starting test run, make sure that the water system and the tank are filled
with water, and air is removed. Otherwise, the pump or backup heater
(optional) may be damaged.
Error code “E2” is displayed on the wired controller: – Check the wiring
between the wired controller and the unit.
Initial start-up at low outdoor ambient temperature: To start the initial
start-up in low outdoor ambient temperature, the water has to be heated
gradually. Please use the preheating for floor function. (Refer to “SPECIAL
FUNCTION” in FOR SERVICEMAN mode)
NOTE
For underfloor heating application, floor could be damaged if the temperature
rises sharply in a short time. Please ask the building construction contractor
for further information.
About error code, see “13.3 Error codes”.
10.2 Configuration
To initialize the unit, a group of advanced settings should be provided by the
installer. The advanced settings are accessible in FOR SERVICEMAN mode. The
overall parameters list of the advanced settings can be found in Annex 2.
Operation Settings. How to enter FOR SERVICEMAN mode Press and hold and
simultaneously for 3 seconds to enter the authorization page. Enter password
234 and confirm it. Then, the system jumps into the page with a list of
advanced settings.
For serviceman
0 0 0
Please input the password
NOTE
“FOR SERVICEMAN” is only for installer or other specialist with sufficient
knowledge and skills. The end user who use “FOR SERVICEMAN” is regarded as
improper use.
Save the settings and quit FOR SERVICEMAN mode After all settings are
adjusted, press , and the confirmation page pops out. Select Yes and confirm
to quit FOR SERVICEMEN mode.
NOTE
· The settings are saved automatically after you quit FOR SERVICEMAN mode.
· Temperature values displayed on the wired controller are measured in °C.
For serviceman
DHW setting Cooling setting Heating setting Auto mode setting
37
COMMISSIONING
Test run is used to confirm the operation of the valves, air purge,
circulation pump operation, cooling, heating and domestic water heating.
Test run
Point check Air purge Circulated pump running Cooling running
Test run
Heating running Cooling running DHW runing
Checklist during commissioning Test run for the actuator. Air purge Test run
for operation. Check of the minimum flow rate in all conditions.
11.1 Test Run for the Actuator
NOTE
During the commissioning of the actuator, the protection function of the unit
is disabled. Excessive use may damage components.
Why Check whether each actuator is in good working conditions.
What – Actuator List
No. 1 SV2 2 SV3 3 Pump_I 4 Pump_O 5 Pump_C 6 IBH 7 AHS 8 SV1 9 Pump_D 10 Pump_S 11 TBH
Name Three-way valve 2 Three-way valve 3 Integrated pump Outside pump Zone 2 pump Internal backup heater Additional heat source Three-way valve 1 Circulation pump for DHW Solar pump Tank backup heater
Note
Invisible if DHW is disabled Invisible if DHW is disabled Invisible if DHW is
disabled Invisible if DHW is disabled
How
1 Go to “FOR SERVICEMAN” (Refer to 10.2 Configuration). 2 Find “Test run” and enter the process. 3 Find “Point check” and enter the process.
4 Select the actuator, and press to activate or deactivate the actuator. · The status ON means the actuator is activated, and OFF means the actuator is deactivated.
NOTE
When you return to the upper layer, all actuators turn OFF automatically.
11.2 Air Purge
Why To purge out the remaining air in the water loop.
How
1
Go to “FOR SERVICEMAN” (Refer to 10.2 Configuration).
2
Find “Test run and enter the process.
3
Find “Air purge” and enter the process.
4
Select “Air purge” and press to activate or deactivate the air purge function.
·
means the air purge function is activated, and
means the air purge function is deactivated.
38
Besides
“Air vent pump_i output”
To set pump_i output. The higher the value is, the pump gives a higher output.
“Air vent running time”
To set the duration of air purge. When the set time is due, air purge is deactivated.
“Status check”
Additional operation parameters can be found.
11.3 Test Run
Why Check whether the unit is in good working conditions.
What Circulated pump operation Cooling operation Heating operation DHW
operation
How
1 Go to “FOR SERVICEMAN” (Refer to 10.2 Configuration) 2 Find “Test run” and enter the page.
3 Find “Other” and enter the process.
Select “XXXX”* and press to run the test. During test, press , select OK and confirm to return to the upper 4 layer.
- – Four performance test options are shown in What.
NOTE
In performance test, the target temperature is preset and cannot be changed.
If the outdoor temperature is outside the range of operating temperature, the
unit may not operate or may not deliver the required capacity. In circulated
pump operation, If the flow rate is out of recommended flow rate range, please
make proper change of the installation, and ensure that the flow rate in the
installation is guaranteed in all conditions.
11.4 Check of the Minimum Flow Rate
1
Check the hydraulic configuration to find out the space heating loops that can be closed by mechanical, electronic, or other valves.
2 Close all space heating loops that can be closed.
3 Start and operate the circulation pump (See “11.3 Test Run “).
4
Read out the flow rate(a) and modify the bypass valve settings until the set value reaches the minimum flow rate required + 2 l/min.
(a) During pump trail run, the unit can operate below the minimum required flow rate.
12 HAND-OVER TO THE USER
· Make sure that the user has the printed documentation and ask the user to
keep it for future reference. · Empty the error history in the HMI before
hand-over to the user. · It is highly recommended to do the WLAN connection of
the unit. You can read more information in the APP. · Explain to the user how
to properly operate the system and what to do in case of problems. · Show the
user what to do for the maintenance of the unit. (For the maintenance, refer
to the INSTALLATION, OPERATION AND MAINTENANCE MANUAL) · Explain to the user
about energy saving tips. (Refer to the INSTALLATION, OPERATION AND
MAINTENANCE MANUAL)
39
MAINTENANCE
Regular checks and inspections at certain intervals are required to guarantee
the optimal performance of the unit.
13.1 Safety Precautions for Maintenance
DANGER
Risk of electrocution.
WARNING
· Please note that some parts of the electric component box are hot.
· Do not rinse the unit. Otherwise, electric shock or fire may occur.
· Do not leave the unit unattended when the service panel is removed.
NOTE
Before performing any maintenance or service work, touch a metal part of the
unit to eliminate static electricity and to protect the PCB.
13.2 Annual Maintenance
13.2.1 Water pressure
Check the water pressure. If it is below 1 bar, fill the system with more
water.
13.2.2 Water strainer
Clean the water strainer.
13.2.3 Water pressure relief valve
-Check for correct operation of the pressure relief valve by turning the black knob on the valve counterclockwise: -If no clacking sound is heard, contact the local dealer. -In case the water keeps running out of the unit, close the shut-off valves at both the water inlet and outlet, and then contact the local dealer.
13.2.4 Pressure relief valve hose
Verify that the pressure relief valve hose is positioned appropriately to
drain the water.
13.2.5 Insulation cover of backup heater
Verify that the insulation cover of the backup heater is fastened tightly
around the backup heater vessel.
13.2.6 Pressure relief valve of domestic hot water tank (supplied by the user)
Applicable only to installations with a domestic hot water tank. Check for
correct operation of the pressure relief valve on the domestic hot water tank.
13.2.7 Booster heater of domestic hot water tank
Applicable only to installations with a domestic hot water tank. Remove the
scale buildup from the booster heater, especially in regions with hard water.
Drain the domestic hot water tank, remove the booster heater from the domestic
hot water tank, and dissolve the scale with specific descaling agent.
13.2.8 Switch box of the unit
· Visually inspect the switch box and look for obvious defects such as loose
connections or defective wiring.
· Verify that cabling will not be subject to wear, corrosion, excessive
pressure, vibration, sharp edges or any other adverse environmental effects.
Take into account the effects of aging or continual vibration from sources
such as compressors or fans.
· Check for correct operation of contactors with an ohmmeter. All contacts of
these contactors must be in open position.
13.2.9 Temperature sensor
Check the resistance of each temperature sensor with an ohmmeter.
NOTE
As the connector is small, use thin probes. · Refer to 2.8.4 Control board for
the socket of
each temperature sensor, and unplug the connector. · Check the resistance with
an ohmmeter. · Compare the read value with that in the
resistance characteristics table. The temperature sensor is in good conditions
if the deviation is within tolerance.
For the temperature sensor in accessories and temperature sensors on the water
loop, e.g. TW_in and TW_out, refer to Table 3-1.
13.2.10 Use of antifreeze
· The “safety precautions” must be observed. · Make sure that the glycol
solution disposed in accordance with local regulations and standards.
13.2.11 Refrigerant leakage check
Refer to 15.2. Leak Detection Methods.
13.2.12 Flow switch failure
Water may enter the flow switch and may freeze when the temperature is too
low. In such a case, the flow switch should be removed and dried before being
installed in the unit. Before removal of the flow switch, the water in the
system should be drained.
Keep dry
· Rotate the flow switch counterclockwise to remove it. · Dry the flow switch
completely.
40
TECHNICAL DATA
14.1 General
Model
Nominal capacity Dimensions H×W×D Packing dimensions H×W×D Weight Net weight
Gross weight Connections Water inlet/outlet Water drain Expansion vessel
Volume Maximum working pressure (MWP) Pump Type No. of speed Pressure relief
valve in water loop Operation range – water side Heating Cooling Operation
range – air side Heating Cooling Domestic hot water by heat pump
3-phase 26 kW
3-phase 30 kW Refer to the Technical Data
1816×1384×523 mm 2000×1480×570 mm
260 kg 285 kg
G1 1/4″BSP Hose nipple
4.5 L 8 bar
Water cooled Variable speed
3 bar
+25 to +85°C 0 to +25°C
-25 to 43°C -15 to 48°C -25 to 43°C
3-phase 35 kW
Refrigerant Refrigerant type Refrigerant charge
R290 2.9 kg
Fuse on PCB PCB name Model name Working voltage (V) Working current (A)
Main control board FUSE-T-10A/250VAC-T-P 250 10
Fan inverter board FUSE-T-6.3A/500VAC-T/S 500 6.3
Fuse on Drive electronic control box Model name Working voltage (V) Working current (A)
FUSE-T-63A/690VAC-T/S 690 63
41
14.2 Piping Diagram
26-35 kW units (standard)
outlet
S
inlet
Item
Description
1 DC inverter compressor
2 Crankcase heater
3 Discharge temperature sensor 4 High pressure switch 5 High pressure sensor 6 4-way valve
7 Pin valve (Discharge side)
8 DC fan 1 /DC fan 2
9 Condenser
10 Suction temperature sensor
11 Temperature sensor (heat exchanger)
12
Temperature sensor (heat exchanger outlet refrigerant: cooling)
13 Filter
14 Heating Electronic expansion valve
15 One-way valve
16 EVI Electronic expansion valve
17 Plate heat exchanger (Economizer)
18 Economizer inlet temperature sensor
19 Economizer outlet temperature sensor
Item
Description
20 Vapor-liquid separator
21 Temperature sensor (compressor suction)
22 Low pressure sensor
23 Cooling Electronic expansion valve
24 One-way valve
25 Liquid reservoir
26
Temperature sensor (plate heat exchanger inlet refrigerant: cooling)
27
Temperature sensor (plate heat exchanger outlet refrigerant: cooling)
28 Plate heat exchanger
29 Heat tape (plate heat exchanger)
30 Temperature sensor (water inlet)
31 Temperature sensor (water outlet)
32 Water pump
33 Expansion vessel
34 Automatic air vent valve
35 Water flow switch
36 Automatic air vent valve
37 Safety valve
42
ANNEX Annex 1. Menu Structure (Wired Controller)
Menu Mode Schedule Weather temp. settings DHW settings (1) Settings Unit status Error info. FAQ
Mode (2) Heating Cooling Auto
Schedule Zone 1 daily timer Zone 2 daily timer (1) DHW daily timer (1) Zone 1
weekly schedule Zone 2 weekly schedule (1) DHW weekly schedule (1) Holiday
away Holiday home
Weather temp. settings Weather temp. settings introduction Zone 1 heating mode
Zone 1 cooling mode Zone 2 heating mode (1) Zone 2 cooling mode (1)
DHW settings (1) Disinfect (1) Fast DHW Tank heater (1) DHW pump
Settings Silent and boost mode setting Backup heater (1) Display setting WLAN
setting Force defrost (1)
Error info.
FAQ
Unit status Operation parameter Energy metering (1) Device info. Service call
Weekly schedule Schedule 1 Schedule 2 Schedule 3 Schedule 4
Holiday away Current state From Until Heating mode (1) DHW mode (1) Disinfect
(1)
Holiday home Current state From Until Zone 1 holiday timer Zone 2 holiday
timer (1) DHW holiday timer (1)
Temperature curve Temperature curve type Temperature level Temperature offset
Disinfect (1) Disinfect timer Operation day Start
Silent and boost mode setting Current state Mode setting Timer 1 From Until
Timer 1 From Until
WLAN setting Smart link Restore WLAN setting
Display setting Time Date Daylight saving time Language Backlight Buzzer
Screen lock Screen lock time Decimal separator
Energy metering Heating energy data Cooling energy data DHW energy data
(1) Invisible if corresponding function is disabled. (2) The layout could be different if the corresponding function is disabled or enabled. There are also some other items that are invisible if the function is disabled or unavailable.
43
For serviceman
For serviceman 1 DHW setting 2 Cooling setting 3 Heating setting 4 Auto mode setting 5 Temp. type setting 6 Room thermostat setting 7 Other heating source 8 Holiday away setting 9 Service call 10 Restore factory setting 11 Test run 12 Special function 13 Auto restart 14 Power input limitation 15 Input define 16 Cascade setting 17 HMI address setting 18 Common setting
1 DHW setting 1.1 DHW mode 1.2 Disinfect 1.3 DHW priority 1.4 Pump_D 1.5 DHW
priority time set 1.6 dT5_ON 1.7 dT1S5 1.8 T4DHWMAX 1.9 T4DHWMIN 1.10
t_INTERVAL_DHW 1.11 T5S_DISINFECT 1.12 t_DI_HIGHTEMP 1.13 t_DI_MAX 1.14
t_DHWHP_RESTRICT 1.15 t_DHWHP_MAX 1.16 PUMP_D TIMER 1.17 PUMP_D RUNNING TIME
1.18 PUMP_D DISINFECT 1.19 ACS function
2 Cooling setting 2.1 Cooling mode 2.2 t_T4_FRESH_C 2.3 T4CMAX 2.4 T4CMIN 2.5
dT1SC 2.6 dTSC 2.7 t_INTERVAL_C 2.8 ZONE1 C-emission 2.9 ZONE2 C-emission
3 Heating setting 3.1 Heating mode 3.2 t_T4_FRESH_H 3.3 T4HMAX 3.4 T4HMIN 3 .5
dT1S H 3.6 dTSH 3.7 t_INTERVAL_H 3.8 ZONE1 H-emission 3.9 ZONE2 H-emission
3.10 Force defrost
4 Auto mode setting 4.1 T4AUTOCMIN 4.2 T4AUTOHMAX
5 Temp. type setting 5.1 Water flow temp. 5.2 Room temp. 5.3 Double zone
6 Room thermostat setting 6.1 Room thermostat 6.2 Mode set priority
17 HMI address setting 17.1 HMI setting 17.2 HMI address for BMS 17.3 Stop BIT
18 Common setting 18.1 t_DELAY PUMP 18.2 t1_ANTILOCK PUMP 18.3 t2_ANTILOCK
PUMP RUN 18.4 t1_ANTILOCK SV 18.5 t2_ANTILOCK SV RUN 18.6 Ta_adj. 18.7 F-PIPE
LENGTH 18.8 PUMP_I SILENT OUTPUT 18.9 Energy metering 18.10 Pump_O
7 Other heating source 7.1 IBH function 7.2 IBH locate 7.3 dT1_IBH_ON 7.4
t_IBH_DELAY 7.5 T4_IBH_ON 7.6 P_IBH1 7.7 P_IBH2 7.8 AHS function 7.9 AHS_PUMPI
CONTROL 7.10 dT1_AHS_ON 7.11 t_AHS_DELAY 7.12 T4_AHS_ON 7.13 EnSwitchPDC 7.14
GAS_COST 7.15 ELE_COST 7.16 MAX_SETHEATER 7.17 MIN_SETHEATER 7.18
MAX_SIGHEATER 7.19 MIN_SIGHEATER 7.20 TBH FUNCTION 7.21 dT5_TBH_OFF 7.22
t_TBH_DELAY 7.23 T4_TBH_ON 7.24 P_TBH 7.25 SOLAR function 7.26 SOLAR control
7.27 Deltasol
8 Holiday away setting 8.1 T1S_H.A._H 8.2 T5S_H.A._DHW
9 Service call Phone number Mobile number
10 Restore factory setting
11 Test run
12 Specical function 12.1 Preheating for floor 12.2 Floor drying up
13 Auto restart 13.1 Auto restart cooling/ heating mode 13.2 Auto restart DHW
mode
14 Power input limitation 14.1 Power input limitation
15 Input define 15.1 M1M2 15.2 Smart grid 15.3 T1T2 15.4 Tbt 15.5 P_X PORT
16 Cascade setting 16.1 PER_START 16.2 TIME_ADJUST
19 Clear energy data
20 Intelligent function settings 20.1 Energy correction
21 C2 fault restore
There are some items that are invisible if the function is disabled or
unavailable.
44
Annex 2. User Settings Parameters
No.
Code
Mode
Operation mode
T1S
Temperature set
T1S2
TS
T5S (DHW MODE=Yes)
TIMER1-TIMER6 TIMER1-TIMER6 Time
TIMER1-TIMER6 Mode
Zone 1 daily timer
TIMER1-TIMER6 Temp.
TIMER1-TIMER6 TIMER1-TIMER6 Time
TIMER1-TIMER6 Mode
Zone 2 daily timer
TIMER1-TIMER6 Temp.
TIMER1-TIMER6
DHW TIMER1-TIMER6 Time
daily timer
TIMER1-TIMER6 DHW
TIMER1-TIMER6 Temp.
Schedule1 – Schedule4
Schedule1 – Schedule4
Day
Sunday / Monday /
Tuesday / Wednesday /
Thursday / Friday /
Saturday
Command1-Command4
Zone 1 Command1-Command4 weekly Time
sche- Command1-Command4
dule Mode
Command1-Command4 Temp.
Definition
6.1 Mode & Temperature set
Operation mode setting 1=Auto,
2=Cooling, 3=Heating
Water outlet temperature (Zone 1)
For FCU cooling For FLH / RAD cooling For FLH heating For FCU / RAD heating
Water outlet set
For FCU cooling For FLH / RAD cooling
temperature For FLH heating
(Zone 2)
For FCU / RAD heating
Room set
Cooling
temperature Heating
Ta
AUTO
DHW set temperature
6.2 Schedule
Enablement0=inactive, 1=active
Timer start time
Operation mode of the timer 2=Cooling,
1=Heating, 0=OFF
For FCU cooling
For FLH / RAD cooling
Set temperature
of
For For
FLH heating FCU / RAD heating
the timer
Room heating set
temperature Ta
Room cooling set temperature Ta
Enablement 0=inactive, 1=active
Timer start time
Operation mode of the timer 2=Cooling,
1=Heating, 0=OFF
For FCU cooling
For FLH / RAD cooling
Set temperature
of
For For
FLH heating FCU / RAD heating
the timer
Room heating set
temperature Ta
Room cooling set temperature Ta
Enablement 0=inactive, 1=active
Timer start time
Operation mode of the timer 1=DHW
0=OFF
Set temperature of the timer
Enablement 0=inactive, 1=active
Default Minimum Maximum
Setting interval
Unit
3
1
12
5
23
18
30
25
40
35
12
5
23
18
30
25
40
35
24
17
24
17
24
17
50
20
0 00:00
0
12 23 30 40
24
0 00:00
0
5 18 25 35
17
24
0 00:00
0
12 23 30 40
24
17
0 00:00
0
5 18 25 35
17
24
0 00:00
0
50 0
17
0 00:00
0
20 0
3
25 25 55 85 25 25 55 85 30 30 30 75
1 23:50
2
25 25 55 85
30
30
1 23:50
2
25 25 55 85
30
30
1 23:50
1
75 1
/
/
1
°C
1
°C
1
°C
1
°C
1
°C
1
°C
1
°C
1
°C
0.5 °C
0.5 °C
0.5 °C
1
°C
1
/
1/10 h/min
1
/
1
°C
1
°C
1
°C
1
°C
0.5 °C
0.5 °C
1
/
1/10 h/min
1
/
1
°C
1
°C
1
°C
1
°C
0.5 °C
0.5 °C
1
/
1/10 h/min
1
/
1
/
1
/
Enablement 0=inactive, 1=active (if all the date is active, then display `Every day’)
0
0
1
1
/
Enablement
Timer start time
Operation mode of the timer 2=Cooling,
1=Heating, 0=OFF
For FCU cooling
For FLH / RAD cooling
Set temperature
of
For For
FLH heating FCU / RAD heating
the timer
Room heating set
temperature Ta
Room cooling set
temperature Ta
0 00:00
0 00:00
0
0
12
5
23
18
30
25
40
35
24
17
24
17
1 23:50
2 25 25 55 85 30
30
1
/
1/10 h/min
1
/
1
°C
1
°C
1
°C
1
°C
0.5 °C
0.5 °C
45
Schedule1 – Schedule4 Schedule1 – Schedule4 Day Sunday / Monday / Tuesday /
Wednesday / Thursday / Friday / Saturday Command1-Command4 Zone 2
Command1-Command4 weekly Time sche- Command1-Command4 dule Mode
Command1-Command4 Temp.
Schedule1 – Schedule4 Schedule1 – Schedule4 Day Sunday / Monday / Tuesday /
Wednesday / DHW Thursday / Friday / weekly Saturday sche- Command1-Command4
dule Command1-Command4 Time Command1-Command4 DHW Command1-Command4 Temp.
Current state
From
Until Holiday away Heating mode
Heating temp. DHW mode DHW temp. Disinfect
Enablement 0=inactive, 1=active
0
0
1
Enablement 0=inactive, 1=active (if all the date is active, then display `Every day’)
0
0
1
Enablement 0=inactive, 1=active
Timer start time
Operation mode of the timer 2=Cooling,
1=Heating, 0=OFF
For FCU cooling
For FLH / RAD cooling
Set temperature
of
For For
FLH heating FCU / RAD heating
the timer
Room heating set
temperature Ta
Room cooling set
temperature Ta
Enablement 0=inactive, 1=active
0 00:00
0 00:00
0
0
12
5
23
18
30
25
40
35
24
17
24
17
0
0
1 23:50
2 25 25 55 85 30
30 1
Enablement 0=inactive, 1=active (if all the date is active, then display `Every day’)
0
0
1
Enablement 0=inactive, 1=active
Timer start time
Operation mode of the timer 2=Cooling, 1=Heating, 0=OFF
Set temperature of the timer
Enablement 0=inactive, 1=active
Timer start date
Timer end date
Enablement 0=inactive, 1=active Set temperature of Holiday away Enablement
0=inactive, 1=active Set temperature of Holiday away Enablement 0=inactive,
1=active
0 00:00
0 00:00
1 23:50
0
0
1
50
20
75
0
0
1
Current date +1
Current date +1
12/31/2099
Current date +1
Current date +1
12/31/2099
1
0
1
25
20
25
1
0
1
25
20
25
1
0
1
1
1
1 1/10
1 1 1 1 1 0.5 0.5 1
1
1 1/10
1 1 1 1/1/1 1/1/1 1 1 1 1 1
/
/
/ h/min
/ °C °C °C °C °C °C /
/
/ h/min
/ / / d/m/y d/m/y / °C / °C /
Current state
Enablement 0=inactive, 1=active
0
0
1
1
/
From
Until
Zone 1 holiday timer -timer1-timer6 Zone 1 holiday timer -timer1-timer6 Time
Zone 1 holiday timer -timer1-timer6 Mode
Timer start date Timer end date Enablement 0=inactive, 1=active
Current date +1
Current date +1
12/31/2099
Current date +1
Current date +1
12/31/2099
1/1/1 1/1/1
d/m/y d/m/y
0
0
1
1
/
Timer start time
Operation mode of the timer 2=Cooling, 1=Heating, 0=OFF
00:00 00:00
0
0
23:50 2
1/10 h/min
1
/
For FCU cooling
12
5
25
1
°C
Holiday home
For FLH / RAD cooling
23
18
25
1
°C
Zone 1 holiday timer -timer1-timer6 Temp.
Zone 2 holiday timer -timer1-timer6 Zone 2 holiday timer -timer1-timer6 Time
Zone 2 holiday timer -timer1-timer6 Mode
Set
For FLH heating
30
25
temperature of
the timer
For FCU / RAD heating
40
35
Room heating set temperature Ta Room cooling set temperature Ta
24
17
24
17
Enablement 0=inactive, 1=active
0
0
Timer start time
Operation mode of the timer 2=Cooling, 1=Heating, 0=OFF
00:00 00:00
0
0
55 85 30 30 1 23:50 2
1
°C
1
°C
0.5 °C
0.5 °C
1
/
1/10 h/min
1
/
46
For FCU cooling
12
5
For FLH / RAD cooling
23
18
Zone 2 holiday timer -timer1-timer6 Temp.
Set
For FLH heating
temperature of
the timer
For FCU / RAD heating
DHW holiday timer -timer1-timer6 DHW holiday timer -timer1-timer6 Time DHW holiday timer -timer1-timer6 Mode DHW holiday timer -timer1-timer6 Temp.
Room heating set temperature Ta Room cooling set temperature Ta
Enablement 0=inactive, 1=active
Timer start time
Operation mode of the timer 2=Cooling, 1=Heating, 0=OFF
Set temperature of the timer
6.3 Weather temp. settings
Temperature curve
Temperature curve type
Standard – Temperature
level
Standard – Temperature offset
Custom – Temperature
setting – T1SetH1
Zone heating mode
Custom – Temperature setting – T1SetH2 Custom – Temperature
setting – T4H1
Custom – Temperature setting – T4H2
ECO – Temperature level
ECO timer From Until Temperature curve
Temperature curve type
Standard – Temperature level
Standard – Temperature Zone 1 offset cooling Custom – Temperature mode setting
– T1SetC1
Custom – Temperature setting – T1SetC2
Custom – Temperature setting – T4C1
Custom – Temperature setting – T4C2
Temperature curve
Temperature curve type
Standard – Temperature level
Standard – Temperature Zone 2 offset heating Custom – Temperature mode setting
– T1SetH1
Custom – Temperature setting – T1SetH2
Custom – Temperature setting – T4H1
Custom – Temperature setting – T4H2
Enablement 0=inactive, 1=active Temperature curve type 0=Standard, 1=Custom,
2=ECO Curve for FCU / RAD heating Curve for FLH heating Zone 1 heating set
temperature offset of curve
Heating set temperature 1 of curve
Heating set temperature 2 of curve
Heating ambient temperature 1 of curve
Heating ambient temperature 2 of curve
Curve for FLH heating Curve for FCU / RAD heating Enablement 0=inactive,
1=active Timer start date Timer end date Enablement 0=inactive, 1=active
Temperature curve type 0=Standard, 1=Custom Curve for FLH / RAD cooling Curve
for FCU cooling Zone 1 cooling set temperature offset of curve
Cooling set temperature 1 of curve
Cooling set temperature 2 of curve
Cooling ambient temperature 1 of curve
Cooling ambient temperature 2 of curve
Enablement 0=inactive, 1=active Temperature curve type 0=Standard, 1=Custom
Curve for FCU / RAD heating Curve for FLH heating Zone 2 heating set
temperature offset of curve
Heating set temperature 1 of curve
Heating set temperature 2 of curve
Heating ambient temperature 1 of curve
Heating ambient temperature 2 of curve
30 40
24
24
0
00:00
0
50
0 0 6 3 0
35
28
-5
7 3 6 0 8:00 19:00 0 0 4 4 0
10
16
35
25 0 0 6 3 0
35
28
-5
7
25 35
17
17
0
00:00
0
20
0 0 1 1 -10
25
25
-25
-25 1 1 0 00:00 00:00 0 0 1 1 -10
5
5
-5
-5 0 0 1 1 -10
25
25
-25
-25
25 25 55 85
30
30
1
23:50
1
75
1 2 8 8 25
85
85
35
35 8 8 1 23:50 23:50 1 1 8 8 10
25
25
48
48 1 1 8 8 25
85
85
35
35
1
°C
1
°C
1
°C
1
°C
0.5 °C
0.5 °C
1
/
1/10 h/min
1
/
1
/
1
/
1
/
1
/
1
/
1
°C
1
°C
1
°C
1
°C
1
°C
1
/
1
/
1
/
1/10 h/min
1/10 h/min
1
/
1
/
1
/
1
/
1
°C
1
°C
1
°C
1
°C
1
°C
1
/
1
/
1
/
1
/
1
°C
1
°C
1
°C
1
°C
1
°C
47
Temperature curve
Enablement 0=inactive, 1=active
0
0
1
1
/
Temperature curve type
Temperature curve type 0=Standard, 1=Custom
0
0
1
1
/
Standard – Temperature Curve for FLH / RAD cooling
4
1
8
1
/
level
Curve for FCU cooling
4
1
8
1
/
Standard – Temperature Zone 2 cooling set temperature offset of
Zone 2 offset
curve
0
-10
10
cooling Custom – Temperature mode setting – T1SetC1
Cooling set temperature 1 of curve
10
5
25
1
°C
1
°C
Custom – Temperature setting – T1SetC2
Cooling set temperature 2 of curve
16
5
25
1
°C
Custom – Temperature setting – T4C1
Cooling ambient temperature 1 of curve
35
-5
48
1
°C
Custom – Temperature setting – T4C2
Cooling ambient temperature 2 of curve
25
-5
48
1
°C
6.4 DHW settings
Current state
State OFF=0, ON=1
1
0
1
1
/
Operation day
Enablement 0=inactive, 1=active (if all the
Sunday / Monday /
date is active, then display `Every day’) Thurs-
Disinfect Tuesday / Wednesday /
day = 1, 0
1
1
/
Thursday / Friday /
other=0
Saturday
Start
Start time
23:00 00:00 23:50 1/10 h/min
Fast DHW
Fast DHW
State OFF=0, ON=1
0
0
1
1
/
Tank heater
Tank heater
State OFF=0, ON=1
0
0
1
1
/
DHW pump
DHW pump timer 1-12 DHW pump timer 1-12 time
State OFF=0, ON=1 Start time
0 00:00
0 00:00
1 23:50
1
/
1/10 h/min
6.5 Settings
Silent mode
Enablement OFF=0, ON=1
0
0
1
1
/
Silent mode level
0=Silent 1=Super silent
0
0
1
1
/
Silent mode timer 1
Enablement 0=inactive, 1=active
0
0
1
1
/
Silent From
Start time 1
12:00 00:00 23:50 1/10 h/min
mode Until
End time 1
15:00 00:00 23:50 1/10 h/min
Silent mode timer 2
Enablement 0=inactive, 1=active
0
0
1
1
/
From
Start time 2
22:00 00:00 23:50 1/10 h/min
Until
End time 2
07:00 00:00 23:50 1/10 h/min
Backup heater
Backup heater
Enablement 0=OFF, 1=ON
0
0
1
1
/
Time
Current time
00:00 00:00 23:59
1/1 h/min
Date
Current date
1/1/2023 1/1/2023 12/31/2099 1
/
0=English, 1=Français, 2=Italiano,
3=Español, 4=Polski, 5=Português,
Display Language setting
6=Deutsch, 7=Nederlands, 8=Român,
9=, 10=Türkçe, 11=,
0
0
17
1
/
12=Slovenscina, 13=Svenska,
14=Cestina, 15=Slovák, 16=Magyar,
17=Hrvatski
Backlight
Backlight level
2
1
3
1
/
Buzzer
Enablement, 0 = inactive, 1 = active
1
0
1
1
/
Screen lock time
lock timer
0
0
300
30 Second
Force defrost
Force defrost
Enablement 0=OFF, 1=ON
0
0
1
1
/
48
Annex 3. Terms and abbreviation
Tp
Compressor discharge temperature
Th
Compressor Suction temperature
T4
Outdoor air temperature
T3
Heat exchanger temperature
TL
Heat exchanger outlet refrigerant(cooling) temperature
T2
Plate heat exchanger inlet refrigerant(cooling) temperature
T2B
Plate heat exchanger outlet refrigerant(cooling) temperature
Tw_in
Inlet water temperature
Tw_out
Outlet water temperature
T5
DHW tank temperature
Tw2
Zone 2 water temperature
Tbt
Balance tank temperature
T1
IBH/AHS outlet water temperature
Ta
Indoor ambient temperature
SV
3-way valves
Pump_I
Integrated circulation pump
P_c (Pump_C)
Zone 2 pump
P_o (Pump_O)
Additional circulation pump(for Zone 1)
P_s (Pump_S)
Solar heating loop circulation pump
P_d (Pump_D)
DHW pipe pump
AHS
Additional heat source
IBH
Internal backup heater
TBH
Tank booster heater
SG
SG-ready signal 1
EVU
SG-ready signal 2
HMI
Human-machine interface (wired controller)
49
16125300004119 V.D
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>