FireLite MDF-300 Dual Monitor Module Installation Guide
- July 16, 2024
- FIRELITE
Table of Contents
FireLite MDF-300 Dual Monitor Module
SPECIFICATIONS
Normal Operating Voltage: | 15 to 32 VDC |
---|---|
Maximum Current Draw: | 6.4 mA (LED on) |
Average Operating Current: | 750µA (LED flashing) |
EOL Resistance: | 47K Ohms |
Maximum SLC Wiring Resistance: | 40 Ohms |
Maximum IDC wiring resistance: | 1,500 Ohms |
Maximum IDC Voltage: | 11 Volts |
Maximum IDC Current: | 240µA |
Temperature Range: | 32˚F to 120˚F (0˚C to 49˚C) |
Humidity: | 10% to 93% Non-condensing |
Dimensions: | 41/2 in H × 4.275 in W × 1.4 in D (Mounts to a 4 in square by |
21/8 in deep box.)
Accessories:| SMB500 Electrical Box
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The Dual Monitor Module is intended for use in addressable, two wire systems. It provides two independent 2-wire initiating device circuits (IDC), at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices, or either normally open or normally closed security devices.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
FireLite system control panel (list available from FireLite).
MOUNTING
Mounts directly to 4-inch square electrical boxes, Figure 2A). The box must
have a minimum depth of 21/8 inches. Surface mounted electrical boxes (SMB500)
are available from Fire Lite.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power limited wiring only.
-
Install module wiring in accordance with the job drawings and appropriate wiring diagrams.
-
Set the address on the module per job drawings.
NOTE: Monitor module L (using terminals 6 and 7) responds at the address set on the code switches. Monitor module H (using terminals 8 and 9) will automatically respond at the next higher address. For example, if the code switches are set to 76, module L will respond at address 76 and module H will respond at address 77. Use caution to avoid duplicate addressing of modules on the system. -
Secure module to electrical box (supplied by installer), as shown in Figure 2.