Johnson Controls RAC134-18B2 Mini Split Systems User Guide

June 12, 2024
Johnson Controls

RAC134-18B2 Mini Split Systems
User Guide

Description

The RAC134 models are part of our successful 13.4 SEER2 Regional Minimum Efficiency in the northern United States and Canada. These outdoor units are specifically designed to be matched with our residential indoor coils, furnaces,  and air handlers to provide a complete system solution.
Figure 1: Installation map

Due to continuous product improvement, specifications are subject to change without notice.
Visit us on the web at www.simplygettingthejobdone.com. Additional rating information can be found at www.ahridirectory.org.
This document is only for distribution use – it is not to be used at point of retail sale.

Certification

Warranty summary

Standard 5-year limited parts warranty.
Standard 10-year limited compressor warranty.
Extended 10-year limited parts warranty when product is registered online within 90 days of purchase for replacement or closing for new home construction.
Warranty does not apply to R-22 models, three-phase models, or Internet sales.
See the limited warranty certificate in the User’s Information Manual for details.

Features

  • Small footprint – Minimum footprint for easier handling, transportation, and installation.

  • Easier installation – Independent panels provide quick access for unit setup. Installation time is reduced by easy power and control wiring access. Select indoor matches with factory mounted TXVs are available for quicker system  installation. The filter-drier is shipped loose for installation in the field. The unit is factory-charged for 15 ft refrigeration piping. The small base dimension and reduced unit clearances make for easier retrofits.

  • Accessible information – QR code on unit provides quick access to technical documents and warranty information.

  • Durable finish – The coated steel wire fan guard, coated external fasteners, and pretreated G90-equivalent galvanized steel chassis components resist corrosion and rust creep.
    Champagne colored powder coat paint further protects external panels.

  • Quality coils – The high efficiency microchannel aluminum coil is manufactured using an improved material system, providing reliable performance and small unit size.

  • Rugged coil protection – Coils are protected from mechanical damage by a proven stamped steel coil guard design.

  • Protected compressor – Compressors are protected internally by a high-pressure relief valve and a temperature sensor, and externally by the system high-pressure switch.

  • Reliable operation – Ball bearing fan motors provide superior performance in extreme temperatures.

  • Environmentally friendly – CFC-free R-410A refrigerant delivers environmentally friendly performance with zero ozone depletion.

  • Top discharge – Warm air is blown up, away from the structure and any landscaping, allowing compact location on multi-unit applications.

  • Low operating sound levels – Developed using CFD and FEA tools, the sturdy cabinet and top design provides sound performance of 76 dBA or lower. Compatible accessories for further sound reduction are also available.

  • Better service access – Diagonal base valves with open access for low-loss fittings, single panel access to the electrical controls, swing out control box for full corner access, and removable fan guard allow easy access for unit  maintenance.

  • Agency listed – Safety certified by CSA to UL 1995/CSA 22.2. Performance certified to ANSI/AHRI Standard 210/240 in accordance with the Unitary Small Equipment certification program.

Nomenclature

Table 1: Nomenclature

Brand R R = OTC factory-branded
Product type AC AC = Air conditioner
Nominal series efficiency and staging 134 134 = 13.4 (SEER2 –

US northern region)
Nominal unit capacity (MBH)| 18| 18 = 1.5 ton
24 = 2 ton
30 = 2.5 ton
36 = 3 ton
42 = 3.5 ton
48 = 4 ton
60 = 5 ton
Refrigerant| B| B = R-410A
Voltage (voltage-phase-hertz)| 2| 2 = 208/230-1-60
Generation (major revision)| 1| 1 = First generation
2 = Second generation
Factory option| S| S = Standard (no options)
Style letter (minor revision) not used for ordering| A| A = Style A
B = Style B

Physical and electrical data

Table 2: Physical and electrical data

Outdoor unit model| RAC134
18B21S| RAC134
24B21S| RAC134
30B21S| RAC134
36B21S| RAC134
42B21S| RAC134
48B21S| RAC134
60B21S
---|---|---|---|---|---|---|---
Unit supply voltage| 208/230 V, 1 phase, 60 Hz
Normal voltage
range (V)1| 187 to 252
Minimum circuit ampacity (A)| 8.9| 11.3| 15.3| 19.6| 21.1| 25.7| 29.1
Maximum overcurrent device (A)2| 15| 15| 25| 30| 35| 45| 50
Minimum overcurrent device (A)3| 15| 15| 20| 20| 25| 30| 30
Compressor type4| Rotary| Rotary| Scroll| Scroll| Scroll| Scroll| Scroll
Compressor rated load| 6.5| 8.4| 11.7| 14.7| 15.9| 19.5| 22.2
Compressor locked rotor| 33.0| 53.0| 71.3| 75.0| 112.3| 130.0| 128.0
Crankcase heater| No| No| No| No| No| No| No
Factory external discharge muffler| No| No| No| No| No| No| No
HS kit required with TXV| No| No| No| No| No| No| No

Table 2: Physical and electrical data

Outdoor unit model| RAC134

18B21S

| RAC134

24B21S

| RAC134

30B21S

| RAC134

36B21S

| RAC134

42B21S

| RAC134

48B21S

| RAC134

60B21S

---|---|---|---|---|---|---|---
HS Kit Part Number

(S1-2SA067*****)5

| 22006| 22006| 10106| 10106| 10106| 10106| 10106
Fan diameter (in.)| 18| 18| 18| 22| 22| 24| 26
Fan motor type| PSC| PSC| PSC| PSC| PSC| PSC| PSC
Fan motor rated HP| 1/8| 1/8| 1/8| 1/4| 1/4| 1/4| 1/4
Fan motor rated load

(A)

| 0.7| 0.7| 0.7| 1.3| 1.3| 1.3| 1.3
Fan motor nominal

RPM

| 1075| 1075| 1075| 850| 850| 850| 850
Fan motor nominal

CFM

| 2150| 2575| 2575| 2875| 3350| 3550| 4300
Coil face area (sq. ft)| 11.07| 12.45| 12.45| 13.83| 17.37| 18.74| 23.40
Coil rows deep| 1| 1| 1| 1| 1| 1| 1
Coil fins per inch| 23| 23| 23| 23| 23| 23| 23
Liquid refrigeration piping outdoor unit

(field-installed)

| 3/8| 3/8| 3/8| 3/8| 3/8| 3/8| 3/8
Vapor refrigeration piping outdoor unit (field- installed)6| 3/4| 3/4| 3/4| 3/4| 7/8| 7/8| 1 1/8‡
Unit charge (lb-oz)7| 3-3| 3-4| 3-4| 4-3| 4-15| 4-11| 5-9
Charge (oz/ft)| 0.62| 0.62| 0.62| 0.62| 0.67| 0.67| 0.75
Operating weight (lb)| 120| 135| 130| 150| 195| 200| 230

Physical and electrical data notes

  1. Rated in accordance with AHRI Standard 110-2012, utilization range A.
  2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
  3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
  4. Rotary compressor models are limited to an equivalent length of refrigeration piping of 100 ft with no exceptions.
  5. Refer to the Hard Start Kit Accessory Installation Manual for the hard start kit part number for each model. The hard start kit is a field installed accessory.
  6. For applications with non-standard vapor line sizes, refer to the Applications and accessories section.
  7. The unit charge is correct for the outdoor unit, smallest matched indoor unit, and 15 ft of refrigerant tubing. For tubing lengths other than 15 ft, add or subtract the amount of refrigerant, using the difference in actual refrigeration  piping length (not the equivalent length) multiplied by the per foot value.
    ‡ The adapter fitting must be field installed for the required 1 1/8 in. refrigeration piping.

Illustration of dimensions

Figure 2: Unit dimensions

Dimensions

Table 3: Dimensions

Outdoor unit model| Dimensions (in.)| Refrigerant connection service valve size (in.)
---|---|---
A| B| C| Liquid| Vapor
RAC13418B21S| 30| 24| 24| 3/8| 3/4
RAC13424B21S| 33 1/4| 24| 24
RAC13430B21S| 33 1/4| 24| 24
RAC13436B21S| 30| 29 1/4| 29 1/4
RAC13442B21S| 36 1/4| 29 1/4| 29 1/4| 7/8
RAC13448B21S| 33 1/4| 35 1/4| 31 3/4
RAC13460B21S| 36 1/4| 38| 34 1/4| 7/8‡

Dimensions data notes
‡ The adapter fitting must be field-installed for the required 1 1/8 in. refrigeration piping.

  • All dimensions are in inches and are subject to change without notice.
  • The overall height is from the bottom of the base pan to the top of the fan guard.
  • The overall length and width include screw heads.

System charge table

Table 4: System charge table

Outdoor unit model| RAC134
18B21S| RAC134
24B21S| RAC134
30B21S| RAC134
36B21S| RAC134
42B21S| RAC134
48B21S| RAC134
60B21S
---|---|---|---|---|---|---|---
Required indoor

metering device 1,2

| BA1| BA1| BA1| BC1| BC1| BC1| BC1
Indoor coil model 3,4,5| Additional charge (oz)
RFCB18BXEMP2S1A| 2| —| —| —| —| —| —
RFCB24CXEMP2N1A| —| 3| —| —| —| —| —
RFCB30DXEMP2N1A| —| —| 6| —| —| —| —
RFCB36DXEMP2N1A| —| —| 6| 0| —| —| —
RFCC36DXEMP2N1A| —| —| 6| 0| —| —| —
RFCC42FXEMP2N1A| —| —| —| —| 2| —| —
RFCC48GXEMP2N1A| —| —| —| —| —| 5| —
RFCC60HXEMP2N1A| —| —| —| —| —| —| 6
RFCD48GXEMP2N1A| —| —| —| —| —| 5| —
RFCD60HXEMP2N1A| —| —| —| —| —| —| 6
XAF/XAHB24B| 2| 0| —| —| —| —| —
XAF/XAHC30C| —| 3| 0| —| —| —| —
XAF/XAHC36D| —| —| 6| 0| —| —| —
XAF/XAHC60H| —| —| —| —| —| —| 6
XAF/XAHD42E| —| —| —| 2| 0| —| —
XAF/XAHD48F| —| —| —| —| 2| 0| —
XAF/XAU/XAHA18A| 0| —| —| —| —| —| —
XAF/XAU/XAHA24B| 2| 0| —| —| —| —| —
XAF/XAU/XAHB30C| —| 3| 0| —| —| —| —
XAF/XAU/XAHB36D| —| —| 6| 0| —| —| —
XAF/XAU/XAHC42E| —| —| —| 2| 0| —| —
XAF/XAU/XAHC48F| —| —| —| —| 2| 0| —
XAF/XAU/XAHC60G| —| —| —| —| —| 5| 0
XAF/XAU/XAHD60G| —| —| —| —| —| 5| 0
XAF/XAU/XAHD60H| —| —| —| —| —| —| 6
XAFA30D| —| —| 6| —| —| —| —
XAFB18A| 0| —| —| —| —| —| —
XAFB36E| —| —| —| 2| —| —| —

System charge A-coil data notes

  1. For applications requiring a TXV, use S1-1TVM*** series kit.
  2. A TXV kit must be used with these indoor units to obtain system performance.
  3. Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower time delay.
  4. Do not use XAF/XAU coils in horizontal applications. Do not use XAH coils in upflow/downflow applications.
  5. Charge adders shown above do not indicate that coils are rated for every application. Refer to the Performance data tables for actual performance for specified system matches. Obtain certified system ratings from http://www.ahridirectory.org.

Charging

  1. Check the factory unit charge listed on the unit nameplate to verify the refrigerant charge for the outdoor unit, the smallest matched indoor unit, and the 15 ft of interconnecting refrigeration piping.
  2. Verify the indoor metering device and additional charge required for the specific matched indoor unit in the system using Table .
  3. Add additional charge for the amount of interconnecting refrigeration piping greater than 15ft at the rate specified in Table.
  4. For installations requiring additional charge, weigh in refrigerant for the specific matching indoor unit and actual refrigeration piping length.
  5. After weighing in the charge adders for the matched indoor unit and refrigeration piping, verify the system operation against the temperatures and pressures in the charging chart for the outdoor unit. Locate the charging charts on  the outdoor unit and in the Service Data Application Guide on www.simplygettingthejobdone.com. Follow the subcool or superheat charging procedure in the Installation Manual according to the type of indoor metering device in  the system, and allow 10 min after each charge adjustment for the system operation to stabilize. Record the charge adjustment made to match the charging chart.
  6. Permanently stamp the unit nameplate with the total system charge defined as follows: total system charge = base charge (as shipped) + charge adder for matched indoor unit + charge adder for actual refrigeration piping length +  charge adjustments to match the charging chart.

Air handler capacity

Table 5: Air handler capacity

Outdoor unit model| Air handler model| Air handler

width (in.)

| Indoor coil model| Rated CFM| Net cool

(MBH)

| Sens cool

(MBH)

| SEER2| EER2
---|---|---|---|---|---|---|---|---
RAC13418B21S| EBE15A| 19.6| XAF/XAUA24B| 725| 18.00| 13.90| 14.00| 12.00
RAC13418B21S| EBE15A| 19.6| XAHA18A| 725| 18.00| 13.80| 13.75| 11.75
RAC13418B21S| EBE15A| 19.6| XAHA24B| 725| 18.00| 13.90| 14.00| 12.00
RAC13418B21S| JMET08BS2N1| 17.5| XAFB18A| 650| 18.00| 12.90| 16.00| 13.00
RAC13418B21S| JMET08BS2N1| 17.5| XAFB18A| 725| 18.00| 13.70| 15.00| 12.50
RAC13418B21S| JMET08BS2N1| 17.5| XAFB24B| 650| 18.00| 13.00| 16.00| 13.00
RAC13418B21S| JMET08BS2N1| 17.5| XAFB24B| 725| 18.00| 13.80| 15.00| 12.50
RAC13418B21S| JMET08BS2N1| 17.5| XAHB24B| 700| 18.00| 13.70| 15.00| 12.50
RAC13418B21S| JMET12BS2N1| 17.5| XAFB18A| 575| 17.80| 12.30| 16.00| 13.00
RAC13418B21S| JMET12BS2N1| 17.5| XAFB18A| 650| 18.00| 13.30| 14.75| 12.25
RAC13418B21S| JMET12BS2N1| 17.5| XAFB24B| 575| 17.80| 12.30| 16.00| 13.00
RAC13418B21S| JMET12BS2N1| 17.5| XAFB24B| 675| 18.00| 13.50| 15.00| 12.50
RAC13418B21S| JMET12BS2N1| 17.5| XAHB24B| 650| 18.00| 13.30| 15.00| 12.50
RAC13418B21S| RFCB18BXEMP2S1| 17.5| —| 650| 18.00| 13.30| 15.00| 12.50
RAC13424B21S| EBE15A| 19.6| XAF/XAUA24B| 725| 24.00| 16.90| 14.75| 12.50
RAC13424B21S| EBE15A| 19.6| XAF/XAUB30C| 775| 24.00| 17.50| 15.25| 13.00
RAC13424B21S| EBE15A| 19.6| XAFB24B| 750| 24.00| 17.00| 15.00| 12.75
RAC13424B21S| EBE15A| 19.6| XAFC30C| 775| 24.00| 17.50| 15.25| 13.00
RAC13424B21S| EBE15A| 19.6| XAHA24B| 725| 24.00| 16.90| 14.75| 12.50
RAC13424B21S| EBE15A| 19.6| XAHB24B| 750| 24.00| 17.00| 15.00| 12.75
RAC13424B21S| EBE15A| 19.6| XAHB30C| 750| 24.00| 17.30| 15.25| 13.00
RAC13424B21S| EBE15A| 19.6| XAHC30C| 775| 24.00| 17.50| 15.25| 13.00
RAC13424B21S| JMET08BS2N1| 17.5| XAF/XAUB30C| 850| 24.00| 17.40| 16.00| 13.00
RAC13424B21S| JMET08BS2N1| 17.5| XAF/XAUB30C| 725| 24.00| 17.10| 15.00| 12.50
RAC13424B21S| JMET08BS2N1| 17.5| XAFB24B| 825| 24.00| 16.90| 15.75| 12.75
RAC13424B21S| JMET08BS2N1| 17.5| XAFB24B| 725| 24.00| 16.80| 14.75| 12.25
RAC13424B21S| JMET08BS2N1| 17.5| XAHB24B| 700| 24.00| 16.70| 14.50| 12.25
RAC13424B21S| JMET08BS2N1| 17.5| XAHB30C| 700| 24.00| 17.00| 15.00| 12.50
RAC13424B21S| JMET12BS2N1| 17.5| XAF/XAUB30C| 850| 24.00| 17.40| 16.00| 13.00

Table 12: Furnace capacity

Outdoor unit model| Furnace model| Furnace

width (in.)

| Indoor coil model| Rated CFM| Net cool

(MBH)

| Sens cool

(MBH)

| SEER2| EER2
---|---|---|---|---|---|---|---|---
RAC13448B21S| TM9Y100C20MP11| 24.5| XAFD48F| 1400| 46.50| 32.80| 13.50| 11.25
RAC13448B21S| TM9Y100C20MP11| 21.0| XAHC48F| 1375| 46.00| 32.20| 13.50| 11.25
RAC13448B21S| TM9Y100C20MP11| 21.0| XAHC60G| 1400| 47.00| 33.00| 13.75| 11.50
RAC13448B21S| TM9Y100C20MP11| 24.5| XAHD48F| 1375| 46.00| 32.20| 13.50| 11.25
RAC13448B21S| TM9Y100C20MP11| 21.0| XAHD60G| 1375| 47.00| 32.80| 13.75| 11.50
RAC13448B21S| TM9Y120D20MP11| 24.5| XAF/XAUD60G| 1450| 48.00| 34.00| 14.00| 11.75
RAC13448B21S| TM9Y120D20MP11| 24.5| XAFD48F| 1450| 47.00| 33.40| 13.75| 11.50
RAC13448B21S| TM9Y120D20MP11| 24.5| XAHD48F| 1450| 47.00| 33.40| 13.75| 11.50
RAC13448B21S| TM9Y120D20MP11| 21.0| XAHD60G| 1425| 47.50| 33.60| 14.00| 11.50

Furnace capacity – 5 ton

Table 13: Furnace capacity

Outdoor unit model| Furnace model| Furnace
width (in.)| Indoor coil model| Rated CFM| Net cool
(MBH)| Sens cool
(MBH)| SEER2| EER2
---|---|---|---|---|---|---|---|---
RAC13460B21S| RGF19080CE20MP13| 21.0| XAF/XAUC60G| 1750| 56.00| 41.00| 13.50| 11.00
RAC13460B21S| RGF19080CE20MP13| 24.5| XAF/XAUD60G| 1775| 56.00| 41.00| 13.40| 11.25
RAC13460B21S| RGF19080CE20MP13| 24.5| XAF/XAUD60H| 1750| 56.00| 41.00| 13.50| 11.25
RAC13460B21S| RGF19080CE20MP13| 21.0| XAFC60H| 1750| 56.00| 41.00| 13.50| 11.25
RAC13460B21S| RGF19080CE20MP13| 21.0| XAHC60G| 1750| 56.00| 41.00| 13.50| 11.00
RAC13460B21S| RGF19080CE20MP13| 21.0| XAHC60H| 1750| 56.00| 41.00| 13.50| 11.25
RAC13460B21S| RGF19080CE20MP13| 21.0| XAHD60G| 1725| 56.00| 40.50| 13.50| 11.25
RAC13460B21S| RGF19080CE20MP13| 24.5| XAHD60H| 1750| 56.00| 41.00| 13.50| 11.25
RAC13460B21S| RGF19100CE20MP13| 21.0| XAF/XAUC60G| 1725| 56.00| 40.50| 13.40| 11.00
RAC13460B21S| RGF19100CE20MP13| 24.5| XAF/XAUD60G| 1600| 55.00| 39.00| 13.40| 11.25
RAC13460B21S| RGF19100CE20MP13| 24.5| XAF/XAUD60H| 1575| 55.00| 39.00| 13.50| 11.25
RAC13460B21S| RGF19100CE20MP13| 21.0| XAFC60H| 1600| 55.00| 39.50| 13.50| 11.25
RAC13460B21S| RGF19100CE20MP13| 21.0| XAHC60G| 1725| 56.00| 40.50| 13.40| 11.00
RAC13460B21S| RGF19100CE20MP13| 21.0| XAHC60H| 1600| 55.00| 39.50| 13.50| 11.25
RAC13460B21S| RGF19100CE20MP13| 21.0| XAHD60G| 1700| 55.50| 40.00| 13.50| 11.25
RAC13460B21S| RGF19100CE20MP13| 24.5| XAHD60H| 1725| 55.50| 40.50| 13.50| 11.25
RAC13460B21S| RGF19120DE20MP13| 24.5| XAF/XAUD60G| 1625| 55.00| 39.50| 13.40| 11.00
RAC13460B21S| RGF19120DE20MP13| 24.5| XAF/XAUD60H| 1625| 55.00| 39.50| 13.40| 11.25
RAC13460B21S| RGF19120DE20MP13| 21.0| XAHD60G| 1600| 55.00| 39.50| 13.40| 11.00
RAC13460B21S| RGF19120DE20MP13| 24.5| XAHD60H| 1600| 55.00| 39.50| 13.40| 11.00
RAC13460B21S| RGF1L080CE20MP12| 21.0| XAF/XAUC60G| 1625| 55.00| 39.50| 13.40| 11.00
RAC13460B21S| RGF1L080CE20MP12| 24.5| XAF/XAUD60G| 1625| 55.50| 39.50| 13.40| 11.25
RAC13460B21S| RGF1L080CE20MP12| 24.5| XAF/XAUD60H| 1625| 55.00| 39.50| 13.50| 11.25
RAC13460B21S| RGF1L080CE20MP12| 21.0| XAFC60H| 1625| 55.00| 39.50| 13.50| 11.25
RAC13460B21S| RGF1L080CE20MP12| 21.0| XAHC60G| 1625| 55.00| 39.50| 13.40| 11.00
RAC13460B21S| RGF1L080CE20MP12| 21.0| XAHC60H| 1625| 55.00| 39.50| 13.50| 11.25
RAC13460B21S| RGF1L080CE20MP12| 21.0| XAHD60G| 1600| 55.00| 39.00| 13.40| 11.00
RAC13460B21S| RGF1L080CE20MP12| 24.5| XAHD60H| 1625| 55.00| 39.50| 13.50| 11.25
RAC13460B21S| RGF1L100CE20MP12| 21.0| XAF/XAUC60G| 1725| 55.50| 40.50| 13.40| 11.00
RAC13460B21S| RGF1L100CE20MP12| 24.5| XAF/XAUD60G| 1625| 55.00| 39.50| 13.40| 11.25
RAC13460B21S| RGF1L100CE20MP12| 24.5| XAF/XAUD60H| 1625| 55.00| 39.50| 13.50| 11.25
RAC13460B21S| RGF1L100CE20MP12| 21.0| XAFC60H| 1625| 55.00| 39.50| 13.50| 11.25
RAC13460B21S| RGF1L100CE20MP12| 21.0| XAHC60G| 1625| 55.00| 39.50| 13.40| 11.00
RAC13460B21S| RGF1L100CE20MP12| 21.0| XAHC60H| 1625| 55.00| 39.50| 13.50| 11.25
RAC13460B21S| RGF1L100CE20MP12| 21.0| XAHD60G| 1675| 55.50| 40.00| 13.40| 11.00
RAC13460B21S| RGF1L100CE20MP12| 24.5| XAHD60H| 1625| 55.00| 39.50| 13.50| 11.25
RAC13460B21S| RGF1L120CE20MP12| 21.0| XAF/XAUC60G| 1625| 55.50| 39.50| 13.40| 11.00
RAC13460B21S| RGF1L120CE20MP12| 24.5| XAF/XAUD60G| 1650| 55.50| 40.00| 13.40| 11.25
RAC13460B21S| RGF1L120CE20MP12| 24.5| XAF/XAUD60H| 1650| 55.50| 40.00| 13.50| 11.25
RAC13460B21S| RGF1L120CE20MP12| 21.0| XAFC60H| 1650| 55.50| 40.00| 13.50| 11.25
RAC13460B21S| RGF1L120CE20MP12| 21.0| XAHC60G| 1650| 55.50| 40.00| 13.40| 11.00
RAC13460B21S| RGF1L120CE20MP12| 21.0| XAHC60H| 1650| 55.50| 40.00| 13.50| 11.25
RAC13460B21S| RGF1L120CE20MP12| 21.0| XAHD60G| 1625| 55.00| 39.50| 13.40| 11.00
RAC13460B21S| RGF1L120CE20MP12| 24.5| XAHD60H| 1625| 55.00| 39.50| 13.50| 11.25
RAC13460B21S| RGF1L130DE20MP12| 24.5| XAF/XAUD60G| 1800| 56.00| 41.00| 13.40| 11.00
RAC13460B21S| RGF1L130DE20MP12| 24.5| XAF/XAUD60H| 1800| 56.00| 41.50| 13.50| 11.25

Table 13: Furnace capacity

Outdoor unit model| Furnace model| Furnace
width (in.)| Indoor coil model| Rated CFM| Net cool
(MBH)| Sens cool
(MBH)| SEER2| EER2
---|---|---|---|---|---|---|---|---
RAC13460B21S| RGF1L130DE20MP12| 21.0| XAHD60G| 1750| 56.00| 41.00| 13.50| 11.25
RAC13460B21S| RGF1L130DE20MP12| 24.5| XAHD60H| 1775| 56.00| 41.50| 13.50| 11.25
RAC13460B21S| TM8Y100C20MP11| 21.0| XAF/XAUC60G| 1725| 55.50| 40.50| 13.40| 11.00
RAC13460B21S| TM8Y100C20MP11| 24.5| XAF/XAUD60G| 1750| 55.50| 40.50| 13.40| 11.00
RAC13460B21S| TM8Y100C20MP11| 21.0| XAFC60H| 1725| 55.50| 41.00| 13.40| 11.00
RAC13460B21S| TM8Y100C20MP11| 21.0| XAHC60G| 1725| 55.50| 40.50| 13.40| 11.00
RAC13460B21S| TM8Y100C20MP11| 21.0| XAHC60H| 1725| 55.50| 41.00| 13.40| 11.00
RAC13460B21S| TM8Y100C20MP11| 21.0| XAHD60G| 1700| 55.50| 40.50| 13.40| 11.00
RAC13460B21S| TM8Y120C20MP11| 21.0| XAF/XAUC60G| 1725| 55.50| 40.50| 13.40| 11.00
RAC13460B21S| TM8Y120C20MP11| 24.5| XAF/XAUD60G| 1750| 55.50| 40.50| 13.40| 11.00
RAC13460B21S| TM8Y120C20MP11| 21.0| XAFC60H| 1725| 55.50| 41.00| 13.40| 11.00
RAC13460B21S| TM8Y120C20MP11| 21.0| XAHC60G| 1725| 55.50| 40.50| 13.40| 11.00
RAC13460B21S| TM8Y120C20MP11| 21.0| XAHC60H| 1725| 55.50| 41.00| 13.40| 11.00
RAC13460B21S| TM8Y120C20MP11| 21.0| XAHD60G| 1700| 55.50| 40.50| 13.40| 11.00
RAC13460B21S| TM9Y100C20MP11| 21.0| XAF/XAUC60G| 1575| 55.00| 39.00| 13.40| 11.00
RAC13460B21S| TM9Y100C20MP11| 24.5| XAF/XAUD60G| 1575| 55.00| 39.00| 13.40| 11.00
RAC13460B21S| TM9Y100C20MP11| 24.5| XAF/XAUD60H| 1575| 55.00| 39.50| 13.40| 11.00
RAC13460B21S| TM9Y100C20MP11| 21.0| XAFC60H| 1575| 55.00| 39.50| 13.40| 11.00
RAC13460B21S| TM9Y100C20MP11| 21.0| XAHC60G| 1575| 55.00| 39.00| 13.40| 11.00
RAC13460B21S| TM9Y100C20MP11| 21.0| XAHC60H| 1600| 55.00| 39.50| 13.40| 11.00
RAC13460B21S| TM9Y100C20MP11| 21.0| XAHD60G| 1525| 54.50| 38.50| 13.40| 11.00
RAC13460B21S| TM9Y100C20MP11| 24.5| XAHD60H| 1550| 54.50| 39.00| 13.40| 11.00
RAC13460B21S| TM9Y120D20MP11| 24.5| XAF/XAUD60G| 1700| 55.50| 40.50| 13.40| 11.00
RAC13460B21S| TM9Y120D20MP11| 24.5| XAF/XAUD60H| 1675| 55.00| 40.00| 13.40| 11.00
RAC13460B21S| TM9Y120D20MP11| 21.0| XAHD60G| 1650| 55.00| 39.50| 13.40| 11.00
RAC13460B21S| TM9Y120D20MP11| 24.5| XAHD60H| 1675| 55.00| 40.00| 13.40| 11.00

Furnace capacity data notes

  • For rated condition information, see Air handler capacity data notes.
  • High-efficiency motor furnaces have blower off delay (BOD) standard.
  • PSC furnaces use coil only ratings.

Applications and accessories

Refer to the Price Manual for specific model numbers.
Table 14: Standard application limits

Standard application limits

Maximum line set equivalent length| 80 ft
Outdoor ambient temperature limits
Cooling operation| Maximum DB| 115°F
Minimum DB| 55°F

Note: For low ambient and long line set applications, see the accessories listed below.
Non-standard line set applications: For installations with reduced diameter or long line sets, refer to the current version of the Piping Application Guide P/N 247077, available in the Application Bulletins section on www.simplygettingthejobdone.org.
OD Unit Anti-Short Cycle Kit (10 Pack) (S1-2TD08700124BK): A time delay that prevents rapid compressor restarting as a result of power interruption, limit switch operation, or thermostat resetting. Not required for AC models with factory electronic controls.
Standard Low Ambient Control Kit (S1-2LA06700424): Allows the use of air conditioning at low outdoor ambient temperatures down to +20°F (-7°C). For use with all R-410A singlestage AC models.
Advanced Low Ambient Control Kit (S1-2LA04701024): Contains the necessary components and controls to allow cooling operation down to -20ºF (-29ºC). For use with some R-410A single-stage AC and HP models. This accessory can  only be applied to models that contain a PSC outdoor fan motor.
Low Pressure Switch Kit (S1-2PS06700524): Provides field installed low pressure (loss of charge) protection. Not required for AC models with factory electronic controls.
High Ambient Outdoor Fan Motor (S1-FHMHT): Class F 70°C motor to allow cooling operation up to 160ºF air entering the outdoor coil. For use with all R-410A single-stage AC models containing R-410A refrigerant only.
Outdoor Communicating Board Kit (S1-33102952310): Electronic control upgrade for standard AC units to provide compatibility with the Hx™ Touch Screen Thermostat used in communicating mode.
Start Assist Kit (S1-2SA067****): Provides increased compressor starting torque for areas with low supply voltage. Required for units with reciprocating compressors when applied with indoor TXV, and for all units when applied with  long linesets or low ambient kits. May be factory installed on select AC units (see the Physical and electrical data table). Refer to the Price Pages or Source 1 SmartSearch for the correct kit for each application.
Compressor Crankcase Heater Kit (S1-025-
-): A wrap-around electrical resistance heater that warms the compressor sump, reducing the chance of liquid slugging on startup.
Required on all long lineset and low ambient applications. Refer to the Price Pages or Source 1 SmartSearch for the correct part for each application.
Anchor Bracket Kit (S1-1HK0601): Firmly anchors unit to pad or support structure. When properly installed, approved for ground-mounted or roof- mounted applications.
Indoor TXV Kit (S1-1TVM
): Thermal expansion valves precisely meter refrigerant for optimum performance over a wide range of conditions. See the System charge tables or refer to the Price Pages or Source 1 Smart Search for the  TXV part number for each AC model.
Winter Cover Kit (S1-CCVRE*): Custom fit winter cover protects AC outdoor unit from debris during the off-season. Remove before unit operation. Refer to the Price Pages or Source 1 SmartSearch for the correct cover for each application.
Touch-up Paint (S1-5130153**
: Color matched aerosol paint for touching up unit chassis and panels. Refer to the Price Pages or Source 1 SmartSearch for the correct color for each application.
Compressor Sound Blanket (S1-01007xxx000): A field installed dense foam cover that provides 2 dBA sound level reduction. Refer to the Price Pages or Source 1 SmartSearch for the correct blanket for each application.
Thermostat: Compatible thermostat controls are available through accessory sourcing. For optimum performance, these outdoor units are fully compatible with our residential Hx™ Touch Screen Thermostats available through Source 1. For more information, refer to the Thermostats & Controllers section of the Offering Catalog.

Sound power rating
Table 15: Sound power data– stage 2– Cooling – Octave Band Sound Power Level (db re. 1-pW)

Outdoor unit model| Power level 63 (Hz)| Power level 125 (Hz)| Power level 250 (Hz)| Power level 500 (Hz)| Power level 1000 (Hz)| Power level 2000 (Hz)| Power level 000 (Hz)| Power level 000 (Hz)| dBA| SQI
---|---|---|---|---|---|---|---|---|---|---
RAC13418B21S| 68| 69| 66| 67| 68| 67| 62| 56| 73| 19.0
RAC13424B21S| 69| 71| 66| 68| 66| 63| 59| 55| 74| 19.1
RAC13430B21S| 68| 72| 64| 68| 64| 62| 59| 54| 73| 19.1
RAC13436B21S| 68| 77| 68| 75| 66| 63| 60| 56| 74| 19.1
RAC13442B21S| 69| 73| 68| 70| 67| 65| 63| 59| 76| 19.1
RAC13448B21S| 69| 77| 71| 71| 71| 64| 61| 59| 76| 19.0
RAC13460B21S| 69| 72| 73| 72| 71| 69| 66| 63| 77| 19.1

Mechanical specifications

Manufacture and certifications

  • Units shall be manufactured in an ISO 9001 certified facility.
  • Units shall be certified by CSA to UL 1995/CSA 22.2 and performance certified to ANSI/AHRI Standard 210/240.
  • Units shall be sound tested according to ANSI/AHRI Standard 270.
  • Certified matched system ratings shall be available for download from the AHRI online directory at www.ahridirectory.org.

Unit application

  • Units shall be approved for cooling operation between 55ºF and 115°F without modification.
  • Units shall be approved for line sets up to 80 ft equivalent length without modification.
  • Units shall be approved for installation within 6 in. of a flat vertical wall without modification, according to the instructions in the technical literature.
  • Units shall be certified to the 5th Edition (2014) of the Florida Building Code for a combined allowable lateral and uplift wind force of 200 psf and 100 psf, respectively, for both groundmounted and rooftop-mounted applications up to 200 ft above  grade with approved mounting kit.
  • Units shall be designed to 76 dBA or less to minimize sound pollution.

Unit access

  • Units shall have a removable fan guard that can be removed independently of the top for interior access through the top of the unit without damaging the coil.
  • Units shall have two removable stamped steel coil guards for exterior coil access.
  • Units shall have a separate compartment for electrical controls that can be accessed without disturbing the unit airflow.
  • Units shall have a blockoff panel that can be removed to provide interior unit access through the side of the unit.
  • Units shall have a removable blockoff panel and a swing away removable electrical panel that provides sufficient interior unit access for removing the compressor through the side of the unit.

Unit construction

  • Units shall be shipped completely wired, piped, and assembled. Wiring pigtails shall be provided for field control wiring connections. Service valves shall be provided for field refrigerant line connections.
  • Units shall be factory leak checked, run tested, and shipped with a holding charge of R-410A refrigerant.
  • Unit cabinet components shall be G90 equivalent steel finished with powder-coat paint rated at a minimum of 500 h under ASTM B117 testing.
  • Unit base pan shall be stamped G90 equivalent steel finished with powder-coat paint rated at a minimum of 500 h under ASTM B117 testing.
  • Units shall have a single corner post opposite the electrical control box and two independently removable steel coil guard panels to optimize cabinet strength and serviceability.
  • Units shall have L-shaped stamped sheet metal coil guards with punched and extruded slots for maximum panel durability and stiffness.
  • Unit base valves shall be mounted diagonally on the unit base pan with service ports that provide sufficient clearance for low-loss hose fittings.
  • Units shall be constructed with a high-pressure switch for system protection.
  • Units shall be constructed with all badging and labels applied at the factory.

Unit components

  • Compressor shall be hermetic with internal electrical overload protection and internal overpressure protection.
  • Compressor shall be mounted on rubber vibration isolators that do not require the removal of transportation clips or brackets.
  • Outdoor fan shall be direct drive with vertical air discharge for low sound levels.
  • Outdoor fan motor shall be totally enclosed with permanently lubricated ball bearings motors approved for vertical shaft applications.
  • Outdoor coil shall be air cooled and have zinc-coated aluminum microchannel construction for small size and low weight.

Unit warranties

  • Unit manufacturer shall provide a 10-year compressor warranty without a requirement for unit registration.
  • Unit manufacturer shall provide a 5-year parts warranty without a requirement for unit registration.

Typical installation

Figure 3: Typical installation

CAUTION
Care must be taken to prevent ice from damaging the unit. Damage may occur from ice falling onto unit from a sloped roof or from a vertical drip line due to a partial overhang.

Figure 4: Typical installation

Typical field wiring

Figure 5: Typical field wiring

Alternative installation clearances

Figure 6: Alternative installation clearances

Performance data – 1.5 ton

See the following tables for performance and multiplier data for the RAC13418B21S unit.
Condenser only performance data – 1.5 ton
Table 16: Condenser only performance data – 1.5 ton

Saturated suction at  compressor Outdoor ambient temperature
Temperature Pressure
95°F 105°F
(°F) (psig)
kW MBH

kW
35| 107| 18.8| 0.86| 17.5| 0.96| 16.2| 1.07| 15.0| 1.18| 13.9| 1.29| 12.8| 1.41| 11.6| 1.54
40| 118| 20.9| 0.84| 19.4| 0.94| 18.0| 1.06| 16.7| 1.18| 15.4| 1.30| 14.1| 1.43| 12.8| 1.56
45| 130| 23.2| 0.80| 21.5| 0.92| 20.0| 1.04| 18.4| 1.17| 17.0| 1.30| 15.5| 1.44| 14.1| 1.57
50| 142| 25.7| 0.77| 23.8| 0.89| 22.1| 1.02| 20.4| 1.16| 18.7| 1.30| 17.1| 1.44| 15.5| 1.59
55| 156| 28.4| 0.72| 26.3| 0.86| 24.4| 1.00| 22.5| 1.14| 20.6| 1.29| 18.8| 1.44| 17.1| 1.59

Condenser only performance data notes

  • For outdoor unit (condenser) performance only. Data does not include the effects of air handler power or heat.

  • Performance based on 15°F subcooling and 15°F superheat at the outdoor unit base valves:
    a. Increase capacity by 1% for each 2°F increase in subcooling.
    b. Decrease capacity by 1% for each 2°F decrease in subcooling.

  • Maximum recommended condensing temperature is 140°F.

Table 39: Cool multiplier furnace – 4 ton

Furnace model| Indoor coil model| Total capacity| Sensible capacity| kW
---|---|---|---|---
TM8Y100C20MP11| XAFD48F| 1.00| 0.96| 0.94
TM8Y100C20MP11| XAHC60G| 1.02| 0.99| 0.94
TM8Y100C20MP11| XAHD48F| 1.00| 0.96| 0.94
TM8Y100C20MP11| XAHD60G| 1.02| 0.98| 0.96
TM8Y120C20MP11| XAF/XAUC48F| 0.98| 0.94| 0.94
TM8Y120C20MP11| XAF/XAUC60G| 1.02| 0.98| 0.96
TM8Y120C20MP11| XAF/XAUD60G| 1.02| 0.98| 0.96
TM8Y120C20MP11| XAFD48F| 1.00| 0.96| 0.94
TM8Y120C20MP11| XAHC60G| 1.02| 0.99| 0.94
TM8Y120C20MP11| XAHD48F| 1.00| 0.96| 0.94
TM8Y120C20MP11| XAHD60G| 1.02| 0.98| 0.96
TM9Y100C20MP11| XAF/XAUC48F| 0.98| 0.94| 0.96
TM9Y100C20MP11| XAF/XAUC60G| 1.00| 0.96| 0.96
TM9Y100C20MP11| XAF/XAUD60G| 1.00| 0.96| 0.96
TM9Y100C20MP11| XAFD48F| 0.99| 0.96| 0.97
TM9Y100C20MP11| XAHC48F| 0.98| 0.94| 0.96
TM9Y100C20MP11| XAHC60G| 1.00| 0.96| 0.96
TM9Y100C20MP11| XAHD48F| 0.98| 0.94| 0.96
TM9Y100C20MP11| XAHD60G| 1.00| 0.96| 0.96
TM9Y120D20MP11| XAF/XAUD60G| 1.02| 0.99| 0.96
TM9Y120D20MP11| XAFD48F| 1.00| 0.98| 0.96
TM9Y120D20MP11| XAHD48F| 1.00| 0.98| 0.96
TM9Y120D20MP11| XAHD60G| 1.01| 0.98| 0.97

Performance data – 5 ton
See the following tables for performance and multiplier data for the RAC13460B21S unit.
Condenser only performance data – 5 ton
Table 40: Condenser only performance data – 5 ton

Saturated suction at compressor Outdoor ambient temperature
Temperature Pressure
95°F 105°F
(°F) (psig)
kW MBH

kW
35| 107| 59.4| 2.71| 56.9| 3.03| 53.9| 3.35| 50.6| 3.70| 47.1| 4.08| 43.4| 4.51| 39.6| 5.03
40| 118| 65.2| 2.73| 62.4| 3.05| 59.1| 3.37| 55.5| 3.71| 51.7| 4.10| 47.8| 4.53| 43.7| 5.05
45| 130| 71.3| 2.75| 68.2| 3.07| 64.6| 3.38| 60.7| 3.73| 56.6| 4.11| 52.3| 4.55| 47.9| 5.07
50| 142| 77.8| 2.76| 74.3| 3.07| 70.3| 3.39| 66.1| 3.73| 61.7| 4.11| 57.1| 4.56| 52.4| 5.08
55| 156| 84.7| 2.76| 80.7| 3.06| 76.4| 3.38| 71.8| 3.72| 67.0| 4.11| 62.1| 4.56| 57.0| 5.09

Condenser only performance data notes

  • For outdoor unit (condenser) performance only. Data does not include the effects of air handler power or heat.

  • Performance based on 15°F subcooling and 15°F superheat at the outdoor unit base valves:
    a. Increase capacity by 1% for each 2°F increase in subcooling.
    b. Decrease capacity by 1% for each 2°F decrease in subcooling.

  • Maximum recommended condensing temperature is 140°F.

Technical Guide: RAC Series RAC134 Models – 13.4 SEER2 Split-System Air Conditioner – Single-Phase

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Johnson Controls User Manuals

Related Manuals