FIRELITE MMF-302 Alarms Interface Module Instruction Manual
- June 24, 2024
- FIRELITE
Table of Contents
INSTALLATION AND MAINTENANCE INSTRUCTIONS
MMF-302 Interface Module
SPECIFICATIONS
Normal Operating Voltage: | 15 to 32 VDC |
---|---|
Maximum Current Draw: | 5.1mA (LED on) |
Average Operating Current: | 270µA (LED flashing) |
EOL Resistance: | 3.9K ohms |
Maximum IDC Resistance: | 25 Ohms |
IDC Supply Voltage (between Terminals T10 and T11)
Regulated DC Voltage:| 24 VDC power limited
Ripple Voltage:| 0.1 Volts RMS maximum
Current:| 90mA per module
Temperature Range:| 32˚F to 120˚F (0˚C to 49˚C)
Humidity:| 10% to 93% Non-condensing
Dimensions:| 4 1 ⁄2˝ H × 4˝ W × 1 1 ⁄4˝ D (Mounts to a 4˝ square by 21⁄8˝ deep
box.)
Accessories:| SMB500 Electrical Box
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of
service.
Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The MMF-302 Interface Module is intended for use in addressable two-wire
systems, where the individual address of each module is selected using the
built-in rotary switches. This module allows addressable panels to interface
and monitor two-wire conventional smoke detectors. It transmits the status
(normal, open, or alarm) of one full zone of conventional detectors back to
the control panel. All two-wire detectors being monitored must be UL
compatible with this module.
The MMF-302 has a panel controlled LED indicator and can be used to replace an
M302 module in existing systems.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, these modules shall be connected to listed
compatible system control panels only.
In addition, please refer to Fire-Lite Device Compatibility document number
15384 for the list of compatible detectors.
FIGURE 1. CONTROLS AND INDICATORS: MOUNTING
The MMF-302 mounts directly to 4-inch square electrical boxes (see Figure 2).
The box must have a minimum depth of 2 1⁄8 inches. Surface mounted electrical
boxes (SMB500) are available.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power-limited wiring only.
- Install module wiring in accordance with the job drawings and appropriate wiring diagrams.
- Set the address on the module per job drawings.
- Secure module to electrical box (supplied by installer), as shown in Figure 2.
FIGURE 2. MODULE MOUNTING: FIGURE 3. INTERFACE TWO-WIRE
CONVENTIONAL DETECTORS, NFPA STYLE B (CLASS B): C1061-00
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME
MODULE.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT
RESULT IN A FAULT IN A SEPARATE ZONE.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF
CONNECTIONS. DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE. INSTALL
DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS
FIGURE 4. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS, NFPA STYLE D (CLASS
A): C1062-00*
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME
MODULE.
NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT
RESULT IN A FAULT IN A SEPARATE ZONE.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF
CONNECTIONS. DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE. INSTALL
DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS
FIGURE 5. RELAY CONTROL MODULE USED TO DISCONNECT A POWER
SUPPLY: C0945-00
** CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT
RESULT IN A FAULT IN A SEPARATE ZONE.
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
I56-3652-003
FL-460-002
I56-3652-003
©2008 Fire-Lite Alarms, Inc.