MEAN WELL RPD-60 Series 60W Dual Output Medical Grade Owner’s Manual
- July 9, 2024
- MEAN WELL
Table of Contents
MEAN WELL RPD-60 Series 60W Dual Output Medical Grade
Specifications
- Model: RPD-60A, RPD-60B
- Output Voltage:
- CH1: 5V, 5A (0.5 ~ 5.5A)
- CH2: 12V, 2A (0.1 ~ 2.2A) or 24V, 1.5A (0.1 ~ 1.65A)
- Rated Power:
- RPD-60A: 49W
- RPD-60B: 53.5W (peak load: 58.85W)
- Efficiency: RPD-60A (78%), RPD-60B (82%)
- Input Voltage Range: 90 ~ 264VAC, 127 ~ 370VDC
- Frequency Range: 47 ~ 63Hz
- Safety Standards: IEC 60601-1, TUV BS EN/EN 60601-1, ANSI/AAMI ES60601-1, IEC 62368-1, UL 62368-1
- Isolation Level: Primary-Secondary: 2xMOPP, Primary-Earth: 1xMOPP, Secondary-Earth: 1xMOPP
Product Usage Instructions
Installation
- Ensure the input voltage is within the specified range.
- Connect the output voltages according to your application requirements.
- Properly ground the power supply as per safety standards.
Operation
- Power on the RPD-60 series power supply.
- Monitor the output voltages to ensure they meet your device’s requirements.
- In case of any abnormalities or faults, refer to the user manual for troubleshooting.
Maintenance
- Regularly check for any physical damage to the power supply.
- Clean the unit using a dry cloth to prevent dust buildup.
- If encounter issues, contact customer support for assistance.
FAQ
Q: What are the protections provided by the RPD-60 series?
A: The RPD-60 series offers protections against short circuits, overload, and overvoltage.
Q: What applications are suitable for the RPD-60 series?
A: The RPD-60 series is suitable for applications such as oral irrigators, hemodialysis machines, medical computer monitors, and sleep apnea devices.
Features
- 4″×2″ compact size
- Medical safety approved (2 x MOPP) according to ANSI/AAMI ES60601-1 and IEC/BS EN/EN60601-1
- Suitable for BF application with appropriate system consideration
- Cooling by free air convection
- EMI Class B for class I configuration
- Extremely low leakage current
- Protections: Short circuit / Overload / Over voltage
- 3 years warranty
Description
- RPD-60 is a 60W highly reliable green PCB-type medical power supply with a high power density on the 4″ by 2″ footprint. It accepts 90~264VAC input and offers dual output voltages.
- RPD-60 can be used for Class I (with FG) system design. The extremely low leakage current is less than 150MA. In addition, it conforms to international medical regulations (2*MOPP) and EMC BS EN/EN55011.
Applications
- Oral irrigator
- Hemodialysis machine
- Medical computer monitors
- Sleep apnea devices
GTIN CODE
- MW Search:https://www.meanwell.com/serviceGTIN.asp.
Model Encoding
SPECIFICATION
MODEL | RPD-60A | RPD-60B |
---|---|---|
OUTPUT | OUTPUT NUMBER | CH1 |
DC VOLTAGE | 5V | 12V |
RATED CURRENT | 5A | 2A |
CURRENT RANGE | 0.5 ~ 5.5A | 0.1 ~ 2.2A |
RATED POWER | 49W | 53.5W |
PEAK LOAD(10sec.) Note.2 | 53.9W | 58.85W |
RIPPLE & NOISE (max.) **Note.3** | 80mVp-p | 80mVp-p |
VOLTAGE TOLERANCE Note.4 | +3,-2% | ±6.0% |
LINE REGULATION | ±0.5% | ±1.0% |
LOAD REGULATION | ±1.5% | ±2.0% |
SETUP, RISE TIME | 300ms, 15ms/230VAC 300ms, 15ms/115VAC at |
full load
HOLD UP TIME (Typ.)| 70ms/230VAC 14ms/115VAC at full load
INPUT| VOLTAGE RANGE| 90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 78%| 82%
AC CURRENT (Typ.)| 1.1A/115VAC 0.7 A/230VAC
INRUSH CURRENT (Typ.)| COLD START 60A/230VAC 30A/115VAC
LEAKAGE CURRENT Note.5| Earth leakage current < 150μA/264VAC , Touch
current < 100μA/264VAC
PROTECTION| OVERLOAD| 115 ~ 150% rated output power
Protection type: Hiccup mode, recovers automatically after fault condition is
removed
OVERVOLTAGE| CH1: 5.75 ~ 6.75V
Protection type: Shut down o/p voltage, re-power on to recover
ENVIRONMENT| WORKING TEMP.| -20 ~ +65℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 45℃)
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along
the X, Y, and Z axes
OPERATING ALTITUDE Note.6| 3000 meters
SAFETY & EMC
(Note 9)
| SAFETY STANDARDS| IEC 60601-1:2005+A1, TUV BS EN/ EN 60601-1:2006+A1+A12+A2, ANSI/AAMI ES60601-1:2005+A2,
CAN/CSA C22.2 No. 60601-1:2014+A2, IEC 62368-1:2014, UL 62368-1, 2nd Ed, CSA C22.2 No. 62368-1-14, 2nd Ed, TUV BS EN/ EN 62368-1:2014+A11, EAC TP TC 004 approved
ISOLATION LEVEL| Primary-Secondary: 2xMOPP, Primary-Earth:1xMOPP,
Secondary-Earth:1xMOPP
WITHSTAND VOLTAGE| I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted emission| BS EN/EN55011 (CISPR11)| Class B
Radiated emission| BS EN/EN55011 (CISPR11)| Class B
Harmonic current| BS EN/EN61000-3-2| Class A
Voltage flicker| BS EN/EN61000-3-3| —–
EMC IMMUNITY| BS EN/EN55035,BS EN/EN60601-1-2
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 4, 15KV air ; Level 4, 8KV contact
RF field susceptibility| BS EN/EN61000-4-3| Level 3, 10V/m( 80MHz~2.7GHz )
Table 9, 9~28V/m( 385MHz~5.78GHz )
EFT bursts| BS EN/EN61000-4-4| Level 3, 2KV
Surge susceptibility| BS EN/EN61000-4-5| Level 4, 4KV/Line-FG ; 2KV/Line-Line
Conducted susceptibility| BS EN/EN61000-4-6| Level 3, 10V
Magnetic field immunity| BS EN/EN61000-4-8| Level 4, 30A/m
Voltage dip, interruption| BS EN/EN61000-4-11| 100% dip 1 period, 30% dip 25
periods, 100% interruptions 250 periods
OTHERS| MTBF| 5031.3K hrs min. Telcordia SR-332 (Bellcore);
679.5K hrs min. MIL-HDBK-217F (25℃)
DIMENSION (LWH)| 101.650.829mm or 4″ 2″ 1.14″ inch
PACKING| 0.15Kg; 96pcs/15.4Kg/0.89CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC
input, rated load, and 2 ℃ of ambient temperature.
2. 33% Duty cycle maximum within every 30 seconds. The average output power should not exceed the rated power.
3. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
4. Tolerance: includes set up tolerance, line regulation, and load regulation.
Touch current was measured from primary input to DC output.
6. The ambient temperature derating of 3. ℃/1000m with fanless models and of ℃/1000m with fan models for operating altitudes higher than 2000m 6 00ft.
7. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to an increase in the set-up time.
8. Heat Sink HS1,HS2 can not be shorted.
9. The power supply is considered a component that will be installed into the final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re- confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
※ Product Liability Disclaimer For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve
Output Derating VS Input Voltage
Mechanical Specification
AC Input Connector (CN1) : JST B3P-VH or equivalent
Pin No. | Assignment | Mating Housing | Terminal |
---|---|---|---|
1 | AC/N | JST VHR or equivalent | JST SVH-21T-P1.1 or equivalent |
2 | No Pin | ||
3 | AC/L |
DC Output Connector (CN2) : JST B6P-VH or equivalent
Pin No. | Assignment | Mating Housing | Terminal |
---|---|---|---|
1,2 | V1 | JST VHR or equivalent | JST SVH-21T-P1.1 or equivalent |
3,4 | COM | ||
5 | V2 | ||
6 | NC |
~~~~Grounding Required
- HS1, HS2 cannot be shorted.
- M1 is safety ground. For better EMC performance, Please secure an electrical connection between
- M1, M2, and chassis grounding.
- M1 M2
Installation Manual
- Please refer to:http://www.meanwell.com/manual.html.