HYTRONIK SAM24 Control HF Motion Sensor Owner’s Manual
- July 9, 2024
- HYTRONIK
Table of Contents
HYTRONIK SAM24 Control HF Motion Sensor
Applications
Occupancy detector with DALI-2 control suitable for indoor use:
- Office / Commercial Lighting
- Classroom
- Meeting Room
Use for new luminaire designs and installations
Features
Technical Specifications
Input Characteristics
Input| 220-240VAC 50/60Hz
Current Consumption| Max. 2mA from DALI Bus
Power Consumption| <1W
DALI Input voltage| 9.5~22.5V
Environment
Operation temperature| Ta: -20OC ~ +60OC
Case temperature (Max.)| Tc: +70OC
Storage temperature| -35°C ~ 70°C
Relative humidity| 20 ~ 90%
IP rating| IP20
Insulation| Class II
Safety and EMC
EMC standard (EMC)| EN55015, EN61547,
EN61000-3-2, EN61000-3-3
Safety standard (LVD)| EN61347-1/-2-11
Radio Equipment (RED)| EN300440, EN301489-1/-3, EN50663
| CE , RCM , UKCA
Compliance| IEC62386_101, 103, 303, 304
HF Sensor Propertie
Sensor principle| High Frequency (microwave)
Operation frequency| 5.8GHz +/- 75MHz
Transmission power| <0.5mW
Detection range| Installation height: 3m Max. Diameter(Ø):12m
Detection angle| 30O ~ 150O
Mechanical Structure & Dimensions
Model HCD038/D2
Wire Preparation
To make or release the wire from the terminal, use a screwdriver to push down the button.
- 200 metres (total) max. for 1mm² CSA (Ta = 50℃)
- 300 metres (total) max. for 1.5mm² CSA (Ta = 50℃)
HF SensorDIMTM Model SAM24
Wiring Diagram
Detection Range
Height (m)
| Sensitivity
---|---
100%| 75%| 50%| 10%
Diameter ( Ø :m )
8| 8| 6| 4| none
5| 10| 8| 6| 2
3| 12| 10| 8| 4
Sensitivity Adjustment
Setting the sensitivity can be achieved through the following command
combination:
- “ENABLE WRITE MEMORY”: Enable BANK write function.
- “DTR1:DRT0=0x1:0x2, WRITE MEMORY LOCATION =0x55”: Set the Lock byte of BANK1 to 0x55. Here a total of 2 instructions are used. 0x1(binary) = 1(decimal), 0x2(binary) = 2(decimal), 0x55 (binary) = 85(decimal).
- “DTR1:DRT0=0x1:0x11, WRITE MEMORY LOCATION = sensing gear value”: set the sensitivity of BANK1 to “sensing gear value”. 0x11(binary) = 17(decimal). Sensing gear value can be selected from 0x1 to 0x4, 0x1 is the weakest, 0x4 is the strongest.
Before writing to the bank, two locks need to be unlocked to write normally.
- The first lock is the big lock for all banks. Unlock it with the command “ENABLE WRITE MEMORY”.
- The second lock is that each bank has its own Lock byte. When the written value is 0x55, the small lock is unlocked.
BANK is a memory space freely defined by the manufacturer. Writing a value after unlocking has two steps:
- Specify the write address, and pass in the address through DTR0 and DTR1.
- Pass in the written value with the write command “WRITE MEMORY LOCATION”. This command will return the written value after the write is successful. Write fails without return value.
The following is an example of an instruction to set the sensitivity to 100%.
Type | Address | Command | Data | Delay | Answer |
---|---|---|---|---|---|
DALI24 | BCast | ENABLE WRITE MEMORY | 100… | ||
DALI24 | BCast | ENABLE WRITE MEMORY | 100… | ||
DALI24 | DTR1:DTRO | 1:2 | 100… | ||
DALI24 | WRITE MEMORY LOCATION | 85 | 100… | 85 | |
DALI24 | DTR1:DTRO | 1:17 | 100… | ||
DALI24 | WRITE MEMORY LOCATION | 4 | 100… | 4 |
Additional Information / Documents
- Regarding precautions for Photodiode/Photocell Usages, please kindly refer to www.hytronik.com/download->knowledge->Precautions for Photodiode/Photocell Usages
- The data sheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/Motion Sensors ->Built-in HF Sensor
- Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download->knowledge->Hytronik Standard Guarantee Policy
- Subject to change without notice.
- Edition: 18 Mar. 2024
- Ver. A0
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>