RenewAire GR90 Energy Recovery Ventilator Owner’s Manual
- July 7, 2024
- RenewAire
Table of Contents
RenewAire GR90 Energy Recovery Ventilator
Specifications
- Ventilation Type: Static plate, heat and humidity transfer
- Unit Weight: 36 lbs.
- Dimensions (Shipping): 29 L x 22 W x 15 H
- Filters: MERV 8, spun-polyester media (9 5/8 x 10 1/2 x 1)
- Motor(s): Qty. 2, Standard motorized impeller blowers
- Electrical Data: HP Volts 0.03 120, Watts 46 @ 90 CFM, FLA 0.35
Product Usage Instructions
Installation
The unit can be mounted in any orientation. Ensure proper power wiring inlet
and follow the dimension drawing for airflow orientation.
Orientation & Airflow
The unit can be installed in any orientation. The RA/EA airstream can be
switched with OA/SA airstream as needed for your setup.
Maintenance
Regularly clean or replace the filters to ensure optimal performance. Refer to
the user manual for detailed maintenance instructions.
FAQ
-
Q: Can the unit be installed outdoors?
A: No, the unit is designed for indoor ductwork installation only. -
Q: How often should the filters be replaced?
A: Filters should be checked monthly and replaced every 3-6 months depending on usage and air quality.
ENERGY RECOVERY VENTILATOR
INDOOR UNIT
Note: There are multiple control options designed to address individual climate conditions. Please consult your local installer for the best installation controls for your climate.
SPECIFICATIONS
-
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range: 40–110 CFM -
Unit is HVI Tested/Certified per CSA C439 Protocol:
Using one L-35-G5 Core -
Standard Features:
Unpainted galvanized cabinet
Field wiring to terminal block
Unit may be mounted in any orientation
Cross-core differential pressure ports -
Control :
Can use any switched line-voltage power supply (no low-voltage controls) -
Filters:
Total qty. 2, MERV 8, spun-polyester media:
9 5/8″ x 10 1/2″ x 1″ -
Unit Weight: 36 lbs.
Max. Shipping Dimensions & Weight (in carton):
29″ L x 22″ W x 15″ H 40 lbs.
Units Per Pallet: 10
Motor(s):
Qty. 2, Standard motorized impeller blowers
Accessories:
- Backdraft damper: 6″, 8″
- Automatic balancing damper: 4″, 5″, 6″
- Motorized Dampers: 6″, 8″
- Concentric Vent: 6″ (CV6-110)
- Louvered wall vent 6″: white, brown
- 120V line voltage Honeywell control
- MERV 13 filter: OA airstream (shipped loose)
- Electric duct heater: RH series (1–3 kW); designed for indoor ductwork installation only
ELECTRICAL DATA
HP | Volts | Hz | Phase | Watts | FLA |
---|---|---|---|---|---|
0.03 | 120 | 60 | Single | 46 @ 90 CFM | 0.35 |
UNIT PERFORMANCE
Airflow (CFM)| External Static Pressure (Inches Water
Column)
---|---
36| 0.60
53| 0.50
68| 0.40
81| 0.30
93| 0.20
108| 0.10
CORE PERFORMANCE
Airflow (CFM) | Temp EFF% | Total EFF% Winter/Summer |
---|---|---|
36 | 78 | 75/65 |
53 | 74 | 69/58 |
68 | 70 | 65/53 |
81 | 67 | 61/49 |
93 | 64 | 58/45 |
108 | 61 | 55/42 |
Note: These are core-only ratings and are not HVI certified. Total EFF% calculated at 35/33wb OA and 70/58wb RA (winter) and 98/78wb OA and 75/63wb RA (summer). HVI ratings apply to com-plete units only. This unit is HVI certified. See HVI certified ratings on pg. 47 of Single/Multi-Family Catalog and at hvi.org.
UNIT DIMENSIONS
AIRFLOW ORIENTATION
Available as shown in dimension drawing.
UNIT MOUNTING & APPLICATION
Can be mounted in any orientation. RA/EA airstream can be switched with OA/SA
airstream.
ABBREVIATIONS
-
EA: Exhaust Air to outside
OA: Outside Air intake -
RA: Room Air to be exhausted
-
SA: Supply Air to inside
INSTALLATION ORIENTATION
- Unit may be installed in any orientation.
NOTE
- UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
- SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.
Subject to change without notice: RENEWAIRE.COM | 1.800.627.4499 27