EMPIRE VFPA32BP30LP-1 Vent Free Gas Fireplaces Installation Guide

July 8, 2024
Empire

EMPIRE VFPA32BP30LP-1 Vent Free Gas Fireplaces

Product Information

Specifications

  • Model: EMPIRE VFPA32BP30LP-1
  • Type: Vent-Free Gas Fireplaces
  • Ignition Type: Millivolt or Intermittent Pilot
  • Supplied Components: Battery AA, Cover, Junction Box, Decorative Rock, Flex Line, Hood, Instruction Sheet, Soot Power Adaptor, Receptical, Registration Card, Rockwool, Screws, Trims

Product Usage Instructions

Installation Instructions

Installer: Leave the manual with the appliance. Consumer: Retain the manual for future reference.

Safety Information

  • Danger: Failure to follow instructions may result in death or serious injury.
  • Warning: Ensure proper ventilation and avoid altering burner flame patterns.
  • Caution: Keep burner openings clean to prevent sooting and property damage.

Operation Guidelines

  • Avoid blowing fans directly into the fireplace to maintain burner flame patterns.
  • Do not use unauthorized accessories with the heater.
  • Ensure adequate ventilation for proper operation.
  • Check all components for proper functioning before operation.
  • Consult the troubleshooting section for any issues related to fresh air intake.

FAQs

  • Q: Where can I find replacement parts for the EMPIRE VFPA32BP30LP-1?
    • A: Replacement components are available through your local dealer. Refer to the “How to Order Repair Parts” section of the appliance manual for more information.
  • Q: What should I do if I detect a gas odor while using the fireplace?
    • A: Immediately turn off the gas supply, ventilate the area, and contact a qualified technician to inspect the fireplace for any gas leaks or malfunctions.

This Owner’s Manual is provided and hosted by Appliance Factory Parts.
EMPIRE VFPA32BP30LP-1 Owner’s Manual
Shop genuine replacement parts for EMPIRE VFPA32BP30LP-1
Find Your EMPIRE Fireplace Parts – Select From 642 Models ——– Manual continues below ——–

INSTALLATION INSTRUCTIONS AND OWNER’S MANUAL

VENT-FREE GAS FIREPLACES
INSTALLER:
Leave this manual with the appliance.
CONSUMER:
Retain this manual for future reference.
WARNING If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. — Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance. — WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not touch any electrical switch;
do not use any phone in your building. · Leave the building immediately. · Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions. · If you cannot reach your gas supplier, call the fire department. — Installation and service must be performed by a qualified installer, service agency or the gas supplier.

UNVENTED GAS FIREPLACE MODELS:
MILLIVOLT
VFPA(32,36)BP3(0,1)L(N,P)-1
INTERMITTENT PILOT
VFPA(32,36)BP7(0,1)L(N,P)-1
WARNING If not installed, operated and maintained in accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or serious illness. This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to page 13. This appliance may be installed in an aftermarket, permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases. WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS Water vapor is a by-product of gas combustion. An unvented room heater produces approximately one (1) ounce (30ml) of water for every 1,000 BTU’s (.3KW’s) of gas input per hour. Refer to page 8.
Page 1

Page 2

39025-2-0620

CARTON CONTENTS
12 14

Product Registration
Card

Bag

Decorative Rock

INDEX NUMBER
1 2 3 4 5 6 7 8 9 10 11 12 13 14
39025-2-0620

DESCRIPTION
Battery AA Cover Junction Box
Decorative Rock Flex Line Hood
Instruction Sheet – Soot Power Adaptor Receptical
Registration Card Rockwool
Screw #8 X 1/2 Trim, Left Side Trim, Right Side Trim, Top Side

QUANTITY SUPPLIED

30 Series

70 Series

4

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

5

5

1

1

1

1

1

1

Page 3

IMPORTANT SAFETY INFORMATION

DANGER: Indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING: Indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION: Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE: Addresses practices not related to personal injury. · An unvented room heater having an input rating of more than
6,000 Btu per hour shall not be installed in a bathroom · An unvented room heater having an input rating of more than 10,000
Btu per hour shall not be installed in a bedroom or bathroom. · Due to high temperatures, the appliance should be located out of
traffic and away from furniture and draperies. · Children and adults should be alerted to the hazard of high surface
temperature and should stay away to avoid burns or clothing ignition. · Young children should be carefully supervised when they are in the same room with the appliance. · Do not place clothing or other flammable material on or near the appliance. · Avoid the use of scented air fresheners (plug in type air fresheners, etc. ) while the log set is in operation. Air fresheners produce a residue in the air similar to candles and may produce a soot like substance. · Avoid the use of scented or decorative candles while the log set is in operation. Candles produce a residue in the air that creates a soot like substance. Burning candles while the log set is operating magnifies the problem. It should be noted that candles, in general, produce soot. The amount of time burned and the quantity of candles burned will determine the amount of soot produced and deposited. · Installation and repair should be done by a QUALIFIED SERVICE PERSON. This appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean. · DO NOT use this room heater if any part has been under water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water. · You must operate heater with fireplace screen in place. · Do not place trash, logs or other articles on the log set during operation. · During manufacturing, fabricating and shipping, various components of this appliance are treated with certain oils, films or bonding agents. These bonding agents are not harmful but may produce annoying smoke and smells as they are burned off during initial operation of the appliance. This is a normal temporary occurrence. A window should be opened during the initial bake out period. · Correct installation of the ceramic fiber logs, proper location of the heater and annual cleaning are necessary to avoid potential problems with sooting. Sooting, resulting from improper installation or operation, can settle on surfaces outside the fireplace. See instructions for proper installation.

·

WARNING: Do not allow fans to blow directly into the

fireplace. Avoid any drafts that alter burner flame patterns.

·

WARNING: Do not use a blower insert, heat exchanger insert

or other accessory not approved for use with this heater.

·

WARNING! This fireplace needs fresh air for ventilation to

run properly. This fireplace has an ODS (oxygen depletion

sensor) which will shut down the heater if adequate fresh air is

not available. See troubleshooting section in the instructions.

·

WARNING: DO NOT operate this appliance unless all

components including logs, burners, and controls are in good

working condition. Never operate this appliance if any log or

twig is broken, or out of their intended position. Refer to the

Log set placement instructions for correct log and twig

positioning.

Replacement components are available through your local

dealer as indicated in the How to Order Repair Parts section of

the appliance manual.

· Keep appliance area clear and free from combustible materials,

gasoline and other flammable vapors and liquids.

·

WARNING: Failure to keep the primary air opening(s) of the

burner(s) clean may result in sooting and property damage.

WARNING
When used without adequate combustion and ventilation air, heater may give off CARBON MONOXIDE, an odorless, poisonous gas.
Do not install heater until all necessary provisions are made for combustion and ventilation air. Consult the written instructions provided with the heater for information concerning combustion and ventilation air. In the absence of instructions, refer to the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation, or applicable local codes.
This heater is equipped with a PILOT LIGHT SAFETY SYSTEM designed to turn off the heater if not enough fresh air is available.
DO NOT TAMPER WITH PILOT LIGHT SAFETY SYSTEM!
If heater shuts off, do not relight until you provide fresh air.
If heater keeps shutting off, have it serviced. Keep burner and control compartment clean.
CARBON MONOXIDE POISONING MAY LEAD TO DEATH.
Early signs of carbon monoxide poisoning resemble the flu, with headache, dizziness and/or nausea. If you have these signs, heater may not be working properly. Get fresh air at once! Have heater serviced.
Some people — pregnant women, persons with heart or lung disease, anemia, those under the influence of alcohol , those at high altitudes — are more affected by carbon monoxide than others.
The pilot light safety system senses the depletion of oxygen at its location. If this heater is installed in a structure having a high vertical dimension, the possibility exists that the oxygen supply at the higher levels will be less than that at the heater. In this type of application, a fan to circulate the structure air will minimize this effect. The use of this fan will also improve the comfort level in the structure. When a fan is used to circulate air, it should be located so that the air flow is not directed at the burner.

Page 4

39025-2-0620

SAFETY INFORMATION FOR USERS OF PROPANE GAS

Propane is a flammable gas which can cause fires and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precautions which can protect both you and your family from an accident. Read them carefully now, then review them point by point with the

members of your household. Someday when there may not be a minute to lose, everyone’s safety will depend on knowing exactly what to do. If, after reading the following information, you feel you still need more information, please contact your gas supplier.

PROPANE GAS WARNING ODOR

If a gas leak happens, you should be able to smell the gas because of the odorant put in the Propane Gas.

That’s your signal to go into immediate action!

· Do not operate electric switches, light matches, use your phone. Do not do anything that could ignite the gas.

service person and the fire department. Even though you may not continue to smell gas, do not turn on the gas again. Do

· Get everyone out of the building, vehicle, trailer, or area. Do that IMMEDIATELY.
· Close all gas tank or cylinder supply valves.

not re-enter the building, vehicle, trailer, or area. · Finally, let the service man and firefighters check for escaped
gas. Have them air out the area before you return. Properly

· Propane Gas is heavier than air and may settle in low areas

trained Propane Gas service people should repair the leak,

such as basements. When you have reason to suspect a gas

then check and relight the gas appliance for you.

leak, keep out of basements and other low areas. Stay out until firefighters declare them to be safe. · Use your neighbor’s phone and call a trained Propane Gas

NO ODOR DETECTED – ODOR FADE

Some people cannot smell well. Some people cannot smell the
odor of the chemical put into the gas. You must find out if you can smell the odorant in propane. Smoking can decrease your

The odorant in escaped gas can adsorb or absorb onto or into walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity.

ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.
The odorant in Propane Gas is colorless, and it can fade under some circumstances. For example, if there is an underground leak, the movement of the gas through soil can filter the odorant. Odorants in Propane Gas also are subject to oxidation. This fading can occur if there is rust inside the storage tank or in iron gas pipes.

Propane Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.

SOME POINTS TO REMEMBER

· Learn to recognize the odor of Propane Gas. Your local Propane Gas Dealer can give you a “Scratch and Sniff” pamphlet. Use it to find out what the propane odor smells like. If you suspect that your Propane Gas has a weak or abnormal odor, call your Propane Gas Dealer.

cause odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you have any question about the gas odor, call your Propane Gas Dealer. A periodic sniff test of the Propane Gas is a good safety measure under any condition.

· If you are not qualified, do not light pilot lights, perform service, or make adjustments to appliances on the Propane Gas system. If you are qualified, consciously think about the odor of Propane Gas prior to and while lighting pilot lights or performing service or making adjustments.
· Sometimes a basement or a closed-up house has a musty smell that can cover up the Propane Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of Propane Gas.
· Odor fade, due to oxidation by rust or adsorption on walls of new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or reinstalled old tanks, if they are filled and allowed to set too long before refilling. Cylinders and tanks which have been out of service for a time may develop internal rust which will

· If, at any time, you do not smell the Propane Gas odorant and you think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorized Propane Gas.
· If you experience a complete “gas out,” (the container is under no vapor pressure), turn the tank valve off immediately. If the container valve is left on, the container may draw in some air through openings such as pilot light orifices. If this occurs, some new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container before it goes completely empty or having it refilled before it is completely empty.

39025-2-0620

Page 5

INTRODUCTION

Instructions to Installer 1. Installer must leave instruction manual with owner after
installation. 2. Installer must have owner fill out and mail warranty card
supplied with unvented room heater. 3. Installer should show owner how to start and operate
unvented room heater.
Always consult your local Building Department regarding regulations, codes or ordinances which apply to the installation of an unvented room heater.
This appliance may be installed in an aftermarket manufactured (mobile) home, where not prohibited by state or local codes.
Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
WARNING
ANY CHANGE TO THIS HEATER OR ITS CONTROLS CAN BE DANGEROUS. Improper installation or use of the heater can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
This series is design certified in accordance with American National Standard Z21.11.2 by the Canadian Standards Association Laboratories as an Unvented Room Heater and should be installed according to these instructions.
Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change.
VFPA(32,36)BP(30,31)L Only 750 Millivolt System When you ignite the pilot, the thermocouple produces millivolts (electrical current) which energizes the magnet in the gas valve. After 30 seconds to 1 minute time period you can release the gas control knob and the pilot will stay ON. Allow your pilot flame to operate an additional one (1) to two (2) minutes before you turn the gas control knob from the PILOT position to the ON position. This time period allows the millivolts (electrical energy) to build-up to a sufficient level allowing the gas control to operate properly.
Important All correspondence should refer to complete Model Number, Serial Number and type of gas.
Attention: During initial use of ceramic log you will detect an odor as the ceramic log is cured. Also, during the curing process the ceramic log will burn with a yellow flame.
NOTICE: During initial firing of this unit, its paint will bake out, and smoke will occur. To prevent triggering of smoke alarms, ventilate the room in which the unit is installed.

Installation on Rugs and Tile If this appliance is installed directly on carpeting, tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
The base referred to above does not mean the fire-proof base as used on wood stoves. The protection is for rugs that are extremely thick and light colored tile.
Solid-fuels shall not be burned in a masonry or UL 127 factory-built fireplace in which an unvented room heater is installed.
Qualified Installing Agency Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency. The term “qualified agency” means any individual, firm, corporation or company which either in person or through a representative is engaged in and is responsible for (a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction.
Commonwealth of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts. Sellers of unvented Propane or Natural Gas-fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit. In the Commonwealth of Massachusetts, unvented Propane and Natural Gas-fired space heaters shall be prohibited in bedrooms and bathrooms.
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1.
Available from the American National Standards Institute, Inc. 1430 Broadway, New York, N.Y. 10018.
High Altitudes For altitudes/elevations above 2,000 feet (610m), ratings should be reduced at the rate of 4 percent for each 1,000 feet (305m) above sea level. Contact the manufacturer or your gas company before changing spud/orifice size.
Well Head Gas Installations Some natural gas utilities use “well head” gas. This may affect the Btu output of the unit. Contact the gas company for the heating value. Contact the manufacturer or your gas company before changing spud/orifice size.
WARNING
This appliance is equipped for (Natural Gas or Propane) Gas. Field conversion is not permitted.

Page 6

39025-2-0620

SPECIFICATIONS

MODEL Input BTU/Hr Maximum Input BTU/Hr Minimum
KWH (Maximum) KWH (Minimum)
Height Width Depth Gas Inlet
EK-1 PE-20 FBB5* Brick Liners FRBC FRBTC FREC FWS TMV TRW

VFPA32BP

VFPA36BP

32,000

36,000

22,000

25,000

9.38

10.55

6.45

7.33

MINIMUM FIREBOX OPENING

33″

35″

35″

40″

16-1/2″

19″

1/2″

1/2″

ACCESSORIES

Embers Kit

Platinum Embers

Variable Speed Automatic Blower

Contact Dealer For All Available Options

Battery Operated Remote Control

Battery Operated Remote Control w/Thermostat

Electric Remote Control

Wall Switch

Wall Thermostat, Millivolt – Reed Switch

Remote Wall Thermostat

NOTE: Air shutter is at factory-minimum settings. Some vent configurations may require minor air shutter adjustments for optimum performance.

Gas Type
Natural Propane

GAS SUPPLY PRESSURES (inches water column)

Maximum

Minimum

14

4.5

14

10.8

Manifold
3.5 10

*FBB5 is standard (installed) on VFPA(32,36)BP(31,71) Refractory “-2” logsets can only be used on VFPA(32,36)BP(31,71) units.

39025-2-0620

Page 7

WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS

Water vapor is a by-product of gas combustion. An unvented room heater produces approximately one (1) ounce (30ml) of water for every 1,000 BTU’s (.3KW’s) of gas input per hour.
Unvented room heaters are recommended as supplemental heat (a room) rather than a primary heat source (an entire house). In most supplemental heat applications, the water vapor does not create a problem. In most applications, the water vapor enhances the low humidity atmosphere experienced during cold weather.

The following steps will help insure that water vapor does not become a problem. 1. Be sure the heater is sized properly for the application, including
ample combustion air and circulation air. 2. If high humidity is experienced, a dehumidifier may be used to
help lower the water vapor content of the air. 3. Do not use an unvented room heater as the primary heat
source.

PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR

This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.
A confined space is an area with volume less than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances drawing combustion air from that space. Small areas such as equipment rooms are confined spaces. Furnaces installed in a confined space which supply heated air to areas outside the space must draw return air from outside the space through tightly sealed return air ducts. A confined space must have 2 openings into the space for combustion air. One opening must be within 12 inches of the ceiling and the other must be within 12 inches of the floor. The required sizing of these openings is determined by whether inside or outside air is used to support combustion, the method by which the air is brought to the space (vertical or horizontal duct) and by the total input rate of all appliances in the space.
Unusually Tight Construction The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where: a. Walls and ceilings exposed to the outside atmosphere have
a continuous water vapor retarder with a rating of one perm or less with openings gasketed or sealed, and b. Weather-stripping has been added on openable windows and doors, and c. Caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings. If your home meets all of the three criteria above, you must provide additional fresh air. See “Ventilation Air From Outdoors,” page 9.
Determining if You Have a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height =

cu. ft. (volume of

space)

Example: Space size 16 ft. (length) x 10 ft. (width) x 8 ft. (ceiling

height) = 1,280 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space. 2. Divide the space volume by 50 cubic feet to determine the maximum BTU/Hr the space can support.

(volume of space) ÷ 50 cu. ft. = (maximum BTU/Hr the space can support)

Example: 1,280 cu. ft. (volume of space) ÷ 50 cu. ft. = 25.6 or 25,600 (maximum BTU/Hr the space can support)
3. Add the BTU/Hr of all fuel burning appliances in the space.

Vent-free heater

Gas water heater

Gas furnace

Vented gas heater

Gas fireplace logs

Other gas appliances* +

Total

=

BTU/Hr BTU/Hr BTU/Hr BTU/Hr BTU/Hr BTU/Hr BTU/Hr

Example: Vented gas heater

Vent-free heater

Total

=

20,000 + 18,000
38,000

BTU/Hr BTU/Hr BTU/Hr

*Do not include direct-vent gas appliances. Direct vent draws combustion air from the outdoors and vents to the outdoors. 4. Compare the maximum BTU/Hr the space can support with the actual amount of BTU/Hr used.

BTU/Hr (maximum the space can support) BTU/Hr (actual amount of BTU/Hr used)

Example: 25,600 38,000

BTU/Hr (maximum the space can support) BTU/Hr (actual amount of BTU/Hr used)

WARNING
If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation, or applicable local codes.

Page 8

39025-2-0620

PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR

The space in the above example is a confined space because the actual BTU/Hr used is more than the maximum BTU/HR the space can support. You must provide additional fresh air. Your options are as follows: A. Rework worksheet, adding the space of an adjoining room. If
the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building. B. Vent room directly to the outdoors. See Ventilation Air From Outdoors. C. Install a lower BTU/Hr heater, if lower BTU/Hr size makes room unconfined.
If the actual BTU/Hr used is less than the maximum BTU/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
WARNING
You must provide additional ventilation air in a confined space.
VENTILATION AIR Ventilation Air From Inside Building (Figure 1) This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12″ of the ceiling and one within 12″ of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 1). You can also remove door into adjoining room (see option 3, Figure 1). Each ventilation grill or opening shall have a minimum free area of one square inch per 1,000 BTUH of the total input rating of the gas equipment in the confined space.

12″ (305mm)

OPTION 1: VENTILATION GRILLS INTO ADJOINING ROOM

Ventilation Air From Outdoors (Figure 2) Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12″ of the ceiling and one with 12″ of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. In most cases for direct communication with the outdoors or direct communication through a vertical duct a free area opening of one square inch per 4,000 BTU/Hr of heater input rating for each grill. If a horizontal duct is used, a grill free area or duct opening shall have a free area opening of one square inch per 2,000 BTU/Hr for each grill. Follow the National Fuel Code ANSI Z223.1/NFPA54, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

OUTLET AIR
OUTLET AIR

VENTILATED ATTIC

INLET AIR

VENTILATED CRAWL SPACE

Figure 2

TO ATTIC
TO CRAWL SPACE
INLET AIR

12″ (305mm)

OPTION 2: VENTILATION GRILLS INTO ADJOINING ROOM OPTION 3: REMOVE DOOR INTO ADJOINING ROOM
Figure 1
WARNING Rework worksheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.
39025-2-0620

Page 9

GAS SUPPLY

Check all local codes for requirements, especially for the size and type of gas supply line required.

RECOMMENDED GAS PIPE DIAMETER

Pipe Length

Schedule 40 Pipe Inside Diameter
Natural Propane

Tubing, Type L Outside Diameter
Natural Propane

0-10 feet 0-3 meters

1/2″

3/8″

1/2″

3/8″

12.7mm 9.5mm 12.7mm 9.5mm

10-40 feet 4-12 meters

1/2″

1/2″

5/8″

1/2″

12.7mm 12.7mm 15.9mm 12.7mm

40-100 feet 13-30 meters

1/2″

1/2″

12.7mm 12.7mm

3/4″ 19mm

1/2″ 12.7mm

100-150 feet 31-46 meters

3/4″ 19mm

1/2″

7/8″

12.7mm 22.2mm

3/4″ 19mm

NOTE: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.

NOTE: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.

Installing a New Main Gas Shut-Off Each appliance should have its own manual gas shut-off.
A manual main gas shut-off should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.

The use of the following gas connectors is recommended: — ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings — ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction The above connectors may be used if acceptable by the authority having jurisdiction The Commonwealth of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.
Figure 3

Page 10

39025-2-0620

GAS SUPPLY (CONT’D)

Checking Manifold Pressure
VFPA(32,36)BP(30,31)LN (Natural Gas) will have a manifold pressure of approximately 3.5″ w.c. (.871kPa) for maximum input or 1.7″ w.c. (.423kPa) for minimum input at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 4.5″ w.c. (1.120kPa) for the purpose of input adjustment to a maximum of 10.5″ w.c. (2.614kPa).
VFPA(32,36)BP(70,71)LN (Natural Gas) will have a manifold pressure of approximately 3.5″ w.c. (.871kPa) for maximum input or 1.7″ w.c. (.423kPa) for minimum input at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 4.5″ w.c. (1.120kPa) for the purpose of input adjustment to a maximum of 10.5″ w.c. (2.614kPa).
VFPA(32,36)BP(30,31) (Propane Gas) will have a manifold pressure approximately 10.0″w.c. (2.49kPa) for maximum input or 4.9″w.c. (1.220kPa) for minimum input at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 11.0″w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0″w.c. (3.237kPa).

VFPA(32,36)BP(70,71) (Propane Gas) will have a manifold pressure approximately 10.0″w.c. (2.49kPa) for maximum input or 4.9″w.c. (1.220kPa) for minimum input at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 11.0″w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0″w.c. (3.237kPa).
VFPA(32,36)BP(3,7)(0,1) Control The valve regulator controls the burner pressure which should be checked at the pressure test point. Turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point (Use test point “A” closest to control knob). After taking pressure reading, be sure and turn captured screw clockwise firmly to re-seal. Do not over torque. Check for gas leaks.

CLEARANCES

Minimum Wall and Ceiling Clearances Sidewall Clearances: The clearance from the inside of the fireplace to any combustible wall should not be less than 2″. Fireplace Side and Back Clearances: The fireplace outer casing sides and back have zero clearance to combustibles. Ceiling Clearances: The ceiling height should not be less than 36″ from the top of the hood. Mantel Clearances: Vent free fireplace models must use the hood supplied with the fireplace. If a combustible mantel is installed, it must meet the clearance requirements detailed above.
36″

Mantel Clearances

CEILING

FINISHED WALL
12″ MAX
10″

MANTEL

21″
42″ MIN CEILING TO
TOP OF HOOD

10″

8″

COMBUSTIBLES ALLOWED

18 ½”

6 ½”

16 ½” 5″

13″

14 ½”

3 ½”

84″ MIN. (CEILING TO FLOOR)

12 ½” 10 ½”

2″ 3/4″

9″

8″ MIN.

WALL FRAMING
OPEN GAP

Top of Hood
2″
Figure 4

3/4″ COMBUSTIBLE CLEARANCE REQUIRED
FROM TOP EDGE OF FIREBOX

HOOD

FIREBOX FACE
Figure 5

39025-2-0620

Page 11

COMBUSTIBLE MATERIALS

Do not attach combustible material to the mantel of your fireplace This is a fire hazard.

No greeting cards, stockings or ornamentation of any type should be
placed on or attached to the fireplace. This is a heating appliance. The flow of heat can ignite combustibles.

Figure 6

Figure 7

Page 12

39025-2-0620

FIREPLACE DIMENSIONS

OUTER FIREPLACE DIMENSIONS

J N
K

GA I
H F B

J N
K
C

D O L

A B C D F G H I J K L M N O
39025-2-0620

M
OUTER FIREPLACE DIMENSIONS (IN INCHES) VFPA32
33 35 16-1/2 27-7/8 31 22-1/4 1-3/16 31-1/2 8-5/16 4-3/4 30-1/4 60-3/8 2-11/16 42-5/8
Figure 8

VFPA36 35 40 19
31-7/8 36
24-1/4 1-3/16 33-1/2 8-5/16 4-3/4 34-5/8 69-1/8 2-11/16 48-7/8

.5 inches Page 13

PLANNING INSTALLATION

In planning the installation for the fireplace, it is necessary to determine where the unit is to be installed and whether optional accessories are desired. Gas supply piping should also be planned at this time.
The fireplace can be mounted on any of these surfaces: 1. A flat hard combustible or non-combustible surface. 2. A raised platform of combustible or non-combustible material. 3. Four (4) corners of the fireplace so contact is made on all four
perimeter edges on the bottom of the unit. (Example: Four (4) concrete masonry blocks.)

If the fireplace is installed directly on carpeting, tile or other combustible material other than wood flooring, it should be installed on a metal or wood panel extending the full width and depth of the unit.
At this point, you should have decided what components to include in your installation, and where the fireplace is to be located. If this has not been done, stop and consult your dealer for assistance with this planning.

FIREPLACE FRAMING AND INSTALLATION

Fireplace framing can be built before or after the fireplace is set in place. Framing should be positioned to accommodate wall covering and fireplace facing material. The fireplace framing should be constructed of 2 x 4 lumber or heavier.
BEND OUT TABS PRIOR TO INSTALLING UNIT TO FRAMED
OPENING

2 X 4 HEADER

COMBUSTIBLE FINISHED WALL OR MANTEL
FINISHED WITH TRIM KIT OR NON-COMBUSTIBLE MATERIAL

3/4″ GAP REQUIRED

Figure 10
1. Place fireplace in framing opening. 2. Using the four (4) nailing flanges provided with the fireplace,
attach two (2) flanges on each side. Attach flanges through prepunched holes. Additional hole locations will be used for different finishing material with thicknesses of 1/2″, 5/8″ and 3/4″. Attach these flanges with screws provided, two (2) per nailing flange. 3. Nailing flanges should fit directly against framing material. Use at least one (1) nail per tab to secure in place.

Figure 9

Page 14

39025-2-0620

FIREPLACE FRAMING AND INSTALLATION (CONT’D)

DELUXE VENT-FREE FIREBOX FRAMING DIMENSIONS (In Inches)

Model

A
Framing Height

B
Framing Width

C
Framing Depth

VFPA32BP

33 3/4

35 1/2

16 1/4

VFPA36BP

35 3/4

40 1/2

18 3/4

Attention: Add 3-3/4 inches to “A” Dimension when using flush mantel base.
Figure 11

INSTALLING HOOD AND TRIM KIT

A black hood and trim kit is furnished with each model VFPA(32,36)BP fireplace. The hood MUST be installed before the fireplace is used. Failure to do so may create a possible fire hazard. Attention: The hood is located behind top louver during shipment of fireplace. Remove top louver for access to hood.
The trim kit is used to finish the fireplace. The trim kit is used in place of brick, marble or other finishing material.
1. To remove louvers, lift louver and pull forward. 2. Loosen (4) shoulder screws. 3. Insert trim side left and trim side right into the fireplace. Tighten
(4) shoulder screws. 4. Insert flange on fireplace hood on the top of the firebox in the
gap between the louver and firebox top. 5. Attach fireplace hood to fireplace with (5) screws. See Figure 12. 6. Slide top trim flange behind the flat portion of side trim. Be
sure the flat portion of the top trim is in front of flat portion of side trim. See Figure A. 7. Rear lip of top trim will nest behind the back portion of the side trim to keep trim flush to finished material. See Figure B. 8. Replace louvers.

Figure A

Figure B

Finishing All joints (top, bottom and sides), where the wall or decorative facing material meets the fireplace surround must be completely sealed with a non-combustible material.

Hearth extensions are recommended, not a requirement for these gas fireplaces.

Do not cover the louvers at any time with finishing materials. This could cause this product to overheat and cause a fire.

39025-2-0620

Figure 12

Page 15

PLACEMENT OF GLOWING EMBERS AND LAVA ROCK

Refer to the Log Installation Instructions for Ember placement.
Placement of the glowing embers (rock wool) is very individual and light coverage of the areas indicated will provide your best effects. We recommend separation of the rock wool by hand and make your coverage as light and fluffy as possible.
Place just enough embers on the burner to obtain the glow and a gold yellow flame.
Do not place embers (rock wool) over large ports in rear portion of burner.
A thin layer of glowing embers (rock wool) should be placed under open space between the right and left middle logs.
Rock wool should not be placed in the area of the pilot assembly.
Replacement of loose material (glowing embers) must be purchased from Empire Comfort Systems, Inc. Application of excess loose material (glowing embers) may adversely affect performance of the heater. WARNING: All previously applied loose material must be removed prior to reapplication.
Refer to Log Instruction Manual to order loose material (rock wool).

Placing Lava Rock in Front of Burner on Fireplace Floor
Spread lava rocks on fireplace floor in front of the burner pan. The lava rocks are for decorative effect and are not required for fireplace operation.
ATTENTION: DO NOT PLACE LAVA ROCKS ON BURNER, LOGS OR ROCK WOOL. THE LAVA ROCKS SHOULD ONLY BE PLACED ON THE FIREPLACE FLOOR.

Page 16

39025-2-0620

VFPA(32,36)BP(30,31) LIGHTING INSTRUCTIONS

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not touch any electrical switch;
Do not use any phone in your building. · Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.

· If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it; call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING INSTRUCTIONS

1. STOP! Read the safety information label.

behind the burner on the right side.

2. Open bottom louver assembly.

8. Turn gas control knob counterclockwise

to

3. Set REMOTE/OFF/ON switch

“PILOT.”

to “OFF.”

9. Push in control knob all the way and hold in. Repeat-

4. Turn off all electric power to the

edly push the Piezo Ignitor Button until the pilot is lit.

appliance (if applicable).

Continue to hold the control knob in for about one (1)

5. Push in gas control knob slightly

GAS CONTROL KNOB

minute after the pilot is lit. Release knob, and it will

and turn clockwise

to

SHOWN IN “OFF” POSITION.

pop back up. Pilot should remain lit. If it goes out,

“OFF.” NOTE: Knob cannot

REMOTE

repeat steps 5 through 9.

be turned from “PILOT” to “OFF” unless

OFF

· If knob does not pop up when released, STOP and

knob is pushed in slightly. Do not force.

ON

IMMEDIATELY call a qualified service technician

6. Wait ten (10) minutes to clear out any

or gas supplier.

gas. Then smell for gas, in-

PILOT THERMOPILE

· If the pilot will not stay lit after several tries, turn

cluding near the floor. If you

ELECTRODE

the gas control knob to “OFF” and call your ser-

smell gas, STOP! Follow

vice technician or gas supplier.

“B” in the safety information

10. Turn gas control knob counterclockwise

to

above. If you do not smell gas,

“ON.”

go to the next step.

THERMOCOUPLE

11. Set REMOTE/OFF/ON switch to desired setting.

7. Find pilot – Follow metal tube (LPG) from gas control. The pilot is

THERMOCOUPLE (NATURAL)

12. Turn on all electric power to the appliance (if applicable).

13. Close bottom louver assembly.

TO TURN OFF GAS TO APPLIANCE

1. Open bottom louver assembly. 2. Set REMOTE/OFF/ON switch to “OFF.” 3. Turn off all electric power to the appliance if service is
to be performed (if applicable).

4. Push in gas control knob slightly and turn clockwise to “OFF.” Do not force.
5. Close bottom louver assembly.

39025-2-0620

Page 17

VFPA(32,36)BP(70,71) LIGHTING INSTRUCTIONS

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A. This appliance has a pilot which can be lighted with the manual on/off switch, a remote control, or by switching the remote receiver switch to the “ON” position. When lighting the pilot, follow these instructions exactly.
B. Before lighting smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
What To Do If You Smell Gas · Do not try to light any appliance. · Do not touch any electrical switch; · Do not use any phone in your building. · Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.

· If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it; call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING INSTRUCTIONS

1. STOP! Read the safety information above.

2. Turn OFF electric power to the appliance.

3. Remove front surround panel assembly or bottom louver if

included.

4. Turn gas shut-off counterclockwise

to “On” position.

5. Wait ten (10) minutes to clear out any gas. Then smell for gas,

including near the floor. If you smell gas, STOP! Follow “B” in

the safety information above on this page. If you do not smell

gas, go to the next step.

6. Turn ON electric power to the appliance.

7. Find pilot – Follow metal tube from gas control. The pilot is

behind the burner on the right side.

8. Turn main flame to on. If the pilot does not light within 60

seconds, stop and go to Step 5.

PILOT

ELECTRODE

FLAME SENSOR

9. Refer to remote control instructions for detailed information,

control features, and operation. NOTE: There is a CPI/IPI

switch behind the right side panel that allows for a continuous

standing pilot mode or an intermittent pilot mode. See appliance

manual for location of this switch. If the pilot or burner does

not stay lit (in the standing pilot mode), stop and immediately

call a qualified service technician or gas supplier.

10. If the burner or pilot does not operate properly after several

tries, turn the gas shut-off clockwise

to “OFF” and

call your service technician or gas supplier.

11. Replace the front surround assembly or close bottom louver

assembly.

12. Operation of the gas valve is controlled by a manual on/

off switch or a hand held remote control. Refer to remote

instructions for detailed operation information.

GAS SHUT-OFF VALVE

OFF

ON

TO TURN OFF GAS TO FIREPLACE

1. Set REMOTE/OFF/ON switch to OFF. 2. Turn off all electric power to the appliance if service is to be
performed (if applicable). 3. Lower bottom louver assembly.

4. Push in gas control knob slightly and turn clockwise to “OFF.” Do not force.
5. Close bottom louver assembly.

Page 18

39025-2-0620

OPERATION INSTRUCTIONS

/FLAME APPEARANCE

Flames from the pilot (rear right back side of the pan burner) as well as the main flame should be visually checked as the log set is installed.
In normal operation at full rate after 10 to 15 minutes, the flame appearance should be sets of yellow flames.
NOTE: All flames will be random by design, flame height will go up and down.
Glowing embers (rock wool) can cover the pan burner in between the front and middle logs, but very little is necessary to cover this area. Excess ember material causes the yellow flame to become orange and stringy. Apply just enough to obtain slow glow and a gold yellow flame.
Avoid any drafts that alter burner flame patterns. Do not allow fans to blow directly into fireplace. Do not place a blower inside the burner area of the firebox. Ceiling fans may create drafts that alter flame patterns. Sooting and improper burning will result.
During manufacturing, fabricating and shipping, various components of this appliance are treated with certain oils, films or bonding agents. These chemicals are not harmful, but may produce annoying smoke and smells as they are burned off during the initial operation of the appliance, possibly causing headaches or eye or lung irritation. This is a normal and temporary occurrence.
The initial break-in operation should last 2-3 hours with the burner at the highest setting. Provide maximum ventilation by opening windows or doors to allow odors to dissipate. Any odors remaining after this initial break-in will be slight and will disappear with continued use.
Once the break in operation has been completed, adjust the heater to the desired output and then replace the upper and lower louvers.

PERIODIC CLEANING ­ Refer to parts diagram for location of items discussed below. · Do not use cleaning fluid to clean logs or any part of heater. · Logs – brush with soft bristle brush or vacuum with brush
attachment. · Remove loose particles and dust from the burner areas,
controls, piezo covers and grate. Don’t remove ceramic media from inside burner box. · Inspect and clean burner air intake hole. Remove lint or particles with brush. Failure to keep air intake hole clean will result in sooting and poor combustion.
ANNUAL CLEANING/INSPECTION ­ Refer to parts diagram for location of items discussed below. · Inspect and clean burner air intake hole. Remove lint or particles
with vacuum or brush. Failure to keep air intake hole clean will result in sooting and poor combustion. · Inspect and clean all burner ports. · Inspect ODS pilot for operation and accumulation of lint at air intake holes. · Verify flame pattern and log placement for proper operation. · Verify smooth and responsive ignition of main burner. · Check level of ceramic media in burner. Burner should be full, up to the level of openings in burner top.

39025-2-0620

Page 19

PILOT FLAME CHARACTERISTICS

Figures 13 and 15 show a correct pilot flame pattern. The correct flame will be blue and will extend beyond the thermocouple. The flame will surround the thermocouple just below the tip. A slight yellow flame may occur where the pilot flame and main burner flame meet. Figures 14 and 18 show an incorrect pilot flame pattern. The incorrect pilot flame is not touching the thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the
heater will shut down.

MILLIVOLT PILOT

Correct Pilot Flame Pattern

THERMOPILE

PILOT

INTERMITTENT PILOT Correct Pilot Flame Pattern
IGNITOR
SENSOR

PILOT

THERMOCOUPLE (LPG)
Figure 13

THERMOCOUPLE (NATURAL)

Incorrect Pilot Flame Pattern

THERMOPILE

PILOT

Figure 15 Incorrect Pilot Flame Pattern
IGNITOR
SENSOR

THERMOCOUPLE (LPG)

THERMOCOUPLE (NATURAL)

Figure 14
If pilot flame pattern is incorrect, as shown in Figure 14. · See Troubleshooting, page 25.

PILOT
Figure 16 If pilot flame pattern is incorrect, as shown in Figure 16: · See Troubleshooting, page 25-27.

Page 20

39025-2-0620

PILOT FLAME CHARACTERISTICS
Cleaning and Pilot Maintenance Oxygen Depletion Sensor Pilot When the pilot has a large yellow tip flame, clean the Oxygen Depletion Sensor as follows:
1. Clean the ODS pilot by loosening nut B from the pilot tubing. When this procedure is required, grasp nut A with an open end wrench.
2. Blow air pressure through the holes indicated by the arrows. This will blow out foreign materials such as dust, lint and spider webs. Tighten nut B also by grasping nut A.

B

A

VFPA(32,36)BP(30,31) Millivolt Pilot Figure 17

BA
VFPA(32,36)BP(20,21) Hydraulic Thermostat Pilot Figure 18
WARNING Never use needles, wires, or similar cylindrical objects to clean the pilot to avoid damaging the calibrated ruby that controls the gas flow.

39025-2-0620

Page 21

MILLIVOLT WIRING

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Millivolt thermopile is self powered, gas valve does not require 110 volts. Maximum length of 20 feet of 16 AWG to conductor wires is to be used with all optional switches. Use the two leads (Red and Green) to attach optional components. Check 750 Millivolt System Operation Millivolt system and all individual components may be checked with a millivolt meter 0-1000 MV range.
WIRING DIAGRAM

Remote Receiver Use the following steps to place the remote receiver adjacent to the gas valve. Attention: The remote receiver bracket is not used in this installation. 1. The remote receiver can not be placed behind the gas valve
and burner assembly. 2. When facing the appliance, the remote receiver must be placed
to the right of the gas valve.
Install remote control receiver behind bottom louver.
Refer to remote control installation and operating instructions for more details on remote control.

REMOTE CONTROL RECEIVER/ THERMOSTAT/CONTROLE E DISTANCE DU RECEPTEUR

H

N

(OPTIONAL) THERMOSTAT (FACULATIVE) THERMOSTAT

(OPTIONAL) WALL SWITCH INTERRUPTEUR MURAL (FACULTATIVE)

REMOTE/OFF/ON SWITCH A DISTANCE/OUVERT/ FERME INTERRUPTEUR

GAS VALVE VALVE DE GAZ

(OPTIONAL) REMOTE CONTROL RECEIVER (FACULTATIVE) CONTROLE E DISTANCE DU RECEPTEUR

THERMOPILE PILOT VEILLEUSE
THERMOCOUPLE (LPG) THERMOCOUPLE (NATURAL)

REMOTE/OFF/ON SWITCH A DISTANCE/FERME/OUVERT INTERRUPTEUR

REMOTE OFF ON
GAS VALVE

IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH NUMBER 18, 150oC WIRE OR ITS EQUIVALENT.
SI UN DES FILS ELECTRIQUES ORIGINAUX, VENANT DU FABRICANT AVEC CETTE UNITE, DOIT ETRE REMPLACE, VOUS DEVEZ LE REMPLACER AVEC UN FIL ELECTRIQUE DE NUMERO 18, 150oC DU L’EQUIVALENT.

Figure 19

MILLIVOLT MAINTENANCE

Keep the control compartment, logs and burner area surrounding the logs clean by vacuuming or brushing area at least twice a year.
THE LOGS CAN GET VERY HOT ­ HANDLE ONLY WHEN COOL.
Always turn off gas to the pilot before cleaning. For relighting, refer to lighting instructions located on the rating plate of the log set.

Never obstruct the flow of the combustion and ventilation air. Keep the front of the fireplace clear of all obstacles and materials.
Leave at least 36″ clearance from the front of the fireplace.
Screen should be closed during operation.

Page 22

39025-2-0620

MILLIVOLT TROUBLESHOOTING
SYMPTOMS – POSSIBLE CAUSES AND CORRECTIONS

Turn appliance OFF and allow to cool before servicing. Only a qualified service person should service and repair the heater.

1. When ignitor button is pressed, there is no spark at ODS/pilot. a. Ignitor electrode positioned wrong – Replace pilot. b. Ignitor electrode is broken – Replace pilot. c. Ignitor electrode not connected to ignitor cable Reconnect ignitor cable. d. Ignitor cable pinched or wet. Keep ignitor cable dry Free ignitor cable if pinched by any metal or tubing. e. Broken ignitor cable – Replace ignitor cable. f. Bad piezo ignitor – Replace piezo ignitor.
2. Appliance produces unwanted odors. a. Appliance burning vapors from paint, hair spray, glues, etc. – Ventilate room. Stop using odor causing products while heater is running. b. Gas leak – Locate and correct all leaks.
3. Appliance shuts off during use. (Pilot and main burner are off.) a. Not enough fresh air is available for ODS/pilot to operate – Open window and/or door for ventilation. b. Low line pressure – Contact local gas company. c. ODS/pilot is partially clogged – Clean ODS/pilot. d. Defective thermocouple – Replace pilot.
4. Appliance shuts off during use. (Pilot stays on.) a. Low line pressure – Check line pressure to the valve. b. Defective thermopile – Check pilot flame, check wire connections, output should be a minimum of 325 millivolts across. TH/TP and TP terminals with ON/ OFF switch off.
5. Gas odor even when control knob is in OFF position. a. Gas leak – Locate and correct all leaks. b. Control valve defective – Replace control valve.
6. When ignitor button is pressed, there is spark at ODS/pilot, but no ignition. a. Gas supply turned off or manual shutoff valve closed – Turn on gas supply or open manual shutoff valve. b. Control knob not in PILOT position – Turn control knob to PILOT position. c. Control knob not pressed in while in PILOT position – Press in control knob while in PILOT position. d. Air in gas lines when installed – Continue holding down control knob. Repeat igniting operation until air is removed. e. ODS/pilot is clogged – Replace ODS/pilot assembly or get it serviced. f. Gas regulator setting is not correct – Replace gas regulator.
7. ODS/pilot lights but flame goes out when control knob is released.

a. Control knob not fully pressed in – Press in control knob fully.
b. Control knob not pressed in long enough – After ODS/pilot lights, keep control knob pressed in 30 seconds.
c. Manual Shutoff valve not fully open – Fully open manual shutoff valve.
d. Thermocouple connection loose at control valve – Hand tighten until snug, then tighten 1/4 turn more.
e. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This problem could be caused by either low gas pressure or dirty or partially clogged ODS/pilot – Contact local gas company.
f. Thermocouple damaged – Replace thermocouple. g. Control valve damaged – Replace control valve. 8. Burner does not light after ODS/pilot is lit. a. Burner orifice clogged – Clean burner or replace main
burner orifice. b. Burner orifice diameter is too small – Replace burner
orifice. c. Inlet gas pressure is too low – Contact qualified service
person. 9. If burning at main burner orifice occurs (a loud,
roaring blow torch noise). a. You must turn off burner assembly and contact a
qualified service person. b. Manifold pressure is too low – Contact local gas
company. c. Burner orifice clogged – Clean burner or replace burner
orifice. 10. Logs appear to smoke after initial operation.
a. Vapors from paint or curing process of logs – Problem will stop after a few hours of operation. Run the heater with the damper open if you have one, or open a window for the first few hours. Log heater is intended to be smokeless. Turn OFF heater and call qualified service person.
11. Heater produces a whistling noise when main burner is lit. a. Turning control knob to HIGH position when main burner is cold – Turn control knob to LOW position and let warm up for a minute. b. Air in gas line – Operate burner until air is removed from line. Have gas line checked by local gas company. c. Dirty or partially clogged burner orifice – Clean burner or replace burner orifice.
12. No gas to pilot. a. Propane regulator shut down due to inlet pressure too high – Verify Propane tank regulator is installed and set at 11″ to 13″ w.c. Replace regulator on heater.

If the gas quality is bad, your pilot may not stay lit, the burners may produce soot and the heater may backfire when lit. If the gas quality or pressure is low, contact your local gas supplier immediately.

39025-2-0620

Page 23

INTERMITTENT CONTROL SYSTEM OPERATING INSTRUCTIONS

5.25 VDC ELECTRONIC CONTROL VALVE The electronic control valve system includes the ability to switch the pilot from a standing pilot mode to an intermittent pilot mode.
· IPI Mode – In the Intermittent Pilot mode, when the unit is turned ON, it will cause spark to the pilot, light the pilot, then allow the burner to light. When the unit is turned to OFF, both the burner and pilot will be OFF.
· CPI Mode – In the Continuous Pilot mode, the pilot remains ON continuously even when the burner is turned OFF.
NOTE: A small toggle switch is located on a bracket that is used to switch from IPI (upward position) to the CPI (downward position). See Figure 20.
When the unit is turned to ON, the electrical current will energize a spark to the pilot igniter. Once the pilot sensor heats up (after a few seconds), the valve will be energized, allowing gas to flow to the burner.

1. Follow the SAFETY and LIGHTING INSTRUCTIONS for Intermittent Pilot controls found in this manual, and on labels found in the control compartment located in the lower cavity of the appliance.
2. During the operating season (or in power outage periods), it is recommended that the pilot remain in the CPI (standing pilot mode) to reduce cold start issues, and/or conserve battery backup power during a power outage.
3. The gas valve has inlet and outlet pressure taps as shown in Figure 20. Refer to pages 10 and 11 for gas pressure requirements.
NOTE: The gas control has a manual HI/LO flame adjustment knob (regulator) that allows you to increase or decrease the height of the burner flame. See Figure 20. Rotate the HI/LO knob counterclockwise to “HI” to increase the flame height, and clockwise to “LO” to decrease the flame height.
OPTIONAL REMOTE CONTROLS Optional remote controls are available for use with this appliance. To connect the remote receiver to the appliance, first disconnect the ON/OFF switch wires from the white and green wire connectors and connect the wires from the remote receiver to the green and white wire connectors. Follow the instructions included with the remote control for programming and other operational information.

DFC ELECTRONIC CONTROL MODULE

9 PIN CONNECTOR IGNITOR
GROUND
SPARK ROD

SENSOR

PILOT SENSOR

REMOTE

CONTROL

RECEIVER

IPI

CPI
AA (4) BATTERY BACKUP

PILOT SELECTOR SWITCH IPI – INTERMITANT PILOT (UP) CPI – CONTINUOUS PILOT (DOWN)

PILOT ASSEMBLY

GAS VALVE

OUTLET PRESSURE TAP
Figure 20

INLET PRESSURE TAP

Page 24

39025-2-0620

INTERMITTENT CONTROL SYSTEM WIRING DIAGRAM

BLACK WHITE
( ( (

CPI/IPI SWITCH

BLUE WHITE

BLUE WHITE

REMOTE RECEIVER (OPTIONAL)

OR

ON/OFF SWITCH

GREEN ORANGE
YELLOW

PILOT

+ ON REMOTE
– OFF

GAS CONTROL VALVE

BLACK

BLACK

AC/DC POWER ADAPTOR

WHITE GREEN BLACK RED

(GND)

BATTERY BACK-UP BATTERY HOLDER

BLACK RED

Figure 21

ELECTRONIC CONTROL MODULE

If any of the original wire as supplied with this unit must be replaced, it must be replaced with equivalent gauge and temperature rated wire.

This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an aftermarket, permanently located, manufactured (mobile) home where not prohibited by local codes. This appliance is not convertible for use with other gases.

CAUTION Do not operate the appliance with panel(s) removed, cracked or broken. Replacement of the panel(s) should be done by a licensed or qualified service person.
WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.

39025-2-0620

Page 25

INTERMITTENT CONTROL SYSTEM TROUBLESHOOTING

Brief Description of the Components The gas valve is equipped with a manual HI/LO knob to allow for manual modulation of the gas outlet pressure. The manual HI/LO knob can be replaced by an Empire Comfort Systems Variable Remote Kit.
WARNING
This appliance is equipped for Natural or Propane gas. Field conversion is not permitted.
The Digital Fireplace Control (DFC) is an automatic gas ignition system based on a single microcontroller core. This control manages all functions related to ignition, flame sensing and supervision for atmospheric applications.
The DFC can be set to provide continuous or intermittent ignition control sequences and flame monitoring with safety shutdown in case of failure.
The DFC is set up as a stand alone (AC powered system with battery back up. See Lighting Instructions on page 18 and Wiring Diagram on page 24.
Troubleshooting Before proceeding with the procedures in the following troubleshooting table, verify that the power supply (AC/DC adapter) is present and that the batteries inside the receiver and/or optional battery pack are fresh and installed with correct polarity. Make sure all the connections between the wire harnesses and system components are proper and positive.
Verify that the static inlet pressure meets the manufacturer’s recommended inlet pressure. If necessary adjust the line pressure regulator.
If the recommended actions for the following troubleshooting chart do not help to address the problem consider replacing wiring harnesses.
WARNING
Any actions performed on the gas valve must be performed in accordance with this instruction manual. Likewise, any actions performed on the DFC or other system components must be done in accordance with the individual component instructions. Replacement of components must be performed in accordance with this instructions manual.

Page 26

39025-2-0620

INTERMITTENT CONTROL SYSTEM TROUBLESHOOTING
1

If the DFC giving signal lock out:

The board should be unlocked to

reinitiate a pilot flame ignition (for

NO

the correct unlock sequence refer

to the DFC Use and Installation

Instructions).

YES

1. Verify the electrical connections’ integrity and

make sure they are in accordance with the relevant

Is the DFC board in

NO

system wiring diagram. If necessary replace the

lock out?

wire harness.

2. Replace the DFC board.

YES

1. Check the spark electrode positioning – adjust as necessary.

Was observed spark

2. Replace the pilot assembly.

at the Pilot Hood

NO

before the DFC

3. Verify the electrical connections’ integrity and

board locked out?

make sure they are in accordance with the

relevant system wiring diagram. If necessary

replace the wire harness.

4. Replace the DFC board.

YES

1. Verify the electrical connections’ integrity and make sure they are in accordance with the relevant system wiring diagram. If necessary replace the wire harness.
2. If pilot flow adjuster screw is not sealed: Check if pilot flow adjust screw is set correctly in accordance with the appliance manufacturer instructions. If necessary correct it.
3. Replace pilot tube or complete pilot assembly.
4. Replace the pilot orifice with a new orifice of correct size, and type, or replace the pilot assembly. Under all circumstances follow the appliance manufacturer’s service instructions.
5. Remove the provided wiring harnesses from Ev1 of gas valve (red base), and verify voltage at ignition between the Ev1 terminal and the ground connection on teh valve body. If the voltage is greater than 0 then Replace Valve. Otherwise Replace DFC.

Spark continues while the pilot is ON.
NO
2

YES

1. Replace the pilot assembly. 2. Replace the DFC board.

39025-2-0620

Page 27

INTERMITTENT CONTROL SYSTEM TROUBLESHOOTING
2

Main burner lights when the pilot only
should light.

YES

1. Replace DFC board. 2. Replace the gas valve.

1. Verify the pilot flame fully engulfs the tip of the sense electrode. If not replace the pilot

NO

assembly.

2. Replace the pilot assembly.

3. Carefully clean the electrical connections of the sense cable, and the DFC board sense cable connection.

Pilot holds the flame?.

NO

4. Replace the sense cable, or the cable-sense electrode assembly, or the pilot assembly.

5. Verify the pilot is properly grounded.

6. Replace the pilot orifice with a new orifice of correct size, and type, or replace the pilot assembly.

YES

7. If pilot flow adjuster screw is not sealed, correct it.

Main burner ignites? YES

1. Verify the electrical connections’ integrity and make sure they are in accordance with the relevant system wiring diagram. If necessary replace the wire harness.
2. Check if the optional remote transmitter is in “thermostat” or “on” mode and verifyt there is a call for heat (f using a thermostat remote). Adjust the setting for heat.
3. Verify that the pilot hood is properly fitted and a pilot flame is directed to properly ignite the main appliance burner.
NO 4. Replace the main burner orifice with a new orifice of correct size and type, or replace the pilot assembly. Under all circumstances follow the service instructions.
5. Remove the provided wiring harnesses from EV2 of gas valve (red base), and verify voltage at ignition between the EV1 terminal and the ground connection on the valve body. 5.1 If the voltage is greater than 0 then Replace Valve. 5.2 Or Replace DFC.
6. Check the pressure at the outlet pressure test point out according to the manufacturer’s instruction. If not in accordance, replace the gas valve.

1. Verify the electrical connections’ integrity and make sure they are in accordance with the relevant system wiring diagram. If necessary replace the wire harness.

2. Check the pressure at the outlet pressure test point out according the manufacturer’s instruction. If not in accordance replace the gas valve.

Main burner remains

NO

3. With the system in the OFF position, connect the voltmeter between the EV2 terminal

ON

(green base) on the valve, and the ground on the valve body.

Turn the system ON, let pilot light, and observe the following voltage sequence: once the pilot

flame is proved, the voltage on EV2 should spike to approx. 5 VdC for approx. 2 sec and then

drop to approx. 0.6 VdC continuously.

3.1 If the sequence is respected, replace the gas valve.

3.2 If the sequence is not respected, replace the DFC board.

Main burner modulates properly?
Page 28

1. Replace the main burner orifice with a new orifice of correct size (partial blockage possible). Verify that the main burner flame modulates. If it does not modulate replace the gas valve.
2. Verify that the gas valve outlet pressure limits are in accordance with the manufacturer specifications. If not replace the gas valve.
FOR MANUAL HI/LO VERSION 3. Verify the flame changes while rotating the HI/LO knob on the front of the gas valve. If there is no change replace the gas valve.
39025-2-0620

OPTIONAL VARIABLE SPEED BLOWER INSTALLATION INSTRUCTIONS

FBB5 BLOWER INSTALLATION Attention: Install blower assembly before connecting gas inlet supply line.
NOTE: Junction box on right side of fireplace must be pre-wired at time of fireplace installation for use with blower assembly. It is recommended that an ON/OFF wall switch be installed that will activate the power supply to the furnace by a qualified electrician. See page 31 for junction box wiring instructions
1. If installed, turn OFF gas supply to fireplace.
2. If applicable, turn OFF electric supply to fireplace.
3. Lower bottom louver on fireplace.
Attention: If installed, do not damage gas inlet supply line when blower assembly is inserted into fireplace. If necessary, removal of the gas inlet supply line may be necessary.
4. Insert blower assembly into interior, bottom of fireplace. Position blower assembly behind gas valve, align notch on back of blower assembly with center screw on fireplace back and push blower assembly against fireplace back. The blower wheel must be centered with the back wall of the fireplace. Place blower assembly against the back wall. The magnets on the back and bottom of blower assembly will sufficiently hold blower assembly in place.
5. Position speed control box to the right of gas valve. Attach speed control box to bottom of fireplace. The magnets on the bottom of speed control will sufficiently hold the speed control box in place.
6. With base (flush face) of fan control switch facing upward, insert base flanges of fan control switch under the mounting tabs on valve bracket. The base (flush face) of fan control switch must be in contract with bottom of the firebox.
7. Insert power cord plug into junction box.
8. Close bottom louver on fireplace.
NOTE: This blower is equipped with a heat activated fan control switch. Fan will operate when the fireplace warms up, and will turn off when the fireplace cools down.
9. Installation of FBB4 optional variable speed blower assembly is completed.

FAN CONTROL SWITCH LOCATION FAN CONTROL WIRES
Figure 22

39025-2-0620

Page 29

OPTIONAL VARIABLE SPEED BLOWER INSTALLATION INSTRUCTIONS

WIRING The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, if an external electrical source is utilized. This appliance is equipped with a three-prong [grounding] plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug. For an ungrounded receptacle, an adapter, which has two prongs and a wire for grounding, can be purchased, plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw. With this wire completing the ground, the appliance cord plug can be plugged into the adapter and be electrically grounded.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
BLOWER MOTOR The blower motor does not have oiling holes. Do not attempt to oil the blower motor.
BLOWER WHEELS The blower wheels will collect lint and could require periodic cleaning. If the air output decreases or the noise level increases, it indicates a dirty blower wheel. Remove blower and clean blower wheels.
WARNING
Unplugging of blower accessory will not stop the heater from cycling. To turn off gas to the unvented heater: Push in gas control knob slightly and turn clockwise to “OFF.” Do not force.

JUNCTION BOX FAN

110 VOLT AC

FAN SWITCH
WHITE BLACK
SPEED CONTROL
Figure 23
5

GROUND BLACK
WHITE
2

5 1 2 3 4

FBB4 R7649 R4192 R4186

1

4

3

BLOWER ASSEMBLY COMPLETE FAN CONTROL
SPEED CONTROL KNOB SPEED CONTROL

Figure 24

Page 30

39025-2-0620

JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS

CAUTION
All wiring should be done by a qualified electrician and shall be in compliance with all local, city and state building codes. Before making the electrical connection, make sure that main power supply is disconnected. The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the national electrical code ansi/nfpa 70 (latest edition).

A factory installed junction box is located on the lower right hand side of the fireplace. Wiring must be fed to the junction box and attached to the receptacle that is provided. Remove the knockout in the installed junction box to accept wiring into the junction box. Install a UL listed cable clamp (not supplied) in the knockout hole. Leave approximately 6″ of wire in the junction box for connection.
Attach black wire to one side of the receptacle and white wire to opposite side of receptacle. The ground wire should be attached to the green (neutral) screw.
Install the receptacle into the junction box. Attach cover plate.

Figure 25

39025-2-0620

Page 31

MASTER PARTS DISTRIBUTOR LIST

To Order Parts Under Warranty, please contact your local Empire dealer. See the dealer locator at www.empirecomfort. com. To provide warranty service, your dealer will need your name and address, purchase date and serial number, and the nature of the problem with the unit. To Order Parts After the Warranty Period, please contact your dealer or one of the Master Parts Distributors listed below. This list changes from time to time. For the current list, please click on the Master Parts button at www.empirecomfort.com. Please note: Master Parts Distributors are independent businesses that stock the most commonly ordered Original Equipment repair parts for Heaters, Grills, and Fireplaces manufactured by Empire Comfort Systems Inc.

Dey Distributing 1401 Willow Lake Boulevard Vadnais Heights, MN 55101

F. W. Webb Company 200 Locust Street Hartford, CT 06114

Phone: 651-490-9191 Toll Free: 800-397-1339 Website: www.deydistributing.com Parts: Heater, Hearth and Grills

Phone: 860-722-2433 Toll Free: 800-243-9360 Fax: 860-293-0479 Toll Free Fax: 800-274-2004 Websites: www.fwwebb.com & www.victormfg.com Parts: Heater, Hearth and Grills

East Coast Energy Products 10 East Route 36 West Long Branch, NJ 07764
Phone: 732-870-8809 Toll Free: 800-755-8809 Fax: 732-870-8811 Website: www.eastcoastenergy.com Parts: Heater, Hearth and Grills

HOW TO ORDER REPAIR PARTS

Parts Not Under Warranty
Parts can be ordered through your Service Person, Dealer, or a Master Parts Distributor. See this page for the Master Parts Distributors list. For best results, the service person or dealer should order parts through the distributor. Parts can be shipped directly to the service person/dealer.
Warranty Parts
Warranty parts will need a proof of purchase and can be ordered by your Service Person or Dealer. Proof of purchase is required for warranty parts.
All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number and Serial Number from the name plate on your equipment. Then determine the Part Number (not the Index Number) and the Description of each part from the following illustration and part list. Be sure to give all this information . . .

Appliance Model Number

Part Description

Appliance Serial Number

Part Number

Type of Gas (Propane or Natural)

Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store. Shipments contingent upon strikes, fires and all causes beyond our control.

Page 32

39025-2-0620

VFPA32BP(3,7) PARTS LIST

ATTENTION: When ordering parts, it is very important that part number and description of part coincide.

Index No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 14 14 15 15 16 16 17 18 19 20 21 22 23 23 24 25 26 26 27 28 29 30 30 31 32

PART NUMBER – VFPA32

30 Series

70 Series

39279

39279

39492

39492

40736

40736

41135

41135

41136

41136

17169

17169

17170

17170

39517

39517

39278

39278

39520

39520

17370

17370

39273

39274

P200

P200

N/A

N/A

P243

P243

P250

P250

R5676

R5676

R5675

R5675

R3624

R11328

R3623

R11327

20467

N/A

23694

23694

N/A

29376

17369

29825

R2423

R2423

20115

29377

R3626

R11125

R3625

R11126

R3436

R2522

R2708

N/A

20117

33798

20122

33797

R7063

R7063

20116

29816

N/A

N/A

N/A

N/A

N/A

N/A

R5668

R11333

R10947

R11123

Description
Fireplace Painted Assembly Face Assembly Complete Top Trim Left Trim Right Trim Louver Assembly – Top Louver Assembly – Bottom Hood Screen Frame – Welded Assembly Junction Box Assembly Burner Assembly Burner Base Assembly Orifice Fitting Orifice – Natural #42 Orifice – Natural #36 Orifice – Propane 1.65mm Air Shutter – Natural Air Shutter – Propane Pilot Assembly – Natural Pilot Assembly – Propane Pilot Shield Air Shutter Shield Pilot Bracket Tubing Assembly Connector – Male 5/16 X 3/8 NPT Valve Bracket Valve Assembly – Natural Valve Assembly – Propane Switch – ON/OFF Piezo Ignitor Tubing Assembly – Natural Tubing Assembly – Propane Regulator – Pilot – Natural Tubing Assembly – Natural Nipple – 3/8 NPT X 1-1/2 Regulator – Pilot – Natural – 6.0″ WC NAT Regulator – Pilot – Natural – 10.0″ WC LPG Wire – Ignitor Wire Assembly

USE ONLY MANUFACTURER’S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH. NOTE: SEE LOG INSTRUCTION MANUAL FOR DETAILS ON LOGS AND EMBERS

39025-2-0620

Page 33

VFPA32BP(3,7) PARTS LIST (CONT’D)

ATTENTION: When ordering parts, it is very important that part number and description of part coincide.

Index No. 33 34 35 36 37 38 N/S N/S N/S N/S

PART NUMBER – VFPA32

30 Series

70 Series

N/A

R11332

N/A

R2667

N/A

29699

N/A

R11127

N/A

R11122

N/A

R11128

18704

18704

R3491

R3491

R3492

R3492

N/A

31273

Description
Wire – Sensor – 24 in Wire Assembly – ON/OFF Switch Bracket – ON/OFF Switch Control Board – Proflame DFC Battery Holder – AA With Snap On Power Adaptor – 7.0 VDC Decorative Rock (1 LB) Cover – Junction Box Receptical – 3 Prong Pilot Flame Shield

Page 34

39025-2-0620

VFPA36BP(3,7) PARTS LIST

ATTENTION: When ordering parts, it is very important that part number and description of part coincide.

Index No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 14 14 15 15 16 16 17 18 19 20 21 22 23 23 24 25 26 26 27 28 29 30 30 31 32

PART NUMBER – VFPA36

30 Series

70 Series

39295

39295

39494

39494

40737

40737

41137

41137

41138

41138

18807

18807

18808

18808

39518

39518

39294

39294

39520

39520

17386

17386

39289

39290

P200

P200

N/A

N/A

P211

P211

P245

P245

R5676

R5676

R5675

R5675

R3624

R11328

R3623

R11327

20467

N/A

23694

23694

N/A

29376

17369

29825

R2423

R2423

20115

29377

R3626

R11125

R3625

R11126

R3436

R2522

R2708

N/A

20117

33798

20122

33797

R7063

R7063

20116

29816

N/A

N/A

N/A

N/A

N/A

N/A

R5668

R11333

R10947

R11123

Description
Fireplace Painted Assembly Face Assembly Complete Top Trim Left Trim Right Trim Louver Assembly – Top Louver Assembly – Bottom Hood Screen Frame – Welded Assembly Junction Box Assembly Burner Assembly Burner Base Assembly Orifice Fitting Orifice – Natural #37 Orifice – Natural #32 Orifice – Propane #50 Air Shutter – Natural Air Shutter – Propane Pilot Assembly – Natural Pilot Assembly – Propane Pilot Shield Air Shutter Shield Pilot Bracket Tubing Assembly Connector – Male 5/16 X 3/8 NPT Valve Bracket Valve Assembly – Natural Valve Assembly – Propane Switch – ON/OFF Piezo Ignitor Tubing Assembly – Natural Tubing Assembly – Propane Regulator – Pilot – Natural Tubing Assembly – Natural Nipple – 3/8 NPT X 1 1/2 Regulator – Pilot – Natural – 6.0″ WC NAT Regulator – Pilot – Natural – 10.0″ WC LPG Wire – Ignitor Wire Assembly

USE ONLY MANUFACTURER’S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH. NOTE: SEE LOG INSTRUCTION MANUAL FOR DETAILS ON LOGS AND EMBERS

39025-2-0620

Page 35

VFPA36BP(3,7) PARTS LIST

ATTENTION: When ordering parts, it is very important that part number and description of part coincide.

Index No. 33 34 35 36 37 38 N/S N/S N/S N/S

PART NUMBER – VFPA36

30 Series

70 Series

N/A

R11332

N/A

R2667

N/A

29699

N/A

R11127

N/A

R11122

N/A

R11128

18704

18704

R3491

R3491

R3492

R3492

N/A

31273

Description
Wire – Sensor – 24 in Wire Assembly – ON/OFF Switch Bracket – ON/OFF Switch Control Board – Proflame DFC Battery Holder – AA With Snap On Power Adaptor – 7.0 VDC Decorative Rock (1 LB) Cover – Junction Box Receptical – 3 Prong Pilot Flame Shield

Page 36

39025-2-0620

PARTS VIEW
1 2
4

3 6 8
9 5

10

13

15

11

14 12

18

16 20

17

32

26

21

22

23

27 28 25

31 24

MILLIVOLT VALVE ASSEMBLY

39025-2-0620

7

19

16

24

23

22

35

27

26

20

26 28
31 36

33

34

32

37

38

INTERMITTENT PILOT (IP) VALVE ASSEMBLY

Page 37

WARRANTY

Empire Comfort Systems Inc. warranties this hearth product to be free from defects at the time of purchase and for the periods specified below. Hearth products must be installed by a qualified technician and must be maintained and operated safely, in accordance with the instructions in the owner’s manual. This warranty applies to the original purchaser only and is not transferable. All warranty repairs must be accomplished by a qualified gas appliance technician.
Limited Lifetime Parts Warranty with a Five-Year Limited Labor Warranty ­ Combustion Chamber and Heat Exchanger If the combustion chamber or heat exchanger (see parts list) fails because of defective workmanship or material, Empire will repair or replace at Empire’s option. Within five years from the date of purchase, Empire will pay reasonable labor to have the defective part repaired or replaced at Empire’s option.
Limited Five-Year Parts & Labor Warranty ­ All Other Components (Except Remote Controls, Thermostats, Accessories and Replacement Parts)
Should any part fail because of defective workmanship or material within five years from the date of purchase, Empire will repair or replace at Empire’s option. Within five years from the date of purchase, Empire will pay reasonable labor to have that defect repaired at Empire’s option.
Limited One-Year Parts Warranty ­ Remote Controls, Thermostats, Accessories, and Parts Should any remote control, thermostat, accessory, or other part fail because of defective workmanship within one year from the date of purchase, Empire will repair or replace at Empire’s option.
Duties Of The Owner The appliance must be installed by a qualified installer and operated in accordance with the instructions furnished with the appliance. A bill of sale, cancelled check, or payment record should be kept to verify purchase date and establish warranty period. Ready access to the appliance for service.
What Is Not Covered Damages that might result from the use, misuse, or improper installation of this appliance. Travel, diagnostic costs and freight charges on warranted parts to and from the factory. Claims that do not involve defective workmanship or materials. Unauthorized service or parts replacements. Removal and reinstallation cost. Inoperable due to improper or lack of maintenance.
How To Get Service To make a claim under this warranty, please have your receipt available and contact your installing dealer. Provide the dealer with the model number, serial number, type of gas, and purchase verification. The installing dealer is responsible for providing service and will contact the factory to initiate any warranted parts replacements. Empire will make replacement parts available at the factory. Shipping expenses are not covered. If, after contacting your Empire dealer, service received has not been satisfactory, contact: Consumer Relations Department, Empire Comfort Systems Inc., PO Box 529, Belleville, Illinois 62222, or send an e-mail to info@empirecomfort.com with “Consumer Relations” in the subject line.
Your Rights Under State Law This warranty gives your specific legal rights, and you may also have other rights, which vary from state to state.

Page 38

39025-2-0620

SERVICE TECHNICIAN NOTES

Date

Dealer Name

Service Technician Name

Service Performed/Notes

39025-2-0620

Page 39

Page 40

Empire Comfort Systems Inc. Belleville, IL If you have a general question about our products, please e-mail us at info@empirecomfort.com. If you have a service or repair question, please contact your dealer. www.empirecomfort.com

39025-2-0620