VEVOR CW-5202 Industrial Water Chiller User Manual
- July 3, 2024
- VEVOR
Table of Contents
- VEVOR CW-5202 Industrial Water Chiller
- SPECIFICATIONS
- DEVICE ILLUSTRATION
- PARAMETER ADJUSTMENT
- KEY PRESS INSTRUCTIONS
- POWER-ON DISPLAY AND TEMPERATURE CORRECTION
- MENU DESCRIPTION
- MORE INFORMATION
- Frequently Asked Questions
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
VEVOR CW-5202 Industrial Water Chiller
Specifications
- Model: CW-5202
- Power Supply: 220-240V (110-120V model available upon request)
- Frequency: 50Hz or 60Hz
This is the original instruction, please read all manual instructions carefully before operating. VEVOR reserves a clear interpretation of our user manual. The appearance of the product shall be subject to the product you received. Please forgive us that we won’t inform you again if there are any technology or software updates on our product.
Warning- To reduce the risk of injury, the user must read the instructions manual carefully.
WARN
-
PLEASE MAKE SURE THAT THE POWER SUPPLY AND THE POWER OUTLET ARE IN GOOD CONTACT AND THE GROUNDING WIRE MUST BE FIRM!
Although the average working current of the chiller is small, the instantaneous working current can sometimes reach 6~10 amperes (the instantaneous working current of the AC110V power supply model is possible up to 10~1 5 amperes) -
PLEASE MAKE SURE THAT THE WORKING CHILLER HAS A STABLE AND NORMAL VOLTAGE!
Since the refrigeration compressor is more sensitive to the power supply and voltage, so the working voltage our standard product is 220^ 240V (the 110V model is 110 120V), if you need a wider operating voltage range, we can customize it. -
PLEASE MISMATCHED POWER FREQUENCY WILL CAUSE CHILLER DAMAGE!
Please select mode: 50Hz or 60Hz depending on the actual situation. -
TO PROTECT THE PUMP, IT IS STRICTLY FORBIDDEN TO RUN THE CHILLER WITHOUT WATER IN THE STORAGE TANK!
The new machine is packed after draining the entire water in the tank, so please make sure that the tank has enough water and there is water inside the machine before starting, otherwise it is easy to damage the pump.
When the water level is below the green (normal) range of the water level gauge, the cooling capacity of our chillers will drop slightly. Therefore, make sure that the water level is in the green (normal) range. Pumps are strictly forbidden by circulating drainage! -
PLEASE MAKE SURE THE AIR INLET AND OUTLET ARE WELL-VENTILATED!
The air outlet from the obstacle to the back of the cooler must be at least 30 cm, and it should be at least 8 cm between the obstacle and the side air intake. -
THE FILTER MUST BE CLEANED REGULARLY!
The dust meter must be unlocked and cleaned, otherwise it will cause serious clogging failure to the cooler. -
PAY ATTENTION TO THE EFFECT OF CONDENSATE!
As the ambient humidity increases, when the water temperature is lower than the ambient temperature, condensate will create circular pipes and cooling parts on the water surface. If this occurs, it is recommended to set a higher water temperature or keep the connected pipes and cooling components warm.
PROFESSIONAL USE ONLY
- This device must not be used by a child or a person with physical, sensory or physical, sensory, or physical impairments, or lack of experience and knowledge, unless supervision or instruction is given, and the child is not allowed to play with electrical appliances!
- The circulating water of the water cooler must use a sealed container for normal use, such as laser tube cooling water. Unsealed containers cannot circulate, such as water basins, and buckets cannot be used for circulating water cooling with water coolers.
SPECIFICATIONS
Model | CW-5202 |
---|---|
voltage | AC220-240V |
frequency | 50Hz |
power | 550W |
Cooling capacity | 1.45kw |
Refrigerant | R134a |
noises | ≤80dB |
Water tank capacity | 7L |
Maximum flow | 18L/min |
Pump power | 48W |
The main material | Iron, copper |
Security | Compressor overcurrent protection flow alarm |
overtemperature alarm
DEVICE ILLUSTRATION
front
behind
PROCEDURE
- Installing this industrial chiller is very simple.
- The first installation of a new machine can be carried out by following these
steps:
-
OPEN THE PACKAGE TO CHECK IF THE MACHINE IS FIXED AND ALL NECESSARY ACCESSORIES ARE COMPLETE.
-
OPEN THE WATER SUPPLY INLET TO SUPPLY COOLING WATER (DON’T SPILL THE WATER OUT!).
Observe the water level gauge and add water slowly, taking care not to let the water overflow! For the cooling of carbon steel equipment, an appropriate amount of cooling water additive (anti-corrosion water aqua) should be added to the water. Users in cold regions should use non-corrosive antifreeze. -
CONNECT THE INLET AND OUTLET PIPES ACCORDING TO THE SYSTEM CONDITIONS.
-
PLUG IN THE POWER SUPPLY AND TURN ON THE POWER SWITCH. (DON’T START WITHOUT WATER IN THE TANK!)
-
The power switch is turned on and the circulating pump of the chiller starts to work. The first operation may cause more bubbles in the pipe, causing occasional alarms for traffic, but after a few minutes of operation, it will return to normal.
-
After the first start-up, the water pipe must be checked for leakage immediately.
-
The power supply is turned on, if the water temperature is lower than the set value, it is normal that the fan and other parts of the machine do not work. The temperature controller will automatically control the working state of compressor solenoid valves, fans and other components according to the set control parameters.
-
Since the restart of the compressor and other components takes a long time, depending on different conditions, the time varies from a few seconds to a few minutes, so do not turn off the power frequently and turn it on again.
-
CHECK THE WATER LEVEL IN THE TANK. The first start of the new cooler drains the air in the water pipe, causing a slight drop in the water level, but in order to maintain the water level in the green area, it is allowed to add enough water again. Please observe and record the current water level, check again after the chiller has been running for a period of time, and if the water level drops significantly, please re-check the leakage of the water pipe.
-
ADJUST THE TEMPERATURE CONTROLLER PARAMETERS.
CW-5000/5200 series uses intelligent thermostats. Usually, the user does not need to adjust it. If it is really necessary. See “Operating status and parameter tuning”.
PARAMETER ADJUSTMENT
- The new T503 intelligent temperature controller requires no regulation control. Parameters under normal conditions.
- The control parameters can be adjusted according to the room temperature to meet the heat dissipation requirements of the equipment. The new T504 intelligent temperature control selects the constant temperature control mode as the factory setting, and the water temperature is 25°C, which can be adjusted by the user as needed.
- The functions and structure of the T503 and T504 controllers are the same, except for factory parameter settings.
DISPLAY PANEL AND BUTTONS
- Display description: the data display area of the manual exercise board displays temperature, system parameters, alarm codes and other data; The blinking period for each field is 1 second; After powering on, the full display works normally after about 5 seconds.
- Display symbol description:
LIGHT| STATE| FUNCTION OR MEANING
---|---|---
Red light in upper left corner
| Light up| The controller operates in intelligent control
mode
flashing| The controller operates in constant
temperature mode
extinguish| The controller is in parameterization mode
Red light in lower left corner
| Light up| The controller is in a cooled state
flashing| The controller is in an uncooled state
extinguish| The controller is in a microcooled state
3. Key definition description:
KEYSTROKE| NAME| KEY FEATURES
---|---|---
RST key| Determine the key| OK button to save and exit after
setting data
SET key| Set the key| Modify the parameter settings
▲key| Dial up the key| Numeric values/parameter entries are
incremented
▼key| Dial down the key| Numeric value/parameter entry
decrement
KEY PRESS INSTRUCTIONS
SORT | KEYSTROKE | FUNCTION | DESCRIPTION OF THE OPERATION |
---|
1
|
▲+▼+RST
|
Factory parameter adjustment
| Press and hold the ▲ ▼ key and the RST key at the same time after the thermostat is powered on, display 99 after three seconds, press the ▲ ▼ key to modify the password of the factory setting (50), press the SET key to enter the menu, you can modify the factory setting, you can change the (F0~A13) parameters. Press OK (RST) to modify and save the parameters to factory settings.
2
|
▲+SET
|
User parameter adjustment
| 1. First press and hold the ▲ key, and then press the SET key at the same time for five seconds to display 0, at this time press the ▲▼ key to select the set password, and then press the OK key, if the password is correct, the display turns to F0 and enters the setting state. The panel indicator D1 flashes to indicate that the controller is now in the
parameter-setting state. If the password is incorrect, the temperature display is returned.
2. After entering the setting state, press the ▲ key to cycle into the selection setting items in turn, and press the ▼ key to cycle in the opposite direction. (Only display F0-F11) Select the set item and then press the setting key to enter the next level of parameter modification, display the original set value, press the ▲▼ key to modify the parameter value, and then press the set key to return to the previous menu setting item.
3. Press the OK key (RST) at any time, save the modified parameters, exit the parameter setting state, return the
temperature display, and run according to the new
| | | parameters. If no key is pressed within 20 seconds, the controller will
automatically exit the parameter setting state and will not save the modified
parameters. (When the parameter setting state, the system runs according to
the original parameters)
---|---|---|---
3
|
▲+▼
|
Parameter adjustment
| After holding the ▲▼ key at the same time, the thermostat is powered on, and “rE” is displayed after three seconds, and the newly adjusted manufacturer parameter value (the parameter adjusted by ” ▲+▼+RST”) takes effect, and returns to normal operation after three seconds.
4
|
▼
| Check the room temperature flow value (red light D1 flashing)| 1. Press the ▼ key once to display t1, and then press the ▼ key to display the room temperature.2. Press the ▼ key once to display t2, and then press the ▼ key to display the flow rate 1 (single for liter: L).3. Press the ▼ key once to display t3, and then press the ▼ key to display flow rate 2 (single for liter: L).4. No button is pressed, and the water temperature is restored after six seconds.
Note: Live traffic L = flow frequency HZ/flow coefficient.
5
|
SET
|
Quick adjust
| Press the SET key while the thermostat is working properly:
1. The thermostat works in the constant temperature mode of the intelligent thermostat, and the panel displays the parameter value of F0 (set temperature).
2. The thermostat works in intelligent mode, and the panel displays the parameter value of F1 (temperature difference value). Panel D1 now flashes, indicating that the controller is now in the setting state for the parameter.
Press the ▲▼ key to modify the setting, then press the SET key or press it without a key for 20 seconds
then do not save and exit. If you press the RST key, the disk is
saved and exited,and the new parameter takes effect.
6
|
SET+RST
|
Self-test mode
| During 5 minutes of powering on, press the “SET key” and “RST key” at the same time for 10 seconds to enter the self-test mode, and perform the following logic in turn:
1. Display the program version.
2. Display -11.1 ~-22.2 All indicator lights are on, and the compressor relay is closed and disconnected once.
3. Display -33.3 All indicator lights are on, and the solenoid valve relay is closed.
4. Display 444 All indicator lights are off, and the solenoid valve relay is disconnected.
5. Display 555~666 All indicator lights are off, and the alarm relay is closed and disconnected once.
6. Display 777~888 All indicator lights are off, and the buzzer
rings once. 7. Exit the self-test mode.
POWER-ON DISPLAY AND TEMPERATURE CORRECTION
After power-on, the display panel should have 3 seconds flashing at the same time display indicator and digital tube (including D1, D2, — day. day), when the temperature value of the displayed room temperature and water temperature is different from the actual temperature, A4, A5 can be adjusted to correct the displayed temperature value.
Failsafe
In the thermostat alarm state, press any key to stop the alarm buzzer sound,
the display screen displays the alarm code, and when the alarm condition is
eliminated, the display screen returns to normal display.
Alarm code and control logic:
ALARM CODE | ALARM CONTENT | ALARM CONDITIONS |
---|---|---|
E1 | The room temperature is super high | Room temperature> F6 (ultra-high |
temperature alarm value)
E2| The water temperature is super high| Water temperature> water temperature
setting temperature
+ F4 (water temperature super high alarm)
E3| The water temperature is
ultra-low
| Water temperature< water temperature setting temperature
-F5 (water temperature ultra-low alarm)
E4| Room temperature sensor failure| The room temperature sensor is shorted or
open
E5| Water temperature sensor
failure
| The water temperature sensor is shorted or open
E6
| ****
Traffic 1 alarm
| When A9=0, flow 1 enters to start the alarm when flow < F10 (flow 1 alarm value) is detected, and exit the alarm when flow > F10 (flow 1 alarm value); When A9=1,the flow 1 input switch is alarmed when it is open, and the exit alarm is
exited when the switch is turned on
E7
| ****
Traffic 2 alarm
| When A11=0, the flow 2 input starts the alarm when flow < F11 (flow 2 alarm value) is detected, and the alarm is exited when flow > F11 (flow 2 alarm value).
When A11=1, the alarm is activated when the flow 2 input switch is open, and the alarm is exited when the switch is
turned on
Concentrate:
- E2 alarm is effective only after meeting the start-up alarm delay (A1) or entering the target temperature section (that is, between the set temperature and the set temperature + refrigeration return difference F2) after the thermostat is powered on
- E3 alarm is effective only after meeting the start-up alarm delay (A1) and after the thermostat is powered on, the water temperature enters the target temperature section (that is, between the set temperature and the set temperature + refrigeration return difference F2).
- When the power on alarm delay A1 is set to 0,the E2 water temperature ultra-high alarm will be triggered immediately when the water temperature is super high when the power is turned on; When the power on water temperature is ultra-low, the E3 water temperature ultra-low alarm is triggered immediately
Relay output status when alarming:
- When E1, E2, E3 alarm, the compressor and refrigerant solenoid valve are controlled according to the normal control logic.
- The water temperature setting (F0) of the controller when E4 alarm runs according to the factory setting. When operating in constant temperature mode, there is no E4 alarm.
- When E5 alarms, the system automatically switches to the refrigeration state.
MENU DESCRIPTION
CODE
|
SET UP THE PROJECT
|
RANGE
| DEFAULT
VALUE
|
REMARK
---|---|---|---|---
F0
| Set the temperature| F9~F8/-20~
40
| 25.0| Smart temperature mode
Thermostatic mode
F1| Temperature difference value| – 15~5| -2.0|
F2| Refrigeration differential back| 0.1~3.0| 0.3| Accuracy 0.1 degrees
F3| Control mode| 0~1| 1| 1 Smart, 0 Thermostat
F4
| Water temperature super
high alarm
| 1~20| 10.0|
F5
| Water temperature ultra-low
alarm
| 1~20| 15.0|
F6| Alarm for high temperatures| 40~50| 45.0|
F7| password| 00~99| 8|
F8
| Maximum set
water temperature
| (F9+1)~40| 30.0|
F9
| Minimum set
water temperature
| 1~(F8-1)| 20.0|
F10| Traffic 1 alarm value| 0.0~10.0| 0.5| 0.0 = Cancel alarm
F11| Traffic 2 alarm value| 0.0~10.0| 0.0| 0.0 = Cancel alarm
A0| Heating differential back| 0.1~3.0| 0.5|
A1| Power-on alarm delay| 0~30| 5| minute
A2| Power-on delay| 10~99| 30| second
A3| State transition delay| 0~99| 20| second
A4| Room temperature correction| ﹣5.0~5.0| 0.0|
A5| Water temperature correction| ﹣5.0~5.0| 0.0|
A6| System inertia coefficient| 2~30| 8|
A7
| Compressor start-up
protection
| 0~99| 30| second
A8
| Temperature unit| 0~1| 0| 0=Celsius
1=Fahrenheit (not supported)
A9
| Traffic detection 1 input mode| 0~1| 1| 00 = pulse amount 01 =
switching quantity
---|---|---|---|---
A10
| Flow rate 1 factor| 0.0~60.0| 13.0| When set to 0 or 1
the coefficient has no effect
A11
| Traffic detection 2 input mode| 0~1| 0| 00 = pulse amount 01 =
switching quantity
A12
| Flow 2 factor| 0.0~60.0| 13.0| When set to 0 or 1
the coefficient has no effect
A13| Traffic delay alarm| 00~60 秒| 2| second
MORE INFORMATION
- Manufacturer: Shanghaimuxinmuyeyouxiangongsi
- Address: Shuangchenglu 803nong11hao1602A-1609shi, baoshanqu, shanghai 200000 CN.
- EC REP: E-CrossStu GmbH
- Mainzer Landstr.69, 60329 Frankfurt am Main.
- BYH CONSULTING LIMITED.
- C/O YH Consulting Limited Office 147, Centurion House, London Road, Staines-upon-Thames, Surrey, TW18 4AX
- Imported to AUS: SIHAO PTY LTD.
- 1 ROKEVA STREETEASTWOOD NSW 2122 Australia
- Imported to USA: Sanven Technology Ltd.
- Suite 250, 9166 Anaheim Place, Rancho Cucamonga, CA 91730
Technical Support and E-Warranty Certificate www.vevor.com/support
Frequently Asked Questions
- Q: What should I do if the chiller’s cooling capacity drops?
- A: Ensure the water level in the tank is within the green range and the pump is not circulating drainage.
- Q: How often should I clean the dust filter?
- A: The dust filter should be cleaned regularly to prevent clogging issues; monitor its condition periodically.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>