Satel SO-MF5 Keypad With MIFARE Proximity Card Reader Installation Guide

July 2, 2024
Satel

Satel SO-MF5 Keypad With MIFARE Proximity Card Reader

Satel SO-MF5 Keypad With MIFARE Proximity Card Reader

Important Information

Full manual is available on www.satel.pl. Scan the QR code to go to our website and download the manual.

The SO-MF5 keypad can operate as:

  • INT-SCR partition keypad in the INTEGRA alarm system,
  • ACCO-SCR keypad with proximity card reader in the ACCO access control system,
  • keypad with proximity card reader in systems of other manufacturers,
  • standalone door control module.

Before you mount the keypad, program the settings required for the selected operating mode in the CR SOFT program. The exception is a keypad that is to operate in the ACCO NET system and is to be connected to the ACCO-KP2 controller using the RS-485 bus (OSDP protocol). The OSDP protocol is supported by the ACCO-KP2 controllers with firmware version 1.01 (or newer). In that case, you can program the required settings in the ACCO Soft program (version 1.9 or newer).

Installation

The device should be installed by qualified personnel.
Prior to installation, please read the full manual.
Disconnect power before making any electrical connections.

  1. Open the keypad enclosure.

  2. Connect the keypad to the computer. Use the USB / RS-485 converter (e.g. ACCO-USB by SATEL). Follow the instructions in the converter manual.
    Do not connect more than 24 access control devices with the MIFARE card reader (SO-MF5, SO-MF3, CR-MF5 and CR-MF3) to the converter. The CR SOFT program may not be able to support more devices correctly.

  3. Program the keypad in the CR SOFT program.
    Create a new project or open an existing project.
    Establish connection between the program and the device.
    Program the settings and upload them to the keypad.

  4. Disconnect the keypad from the computer.

  5. Run the cables to where you want to install the keypad. To connect the RS-485 bus, we recommend using a UTP cable (unshielded twisted pair). To make other connections, use unshielded straight-through cables.

  6. Place the enclosure base against the wall and mark the location of mounting holes.

  7. Drill the holes in the wall for wall plugs (anchors).

  8. Run wires through the opening in the enclosure base.

  9. Use wall plugs and screws to secure the enclosure base to the wall. Select wall plugs specifically intended for the mounting surface (different for concrete or brick wall, different for plaster wall, etc.).

  10. Connect the wires to the keypad terminals (see: “Description of terminals”).

  11. Close the keypad enclosure.

  12. If necessary, program the settings required for the keypad to operate in the selected system.
     The ACCO Soft program in version 1.9 (or newer) enables programming of all the required settings. If it is to be used, you can skip the steps 2-4

Description of terminals

Description of terminals for keypad in the INTEGRA system

Terminal Description
NC relay output normally closed contact
C relay output common contact
NO relay output normally open contact
DATA/D1 data [INT-SCR interface]
RSA RS-485 bus terminal [OSDP]
RSB RS-485 bus terminal [OSDP]
TMP not used
+12V +12 VDC power input
COM common ground
CLK/D0 clock [INT-SCR interface
IN1 NC type door status input
IN2 NO type request-to-exit input
IN3 not used
BELL OC type output

Description of terminals for keypad in the ACCO system

Terminal Description
NC not used
C not used
NO not used
DATA/D1 data [ACCO-SCR interface]
RSA RS-485 bus terminal [OSDP]
RSB RS-485 bus terminal [OSDP]
TMP not used
+12V +12 VDC power input
COM common ground
CLK/D0 clock [ACCO-SCR interface]
IN1 not used
IN2 not used
IN3 not used
BELL OC type output

Description of terminals for keypad in other manufacturer’s system

Terminal Description
NC not used
C not used
NO not used
DATA/D1 data (1) [Wiegand interface]
RSA RS-485 bus terminal [OSDP]
RSB RS-485 bus terminal [OSDP]
TMP tamper output
+12V +12 VDC power input
COM common ground
CLK/D0 data (0) [Wiegand interface]
IN1 programmable input [Wiegand interface]
IN2 programmable input [Wiegand interface]
IN3 programmable input [Wiegand interface]
BELL OC type output

Description of terminals for the standalone door control module

Terminal Terminal Description
NC relay output normally closed contact
C relay output common contact
NO relay output normally open contact
DATA/D1 not used
RSA RS-485 bus terminal [OSDP]
RSB RS-485 bus terminal [OSDP]
TMP tamper output
+12V +12 VDC power input
COM common ground
CLK/D0 not used
IN1 door status input
IN2 request-to-exit input
IN3 not used
BELL OC type output

CUSTOMER SUPPORT

Hereby, SATEL sp. z o.o. declares that the radio equipment type SO-MF5 is in
compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity
is available at the following internet address: www.satel.pl/ce
SATEL sp. z o.o. • ul. Budowlanych 66 • 80-298 Gdansk • POLAND
tel. +48 58 320 94 00
www.satel.pl Logo