Telemecanique XPSLCMUT1160 Muting Relay Instruction Manual

June 3, 2024
Telemecanique

Telemecanique XPSLCMUT1160 Muting Relay Instruction

Troubleshooting guide

Table from the user manualTelemecanique-XPSLCMUT1160-Muting-Relay-
Instruction-fig-1

Troubleshooting examples

  • Yellow MUT led blinking 2 times ->muting lamp in fault

  • Root cause : bad connection, lamp missing or in fault, led lamp not compatible, too much current or not enough current in the lamp
    How to solve : check lamp connection, check voltage & power of the lamp (24 Vdc / 0.5 – 5 W). Change led lamp by filament lamp if necessary Telemecanique-XPSLCMUT1160-Muting-Relay-Instruction-
fig-3

  • Yellow MUT led blinking 3 times -> wrong selected value of the muting timeout

  • Root cause : 30s value not enough

  • How to solve : select « infinite » value by wiring

  • Yellow MUT led blinking 4 times -> wrong override configuration at power-up

  • Root cause : 1 muting photoelectric sensor in reflex mode not correctly adjusted

  • How to solve : check the muting sensors and mirrors, their fixing …

  • No sensor S1-S2 connected on terminals 1 & 2

    • Root cause: no sensor connection -> see picture showing leds status leds « fail » & « Guard break » On state no led on left side S1 S2 Mut. muting function does not operate at the light curtain
    • How to solve: connect the photoelectric sensors, complying to the user manual specifications, according to the wiring diagram show in the user manual of the unit Don’t forget to connect the muting lamp, because it is monitored