Telemecanique XCSD3p10ppp TES Electric US Safety Limit Switch Instruction Manual

June 13, 2024
Telemecanique

Telemecanique-logo

Telemecanique XCSD3p10ppp TES Electric US Safety Limit Switch

Product Information

The XCSD3ppp / P3ppp is a contact status device available in metal body (XCSD) or plastic body (XCSP). It is designed to comply with various standards including EN/IEC 60947-5-1, EN/ISO 13849-1, EN/IEC 62061, EN/IEC 60947-1, EN/ISO 14119, and EN/IEC 60204. The device can achieve up to category 4 PL=e or SIL 3 when combined with an appropriate Control Safety Unit.

The device is available in different models with different contact configurations and codes:

  • XCSD3p10ppp / XCSP3910ppp
  • XCSD3p02ppp / XCSP3902ppp
  • XCSD3p18ppp / XCSP3918ppp
  • XCSD3p19ppp / XCSP3919ppp

The device can be used in various applications and is suitable for different cable outputs such as ISO M20x1.5 (ppp = P20), PG 13.5 (ppp = G13), and 1/2 NPT (ppp = N12).

Product Usage Instructions

  1. Before working on the equipment, make sure to disconnect all power to avoid electric shock.
  2. Install the XCSD3ppp / P3ppp device according to the specified cable output (ISO M20x1.5, PG 13.5, or 1/2 NPT).
  3. Connect the device to the appropriate control safety unit to achieve the desired safety level (up to category 4 PL=e or SIL 3).
  4. Ensure that qualified personnel handle the installation, operation, servicing, and maintenance of the electrical equipment.
  5. Refer to the reliability data (B10d) provided for the device to understand its expected number of operations.
  6. Follow the specified rated operating characteristics for the device.
  7. Ensure that the device is protected against electric shock.
  8. Consider the minimum actuation speed (0.5 m/s, 1.5 m/s) when using the device in applications.
  9. Refer to the product certifications and ambient air temperature range for optimal performance.
  10. Take into account the vibration resistance and shock resistance of the device for proper usage.
  11. Follow the minimum force for tripping requirements specified (15 N / 3.372 lbs, 45 N / 10.116 lbs).
  12. Pay attention to the closed position of the device for accurate status indication (Fermeture, Geschlossen, Cerrado, Chiusura, Fechado).

Note: For more detailed instructions and technical information, please refer to the complete user manual available at http://qr.tesensors.com/XCS010.

Safety limit switch

http://qr.tesensors.com/XCS010

Telemecanique-XCSD3p10ppp-TES-Electric-US-Safety-Limit-Switch-
\(2\)

These devices have been designed to be in compliance with the standards currently in effect: EN/IEC 60947-5-1, EN/ISO 13849-1, EN/IEC 62061, EN/IEC 60947-1, EN/ISO 14119, EN/IEC 60204.
These devices can achieve up to category 4 PL=e or SIL 3 (if combined with an appropriate Control Safety Unit PL=e / SIL 3).

Dimensions

Telemecanique-XCSD3p10ppp-TES-Electric-US-Safety-Limit-Switch-
\(3\) Telemecanique-
XCSD3p10ppp-TES-Electric-US-Safety-Limit-Switch- \(4\)

Contact status

Contact closed (1)

Contact open (0)

XCSD3p10ppp
XCSP3910ppp

XCSD3p02ppp
XCSP3902ppp

Telemecanique-XCSD3p10ppp-TES-Electric-US-Safety-Limit-Switch-
\(7\)

XCSD3p18ppp
XCSP3918ppp

XCSD3p19ppp
XCSP3919ppp

Telemecanique-XCSD3p10ppp-TES-Electric-US-Safety-Limit-Switch-
\(7\)

  • Minimum force for tripping: 15 N / 3.372 lbsL; 12 N / 2.698 lbs: 0,1 N.m / 0.885 lb.in: 0,1 N.m / 0.885 lb.in
  • Minimum force for positive/direct opening: 45 N / 10.116 lbs:36 N / 8.093 lbs: 0,25 N.m / 2.212 lb.in: 0,25 N.m / 2.212 lb.in
  • Maximum actuation speed: 0,5 m/s: 0,5 m/s: 1,5 m/s: 1,5 m/s

Telemecanique-XCSD3p10ppp-TES-Electric-US-Safety-Limit-Switch-
\(9\)

(P) : Positive/direct opening point

Wiring diagram

DANGER
HAZARDOUS VOLTAGE
For mechanical/electrical redundancy, add another switch with positive/direct opening contacts

Cat. 1 – PL =c (EN/ISO 13849-1)
XCS-D/P
NC + NC + NO

Signaling contact

Telemecanique-XCSD3p10ppp-TES-Electric-US-Safety-Limit-Switch-
\(10\)

Cat. 3* – PL=d (EN/ISO 13849-1)
XCS-D/P
NC + NC + NO

Telemecanique-XCSD3p10ppp-TES-Electric-US-Safety-Limit-Switch-
\(10\)

Servicing precautions

Telemecanique-XCSD3p10ppp-TES-Electric-US-Safety-Limit-Switch-
\(13\)

Setting up

Telemecanique-XCSD3p10ppp-TES-Electric-US-Safety-Limit-Switch-
\(13\)

Head adjustment

Telemecanique-XCSD3p10ppp-TES-Electric-US-Safety-Limit-Switch-
\(13\)

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

Characteristics

  • Product certifications : UL, CSA, CCC, SAC
  • Ambient air temperature Operation : -25…+70 °C (- 13 F to 158 °F) ………… Storage : – 40…+70 °C (-40 F to 158 °F)
  • Vibration resistance 25 gn (10-500 Hz) conforming to IEC 60068-2-6
  • Shock resistance 50 gn (18 ms) conforming to IEC 60068-2-27
  • Number of operations 10 x 106
  • Reliability data B10d 50.000.000 (data value for a service life of 20 years can be limited by contact and mechanical wear)
  • Protection against electric shock Class I (XCSD), Class II (XCSP), as per IEC 61140, NFC 20 030
  • Rated operating characteristics a AC-15, B300:Ue = 240V, Ie = 1,5A c DC-13, R300 : Ue = 250V, Ie = 0,1A conforming to IEC 60 947-5-1, EN 60 947-5-1
  • Uimp 4 kV conforming to IEC 60 947-1, IEC 60 664
  • Short-circuit protection 6 A gG (gl) cartridge fuse (use type CC in the United States)
  • Cable output On screw clamps, tightening capacity : min 1#22 AWG (1 x 0.34 mm2), max 1#16 AWG (1 x 1 mm2) or 2#18 AWG (2 x 0.75 mm2),
  • Minimum actuation speed Snap action contact: 0.01 m/mn, slow break contact: 6 m/mn

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>