FURUNO PR-241 AC DC Power Supply Unit Installation Guide
- June 20, 2024
- FURUNO
Table of Contents
- Installation Guide
- AC/DC POWER SUPPLY UNIT
- Model PR-241
- SAFETY INSTRUCTIONS
- OVERVIEW
- EQUIPMENT LIST
- SYSTEM CONFIGURATION
- 1. MOUNTING
- 2. WIRING FOR SINGLE USE
- 3. WIRING FOR DUAL USE
- 4. HOW TO USE THE UNIT
- 5. JIS CABLE GUIDE
- SPECIFICATIONS OF AC/DC POWER SUPPLY UNIT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
- : MINIMUM SERVICE CLEARANCE.
Installation Guide
AC/DC POWER SUPPLY UNIT
Model PR-241
FURUNO ELECTRIC CO., LTD.
All brand and product names are trademarks, registered trademarks or service marks of their respective holders.
SAFETY INSTRUCTIONS
The operator and installer must read the applicable safety instructions before attempting to install or operate the equipment.
WARNING Indicates a condition that can cause death or serious injury if not avoided.
CAUTION Indicates a condition that can cause minor or moderate injury if not avoided.
Warning, Caution Prohibitive Action Mandatory Action
WARNING
Turn off the power at the switchboard before beginning the installation.
Fire, electrical shock or serious injury can result if the power is left on or is applied while the equipment is being installed.
Be sure that the power supply is compatible with the voltage rating of the equipment.
Connection of an incorrect power supply can cause fire or damage the equipment.
Use only the specified power cable.
Fire or damage to the equipment can result if a different cable is used.
Do not disassemble or modify the equipment.
Fire, electrical shock or serious injury can occur.
CAUTION
Ground the equipment to prevent electrical shock and mutual interference.
Observe the following compass safe distances to prevent deviation of a magnetic compass:
|
Standard compass
| Steering compass
PR-241|
0.85 m
| 0.55 m
Warning Labels(s)
Warning label(s) is(are) attached to the unit. Do not remove the label(s). If a label is missing or damaged, contact a FURUNO agent or dealer about replacement.
Name: Warning Label 1
Type: 86-003-1011-3
Code No.: 100-236-233-10
OVERVIEW
The PR-241 is a unit integrates the functions of our AC/DC power supply units and rectifiers listed below.
- AC/DC power supply unit PR-240, PR-300
- Rectifier unit RU-1746B-2, RU-3423, and RU-3424.
Important notices
The specifications of PR-241 have been changed to be compatible with DC bypass. The DC compatible unit has a white dot as shown in the figure below. Up to two units can be connected in parallel, the same as the previous specifications. However, the DC bypass compatible units cannot be connected in parallel with the DC bypass non-compatible units.
DC bypass non-compatible unit
DC bypass compatible unit
- Has a white dot.
The differences from the conventional PR-241 (DC bypass non-compatible units) are as shown in the table below.
| DC bypass non-compatible units| DC bypass compatible units
---|---|---
When the input from the AC power source is disconnected.| No power is supplied
from DC power source.| Power is automatically supplied from DC power source.
When DC power is turned ON while the power switch is turned OFF.| 24 VDC is
not output.| 24 VDC is output.
Standby power when no device is connected.| Not generated.| 4.8 W is
generated.
The following concern acts as our importer in Europe, as defined in DECISION
No 768/2008/EC.
– Name: FURUNO EUROPE B.V.
– Address: Ridderhaven 19B, 2984 BT Ridderkerk, The Netherland
The following concern acts as our importer in UK, as defined in SI 2016/1025
as amended SI 2019/470.
-Name: FURUNO (UK) LTD.
-Address: West Building Penner Road Havant Hampshire PO9 1QY, U.K.
Discard this product according to local regulations for the disposal of industrial waste. For disposal in the USA, see the homepage of the Electronics Industries Alliance (http://www.eiae.org/) for the correct method of disposal.
EQUIPMENT LIST
Standard Supply
Name
| Type| Code No.| Qty.| Remarks
---|---|---|---|---
AC/DC Power Supply unit| PR-241| –| 1|
Optional Supply
Name
| Type| Code No.| Qty.| Remarks
---|---|---|---|---
Ferrite Core| OP86-11| 001-594-450| 1| EMI Cores (GRFC-10, 7 pcs. and GRFC-13,
3 pcs)
SYSTEM CONFIGURATION
System configuration for single use
: Standard supply
: Optional or local supply
-
Backup Battery
(24 VDC) -
AC/DC Power Supply Unit
PR-241 -
Connected Equipment
(Up to 10 A)
System configuration for dual use
: Standard supply
: Optional or local supply
-
Backup Battery
(24 VDC) -
AC/DC Power Supply Unit
PR-241 -
Connected Equipment
(Up to 20 A)
1. MOUNTING
This unit can be mounted on a desktop or bulkhead. Refer to outline drawing in the back of this manual when you mount the unit.
When mounting the unit, pay attention to the following points.
- This unit has the following ingress-proof ratings: IP22 for desktop mounting, IP20 for wall mounting.
- When using in dual, do not input from multiple AC power supplies or batteries. Due to the difference in the load characteristics of the battery and the PR-241, it may not function as a power supply.
- When using in dual, do not stack the units. Always leave sufficient space between the units to allow for air-flow and prevent heat build-up. See the outline drawing at the back of this manual for minimum distances required.
- Turn off the power at the switchboard before beginning the installation.
- Referring to the outline drawings at the back of this manual, leave sufficient room for service and maintenance.
The mounting procedure is as follows:
-
Referring to the outline drawing at the back of this manual, make four pilot holes for self-tapping screws (4×16, local supply) in the mounting location.
-
Place the unit in a fixed position and align the screw holes.
-
Secure the unit by tightening the self-tapping screws.
-
Self-tapping screws (4×16, 4 pcs.)
2. WIRING FOR SINGLE USE
CAUTION
To prevent noise and interference, separate the AC IN, DC IN and DC OUT cables of this unit from connected equipment’s cables.
Fabrication
Use the following crimp-on lugs (local supply) and cables or equivalent (local supply) for connection with the power supply unit.
- Power cable: TPYC-1.5, DPYC-1.5
- Crimp-on lugs (see below figure): FV2-P4K
FV2-P4K (or equivalent)
Fabrication of TPYC-1.5
- Inner sheath
- Armor
- Pass the heat shrinkable tube (local supply) onto the drain wire.
- Drain wire
- Attach the crimp-on lug (FV2-P4K) to the core.
- Vinyl tape
Fabrication of DPYC-1.5
- Inner sheath
- Armor
- Vinyl tape
- Attach the crimp-on lug (FV2-P4K) to the core.
The procedure of the wiring is as follows;
1. Unfasten the screws on the terminal cover, then remove the cover. The screws and cover are required, do not discard them.
- Screws
- Terminal Cover
2. Unfasten the binding screws on the terminal and attach the fabricated following cables to the appropriate terminal.
- TPYC-1.5 (Power cable from ship’s main)
- DPYC-1.5 (Power cable from backup battery)
-
Binding screws
-
TPYC-1.5
(Cable from Ship’s main) -
DPYC-1.5
(Cable from Backup battery)
3. Attach the terminal cover to the unit and fasten the screws removed at step 2.
Note: The terminal cover also acts as protection against water damage and must be installed.
3. WIRING FOR DUAL USE
CAUTION
To prevent noise and interference, separate the AC IN, DC IN and DC OUT cables of this unit from connected equipment’s cables.
Fabrication
Use the following crimp-on lugs (local supply) and cables or equivalent (local supply) for connection with the power supply unit.
- Power cable: TPYC-1.5, DPYC-2.5
- Signal cable: TTYCSLA-1
- Crimp-on lugs (see below figure): FV2-P4K (for power cable), FV1.25-M3(LF) RED K (for signal cable)
FV2-P4K (or equivalent) FV1.25-M3(LF) RED K (or equivalent)
Fabrication of TPYC-1.5
Note: Attach the Ferrite cores as close as possible to the unit.
- Inner sheath
- Armor
- Pass the heat shrinkable tube (local supply) onto the drain wire.
- Drain wire
- Attach the crimp-on lug (FV2-P4K) to the core.
- Vinyl tape
- Attach the ferrite core (GRFC-10, optional supply)
- Attach with no wrapping.
Fabrication of DPYC-2.5
Note 1: Attach the Ferrite cores as close as possible to the unit
Note 2: For the DC OUT, attach the ferrite cores without wrapping the cable cores.
- Inner sheath
- Armor
- Vinyl tape
- Attach the crimp-on lug (FV2-P4K ) to the core.
- Attach the ferrite core (GRFC-13, optional supply)
- Wrap the cable cores around the ferrite core twice.
Fabrication of TTYCSLA-1
Note: Attach the Ferrite cores as close as possible to the unit.
- Inner sheath
- Armor
- Vinyl tape
- Attach the crimp-on lug (FV1.25-M3(LF) RED K) to the core.
- Attach the ferrite core. (GRFC-10, optional supply)
Installations for dual use, make the necessary connections with the following procedure.
- Refer to the step 1 on page 4, unfasten the screws on the terminal cover, then remove the cover. The screws and cover are required, do not discard them.
- Refer to the step 2 on page 5, unfasten the binding screws on the terminal and attach the fabricated following cables to the appropriate terminal.
• TPYC-1.5 (Power cable from ship’s main)
• DPYC-2.5 (Power cable from backup battery)
• TTYCSLA-1 (Signal cable between main and sub)
- Main
- Sub
- DC IN
- DC OUT
- Communication
- AC IN
- Current Share
The maximum length of the cable that connects between the main and sub is as shown in the table below.
Purpose
| Cable| Maximum Length|
Pattern of Cable
---|---|---|---
AC IN| TPYC-1.5| 90 cm|
DC IN| DPYC-2.5| 90 cm|
DC OUT| 50 cm
Current Share| TTYCSLA-1| 70 cm|
Communication| 20 m
Note 1: To prevent current imbalance, the input and output cables indicated in the below figures must be the same length and the difference in the resistance value of the cables must be 3 mΩ or less.
In the case the connected equipment is single
-
PR-241
(Main) -
PR-241
(Sub) -
Same Length
-
Connected Equipment
In the case the connected equipment is multiple
-
PR-241
(Main) -
PR-241
(Sub) -
Same Length
-
Terminal (Local supply)
-
Connected Equipment
: Output from the main
: Output from the sub
Note 2: When backing up power from the battery, signal cable connection is not required.
3. Attach the terminal cover to the unit and fasten the screws removed at step 2.
Note: The terminal cover also acts as protection against water damage and must be installed.
4. HOW TO USE THE UNIT
Use the power switch to turn this unit on.
- Power Switch
- LED
- Breaker
After turning on the power switch, the LED lights up as follows:
- AC is selected as the input: Green
- Battery is selected as the input: White
- No Input: OFF
Procedure in dual use
Note 1: Do not use the ID SW and Terminate SW of this unit when using this unit in dual.
Note 2: To avoid breaking the breaker, set the total current to 20A or less before starting the unit up.
The procedure in dual use is as follows:
Note: If you do not follow this procedure, the breaker may break.
- Turn on the main switch.
- Turn on the sub switch.
- Turn on the ship’s main switch.
Maintenance
- If the LED does not turn on when the power switch is turned on, contact your local dealer.
- If the breaker breaks, check the cause and take corrective action before resetting the breaker.
- If the breaker is cut off again after doing above, contact your local dealer.
5. JIS CABLE GUIDE
Cables listed in the manual are usually shown as Japanese Industrial Standard (JIS). Use the following guide to locate an equivalent cable locally.
JIS cable names may have up to 6 alphabetical characters, followed by a dash
and a numerical value (example: DPYC-2.5).
For core types D and T, the numerical designation indicates the cross-
sectional Area (mm2) of the core wire(s) in the cable.
For core types M and TT, the numerical designation indicates the number of
core wires in the cable.
1. Core Type
D: Double core power line
T: Triple core power line
M: Multi core
TT: Twisted pair communications (1Q=quad cable)
2. Insulation Type
P: Ethylene Propylene Rubber
3. Sheath Type
Y: PVC (Vinyl)
4. Armor Type
C: Steel
5. Sheath Type
Y: Anticorrosive vinyl sheath
6. Shielding Type
SLA: All cores in one shield, plastic tape w/aluminum tape
-SLA: Individually shielded cores, plastic tape w/aluminum tape
DPYCY TPYCY MPYC-4 TTYCSLA-4
a) Designation type
b) # of twisted pairs
c) # of cores
The following reference table lists gives the measurements of JIS cables commonly used with Furuno products:
Type
| Core| Cable Diameter
---|---|---
Area|
Diameter
DPYC-1.5| 1.5mm²| 1.56mm| 11.7mm
DPYC-2.5| 2.5mm²| 2.01mm| 12.8mm
DPYC-4| 4.0mm²| 2.55mm| 13.9mm
DPYC-6| 6.0mm²| 3.12mm| 15.2mm
DPYC-10| 10.0mm²| 4.05mm| 17.1mm
DPYCY-1.5| 1.5mm²| 1.56mm| 13.7mm
DPYCY-2.5| 2.5mm²| 2.01mm| 14.8mm
DPYCY-4| 4.0mm²| 2.55mm| 15.9mm
MPYC-2| 1.0mm²| 1.29mm| 10.0mm
MPYC-4| 1.0mm²| 1.29mm| 11.2mm
MPYC-7| 1.0mm²| 1.29mm| 13.2mm
MPYC-12| 1.0mm²| 1.29mm| 16.8mm
TPYC-1.5| 1.5mm²| 1.56mm| 12.5mm
TPYC-2.5| 2.5mm²| 2.01mm| 13.5mm
TPYC-4| 4.0mm²| 2.55mm| 14.7mm
TPYCY-1.5| 1.5mm²| 1.56mm| 14.5mm
TPYCY-2.5| 2.5mm²| 2.01mm| 15.5mm
TPYCY-4| 4.0mm²| 2.55mm| 16.9mm
TTYCSLA-1| 0.75mm²| 1.11mm| 9.4mm
TTYCSLA-1T| 0.75mm²| 1.11mm| 10.1mm
TTYCSLA-1Q| 0.75mm²| 1.11mm| 10.8mm
TTYCSLA-4| 0.75mm²| 1.11mm| 15.7mm
TTYCY-1| 0.75mm²| 1.11mm| 11.0mm
TTYCY-1T| 0.75mm²| 1.11mm| 11.7mm
TTYCY-1Q| 0.75mm²| 1.11mm| 12.6mm
TTYCY-4| 0.75mm²| 1.11mm| 17.7mm
TTYCY-4SLA| 0.75mm²| 1.11mm| 19.5mm
TTYCYSLA-1| 0.75mm²| 1.11mm| 11.2mm
TTYCYSLA-4| 0.75mm²| 1.11mm| 17.9mm
TTPYCSLA-1| 0.75mm²| 1.11mm| 9.2mm
TTPYCSLA-1T| 0.75mm²| 1.11mm| 9.8mm
TTPYCSLA-1Q| 0.75mm²| 1.11mm| 10.5mm
TTPYCSLA-4| 0.75mm²| 1.11mm| 15.3mm
PR-241
SPECIFICATIONS OF AC/DC POWER SUPPLY UNIT
PR-241
1 GENERAL
1.1 Rated input voltage 100-230 VAC, 1 phase, 50-60 Hz and 24 VDC
from backup battery
1.2 Input current under no-load 0.8 A max. (60 Hz), 1.0 A max. (50 Hz)
1.3 Rated output voltage 24 VDC±5%: 10 A max. (up to two units
connectable)
1.4 LED indication Input source status (AC: green, DC: white)
1.5 Protective circuit Over current for in/out and over voltage
for output
1.6 Switching backup battery Auto switching from relay
1.7 AC failure detection Relay contact: 1 A, 250 VAC
2 ENVIRONMENTAL CONDITIONS
2.1 Ambient temperature -15°C to +55°C (storage: -20°C to +70°C)
2.2 Relative humidity 93% or less at +40°C
2.3 Degree of protection IP22 (tabletop mount), IP20 (bulkhead mount)
2.4 Vibration IEC 60945 Ed.4
3 UNIT COLOR
N2.5
SP – 1
E5003S06B
201105
- FIXING HOLES
- SAFETY INSTRUCTIONS
- NAMEPLATE
- POWER TERMINAL
- GND TERMINAL
- CABLE ENTRY
- TERMINAL BOARD
- SEVICE CLEARANCE FOR BULKHEAD MOUNT
- AIR VENT
- CABLE
TABLE 1
(mm)
DIMENSION| (mm)
TOLRANCE
---|---
L ≤ 50| ±1.5
50 < L ≤ 100| ±2.5
100 < L ≤ 500| ±3
NOTE
- TABLE 1 INDICATES TOLERANCE OF DIMENSIONS WHICH IS NOT SPECIFIED.
-
: MINIMUM SERVICE CLEARANCE.
- USE ∅4×16 SCREWS FOR FIXING THE UNIT.
- *: HEAT RADIATING SPACE.
DRAWN
10/Sep/2020 T.YAMASAKI
| | | TITLE PR-241
---|---|---|---
CHECKED
10/Sep/2020 H.MAKI
| | | AC/DC
APPROVED
11/Sep/2020 H.MAKI
| | |
SCALE
1/3
|
MASS
±10%
2.8 kg
| | NAME AC/DC POWER SUPPLY UNIT (TABLETOP/BULKHEAD MOUNT)
DWG.No.
C5003-504- C
| REF.No.| OUTLINE DRAWING
FURUNO ELECTRIC CO., LTD.
NOTE
1: SHIPYARD SUPPLY.
2: EMI CORE GFRC-13 SHOULD BE PASS THE CORE TWICE.
DRAWN
26/Jan/2021 T.YAMASAKI
| | | TITLE PR-241
---|---|---|---
CHECKED
26/Jan/2021 H.MAKI
| | | AC/DC
APPROVED
28/May H.MAKI
| | |
SCALE|
MASS
kg
| | NAME
AC/DC POWER SUPPLY UNIT
DWG.No.
C5003-C01- A
| REF.No.| INTERCONNECTION DIAGRAM
FURUNO ELECTRIC CO., LTD.
FURUNO ELECTRIC CO., LTD.
9-52 Ashihara-cho, Nishinomiya, 662-8580, Japan
Tel: +81 (0)798 65-2111 Fax: +81 (0)798 63-1020
www.furuno.com
Publication No. DOCQA1515
Declaration of Conformity
We FURUNO ELECTRIC CO., LTD.
(Manufacturer)
9-52 Ashihara-Cho, Nishinomiya City, 662-8580, Hyogo, Japan
(Address)
declare under our sole responsibility that the product
AC/DC POWER SUPPLY UNIT PR-241
(Model name, type number)
to which this declaration relates conforms to the following standard(s) or other normative document(s)
EU
EMC Directive 2014/30/EU
IEC 60945 Ed.4.0: 2002
For assessment, see
- Test report
Labotech International Co., Ltd.
LIC 12-20-120 Rev.1, 22 Oct 2020
UK
SI 2016 No.1091 EMC Regulations 2016 as amended
EN 60945: 2002
For assessment, see
-
Test report
Labotech International Co., Ltd.
LIC 12-20-120 Rev.1, 22 Oct 2020 -
-
(title and/or number and date of issue of the standard(s) or other normative document(s))
On behalf of Furuno Electric Co., Ltd.
Nishinomiya City, Japan
26 July 2021
(Place and date of issue)
Akihiko Kanechika
Department General Manager
Quality Assurance Department
(name and signature or equivalent marking of authorized person)
Pub. No. C82-02001-B
(2312 TEHI) PR-241
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>