hidealite Moon Slim DALI Installation Guide

June 3, 2024
hidealite

hidealite Moon Slim DALI

hidealite-Moon-Slim-DALI-product

Moon Slim DALI

hidealite-Moon-Slim-DALI-fig-3hidealite-Moon-
Slim-DALI-fig-4

For explanation of symbols see www.hidealite.se

  • This product contains a light source of energy efficiency class D to Regulation (EU) No 2019/2015.

Accessories for Moon Slim DALI 320 & 380

hidealite-Moon-Slim-DALI-fig-6

SAFETY INSTRUCTIONS

  • Read these instructions carefully before commencing installation and retain for future reference. The luminaire should be installed by a licensed electrician and in accordance with local regulations. Make sure that the power is off before installation or maintenance.

Installation

hidealite-Moon-Slim-DALI-fig-8

NOTE! Only change when fixture is OFFhidealite-Moon-Slim-DALI-
fig-9

Installation Moon Slim DALI EM 320/380 and 320/380 with EM accessories

hidealite-Moon-Slim-DALI-fig-10

NOTE! Only change when fixture is OFFhidealite-Moon-Slim-DALI-
fig-11hidealite-Moon-Slim-DALI-fig-12hidealite-Moon-
Slim-DALI-fig-13

Suggestion

  • NOTE! Installation example, the emergency light module requires connection to neutral and constant current.

  • Connect battery
    When voltage is applied – the emergency light module starts self-test.

  • Flashing green light:
    Battery is charging/normal operation

  • Permanent green light:
    Battery fully charged/normal operationhidealite-Moon-Slim-DALI-
fig-16

Emergency light module performs automatic self-test every 30 and 180 days.

Manual self-test:

  1. Press and hold the test button for 1-5sec.
  2. LED of the emergency light module lights up.
    • Every 30 days – automatic self-test
    • Every 180 days – The LED of the emergency light module lights up for 1,5 hours for a complete battery and module test.

Troubleshooting

Flashing red light

  1. Check the connection cable between the battery and the module.
  2. Press and hold the test button for 10sec.
  3. The emergency light module resets and starts self-test.

Flashing / Permanent green:
Normal operation on module and battery

Flashing red light:

  • Battery not connected/Battery defective.
  • Replace battery – Press and hold the test button for 10sec.

Solid red light

  • Defective emergency light module
  • Replace emergency light module and battery

Factory reset:
For factory reset press and hold the test button for 15 sec.
NOTE: Automatic self-test cycle is reset.hidealite-Moon-Slim-DALI-