hidealite 1360959 Touch Panel TW DALI Instruction Manual
- June 1, 2024
- hidealite
Table of Contents
hidealite 1360959 Touch Panel TW DALI Instruction Manual
SAFETY INSTRUCTIONS
Read these instructions carefully before commencing installation and retain for future reference. All connections to the driver must only be made by a qualified electrician or a person with the necessary expertise in electrical installation in accordance with the relevant rules and standards. Make sure that the power is off before installation or maintenance.
E-nr | Snro | El.nr | GTIN | Name |
---|---|---|---|---|
13 609 59 | 26 061 02 | 14 368 69 | 7392971149424 | Touch panel TW DALI |
Dimension
Installation
- DO NOT install with power applied to device.
- DO NOT expose the device to moisture.
Power supply| Output| Operation current| DALI bus output| DALI consumption| Ta| Relative humidity| Dimensions| IP Class
---|---|---|---|---|---|---|---|---
100-240VAC/DALI bus| DALI signal| <15 mA| 100 mA max.| 4 mA| 0-40°C| 8% to 80%| 86x86x41mm| IP20 - Touch sensitive.
- Glass interface.
- Comply to DALI standard protocol IEC 62386-102, IEC 62386-207, IEC 62386-209 and in compliance with DALI products from other international incorporation
- Built-in 100mA DALI power supply to power up to max. 50 DALI ECGs.
- Powered by DALI bus while not connected to AC mains.
- Max. 100 DALI ECGs on a DALI line can be controlled by 4 control panels via broadcast (2 by AC mains, 2 by DALI bus).
- Enable to control 1 DALI Group and 4 DALI Scenes.
- Enable to set start DALI group number (0-15) and scene number (0-15) by rotary switches on the back.
- Support DT8 devices
- Color temperature adjustment according to DALI specifications of Device Type 8, Color Type Tc.
- Each DT8 device is controlled via a single DALI address
Operation
- Set starting Group number via rotary switch on the back: (0-15 selectable)
- This DALI touch panel controller enables dimming commands and DT8 commands to be sent to 1 Group of devices on the DALI circuit. A rotary switch on the back is used to select Groups you would like to control and set the starting Group number, and total 16 Groups (0-15) can be selected.
- When the rotary switch arrow position is at 0, the panel controls all DALI devices on the circuit via broadcast.
- When the rotary switch arrow position is at X except 0 (1-15), the panel controls DALI Group X-1.
Note: all DALI slaves on the circuit shall be assigned to one or more DALI groups by DALI master first.
Please refer to the detailed Group setting table as follows: Rotary Switch Position| 0| 1| 2| 3| 4| 5| 6| 7| 8| 9| A| B| C| D| E| F
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
DALI Group Selected| Broadcast| 0| 1| 2| 3| 4| 5| 6| 7| 8| 9| 10| 11| 12| 13| 14
- Set starting Scene number via rotary switch on the back: (0-15 selectable)
- This DALI touch panel controller enables Scene selection commands for up to 4 Scenes to be sent to the DALI circuit. A rotary switch on the back is used to select Scenes you would like to control and set the starting scene number, and total 16 Scenes (0-15) can be selected.
- When the rotary switch arrow position is at X (0-15), Scene button S1 controls Scene X, S2 controls Scene X+1, S3 controls Scene X+2, and S4 controls Scene X+3.
Please refer to the detailed Scene setting table as follows:
Rotary Switch Position | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | A | B | C | D | E | F |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Scene assigned to S1 | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 |
Scene assigned to S2 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 0 |
Scene assigned to S3 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 0 | 1 |
Scene assigned to S4 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 0 | 1 | 2 |
Figure 1: Wiring scheme to control up to 50 DALI ECG via broadcast or
control 1 DALI group.
Figure 2: Wiring scheme with 2 DALI panels powered by AC mains to control
up to 100 DALI ECG via broadcast or control 1 DALI group.
-
To control up to 100 ECG with the setup (Figure 2) , there are 2 panels connected to AC mains.
-
To control up to 50 ECG with the setup ( Figure 1 ), there is only 1 panel connected to AC mains. Other
panels are powered by DALI bus. Max. 2 DALI panels can be connected to AC mains in the same control circuit.
References
- Svenska institutet för standarder, SIS - Svenska institutet för standarder, SIS
- LED lighting of the highest quality - Hidealite
- Vi udvikler og sælger LED belysning - Hidealite
- LED-belysning, downlights, spotlights och utendørs belysning av topp kvalitet - Hidealite
- Hide-a-lite - LED-belysning & LED-armaturer för ditt projekt! - Hide-a-lite
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>