SAFETY INSTRUCTIONS

Read these instructions carefully before commencing installation and retain for future reference. All connections to the driver must only be made by a qualified electrician or a person with the necessary expertise in electrical installation in accordance with the relevant rules and standards. Make sure that the power is off before installation or maintenance.

E-nr Snro El.nr GTIN Name
13 609 59 26 061 02 14 368 69 7392971149424 Touch panel TW DALI

Dimension

  1. Dimension
  2. Dimension
  3. Dimension

Installation

  • DO NOT install with power applied to device.
  • DO NOT expose the device to moisture.
    Power supply| Output| Operation current| DALI bus output| DALI consumption| Ta| Relative humidity| Dimensions| IP Class
    ---|---|---|---|---|---|---|---|---
    100-240VAC/DALI bus| DALI signal| <15 mA| 100 mA max.| 4 mA| 0-40°C| 8% to 80%| 86x86x41mm| IP20
  • Touch sensitive.
  • Glass interface.
  • Comply to DALI standard protocol IEC 62386-102, IEC 62386-207, IEC 62386-209 and in compliance with DALI products from other international incorporation
  • Built-in 100mA DALI power supply to power up to max. 50 DALI ECGs.
  • Powered by DALI bus while not connected to AC mains.
  • Max. 100 DALI ECGs on a DALI line can be controlled by 4 control panels via broadcast (2 by AC mains, 2 by DALI bus).
  • Enable to control 1 DALI Group and 4 DALI Scenes.
  • Enable to set start DALI group number (0-15) and scene number (0-15) by rotary switches on the back.
  • Support DT8 devices
  • Color temperature adjustment according to DALI specifications of Device Type 8, Color Type Tc.
  • Each DT8 device is controlled via a single DALI address

Operation

  1. Set starting Group number via rotary switch on the back: (0-15 selectable)
    • This DALI touch panel controller enables dimming commands and DT8 commands to be sent to 1 Group of devices on the DALI circuit. A rotary switch on the back is used to select Groups you would like to control and set the starting Group number, and total 16 Groups (0-15) can be selected.
    • When the rotary switch arrow position is at 0, the panel controls all DALI devices on the circuit via broadcast.
    • When the rotary switch arrow position is at X except 0 (1-15), the panel controls DALI Group X-1.
      Note: all DALI slaves on the circuit shall be assigned to one or more DALI groups by DALI master first.
      Please refer to the detailed Group setting table as follows: Rotary Switch Position| 0| 1| 2| 3| 4| 5| 6| 7| 8| 9| A| B| C| D| E| F
      ---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
      DALI Group Selected| Broadcast| 0| 1| 2| 3| 4| 5| 6| 7| 8| 9| 10| 11| 12| 13| 14
  2. Set starting Scene number via rotary switch on the back: (0-15 selectable)
    • This DALI touch panel controller enables Scene selection commands for up to 4 Scenes to be sent to the DALI circuit. A rotary switch on the back is used to select Scenes you would like to control and set the starting scene number, and total 16 Scenes (0-15) can be selected.
    • When the rotary switch arrow position is at X (0-15), Scene button S1 controls Scene X, S2 controls Scene X+1, S3 controls Scene X+2, and S4 controls Scene X+3.
      Please refer to the detailed Scene setting table as follows:
Rotary Switch Position 0 1 2 3 4 5 6 7 8 9 A B C D E F
Scene assigned to S1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Scene assigned to S2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0
Scene assigned to S3 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1
Scene assigned to S4 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2

Figure 1: Wiring scheme to control up to 50 DALI ECG via broadcast or control 1 DALI group.
Connection
Figure 2: Wiring scheme with 2 DALI panels powered by AC mains to control up to 100 DALI ECG via broadcast or control 1 DALI group.
Connection

  1. To control up to 100 ECG with the setup (Figure 2) , there are 2 panels connected to AC mains.
    Connection

  2. To control up to 50 ECG with the setup ( Figure 1 ), there is only 1 panel connected to AC mains. Other
    panels are powered by DALI bus. Max. 2 DALI panels can be connected to AC mains in the same control circuit.