Beghelli 334900784 Pluraluce Extreme LED Emergency Instruction Manual
- June 11, 2024
- Beghelli
Table of Contents
Lungalargaluce Extreme AT
334900784 Pluraluce Extreme LED Emergency
For further information and updates, scan the QR code on the product
6m installation on the work surface| 6m installation on the work surface| 6m
installation on the work surface| 2m installation on the work surface| 2m
installation on the work surface
---|---|---|---|---
D Basic setting (1h-3h) without using App
Attention:
For the use of the device in ATEX environments, it is essential to apply the
ATEX-certified cable gland supplied
Connect the battery AFTER cutting the wire for autonomy selection
The selection of the autonomy of the lamp made by the App has priority over
the settings on the circuit.
SA lamp | SE lamp | REST MODE OPTIONAL |
---|---|---|
A= Test
C= Interuttore accensione lampada/ Light switch
| 230V 50Hz| COS | LED| |
---|---|---|---|---|---
19396 SE/SA| 180mA| 0,115| 4 LED| 1h 2h 3h 8h1,5h| 2x LiFe 6,4V 1,5Ah
For autonomy management refer to the table
*The selection of autonomy from the App has priority over cutting the jumper on the circuit.
By setting “Factory reset” on the App you go back to the setting made on the
circuit (1-3h).
available option
CONFIGURATION AND COMMANDS | senza APP without APP | con APP |
---|---|---|
__CONFIGURATION | Autonomia- Duration 1h | • Default |
Autonomia- Duration 1,5h | • | |
Autonomia- Duration 2h | • | |
Autonomia- Duration 3h | • con jumper | • |
Autonomia- Duration 8h | • |
Settaggio SE/SA (solo su lampade SA)
Setting Non-maintained/Maintained (only on Maintained Luminaire)| | •
Setting even/odd AT| • Preset by ID of QR code. Cannot be modified| •
Test duration 1h or autonomy set| • Test duration 1h| •
Manufacturer data reset| | •
COMMANDS NCTIO| Start/Stop functional Test| | •
Sync automatic Test| | •
__ Use with App B.connect
A- Open App B.connect (available for download on the App Store and Google
Play).
B- The “luminaire” menu is used to access the settings: Autonomy time, Mode,
Even/odd, Test duration, Sync luminaire, Factory reset.
Using the icon: Test emergency: functional Test; stop Test
LAMP RESPONSE:
1 high brightness flash= function performed
5 low light flashes= function NOT enabled
No flashing= command NOT received
POSITION LAMP FOR COVER ENSURE THE PROGRAM (eg. a lot of light – less
distance)OPTIONAL: to put the appliance in
“rest mode”, use the accessory (for the code, consult the sales force) and the
Inibit remote control (code 2730).
AUTOMATIC TESTS PERIODICITY:
FUNCTIONAL TEST (30 sec)= every 28 days
AUTONOMY TEST (1h)= every 26 weeks
Even lamps carry out the autonomy test 1 week after the odd lamps.
(0,2,…,8,A,C,E)= even; (1,3,…,9,B,D,F)= odd.
LED SIGNALS
FIXED GREEN | BATTERY CHARGED |
---|---|
FLASHING GREEN | BATTERY CHARGING |
ONE RED FLASH | BATTERY ERROR DURATION |
TWO RED FLASHES | LIGHTING LED ERROR |
THREE RED FLASHES | BATTERY DISCONNECTED |
OPENING THE COMMUNICATION FROM APP:
Remove and reset the network for less than 3 seconds.
The communication remains possible for 2 hours and for 1 min the LED flashes
orange to signal the communication opening. The Functional Test and the
Functional STOP Test are controlled by the B.Connect App at any time without
having to open communication with the device.
WARNINGS – GUARANTEE
- This device shall be used exclusively for the purpose for which it has been designed. Any other use is considered improper and therefore dangerous.
- Rechargeable battery and LED source are non-replaceable type. Contact an authorised technical service centre for any repairs possibly required use only original spare parts.
The lacked respect of the above conditions may compromise the safety of the
device.
* Caution:** electric shock
www.beghelli.com
BEGHELLI S.p.A.
Via Mozzeghine 13/15
località Monteveglio 40053 Valsamoggia (BO) ITALY
Tel. +39 051 9660411
Fax +39 051 9660444
N° Verde 800 626626