Metalux 24ARS-L3C3-NUV Achieva Selectable Troffer Owner’s Manual

June 11, 2024
METALUX

Metalux 24ARS-L3C3-NUV Achieva Selectable Troffer

24ARS-L3C3-NUV-Achieva-Selectable-Troffer-PRODUCT

Product Specifications

  • Brand: Metalux
  • Product Name: AchievaTM Selectable Center Basket
  • Size Options : 1×4, 2×2, 2×4
  • Certification: NUV (Canada Only)
  • Default CCT/Lumen Setting: 4000K / Med Power

Product Features

  • Selectable Lumens and CCT Troffer
  • WaveLinx LITE and WaveLinx PRO compatibility
  • Multiple ceiling compatibility options
  • Trim Type: Standard
  • Delivered Nominal Lumens range from 2766 to 6202
  • Efficacy ranges from 127 to 149 lm/W

Dimensions

  • 1′ x 4′: 1-1/2″ x 6-3/4″ x 11-3/4″
  • 2′ x 2′: 1-1/2″ x 6-3/4″ x 23-5/8″
  • 2′ x 4′: 1-1/2″ x 6-3/4″ x 23-5/8″

Project

| |

Catalog #

| |

Type

|
---|---|---|---|---|---

Prepared by

| |

Notes

| |

Date

|

SIZE

24ARS-L3C3-NUV-Achieva-Selectable-Troffer-FIG-16

Interactive Menu

  • Order Information/Performance page 2
  • Photometric Data page 3
  • Product Specifications page 4
  • Control Solutions page 5
  • Product Warranty

Top Product Features

  • Selectable lumens (low/medium/high) and selectable CCT (3500K/4000K/5000K) for use in a variety of applications and stock simplicity
  • Selectable lumens are offered in both standard selectable and high-output selectable options
  • Shallow plenum – 1.5” depth fits the most challenging spaces
  • 0-10V dimming to 5% standard with 120-347V NUV driver
  • Fully assembled driver integrated without exposed wires in the plenum.
  • Emergency, Wavelinx, and Flex options available
  • Integrated grid clips with holes for retaining wire and end hole to enable secure attachment to the grid where required

AchievaTM Selectable Center Basket NUV (Canada Only)
AchievaTM Selectable Lumens and CCT Troffer 1×4 / 2×2 / 2×4

Typical Applications

  • Offices
  • Education
  • Healthcare
  • Retail

Product Certification

Product Features

Achieva Dimensions

(Full Dimensions on Page

24ARS-L3C3-NUV-Achieva-Selectable-Troffer-FIG-3

Ceiling Compatibility

24ARS-L3C3-NUV-Achieva-Selectable-Troffer-
FIG-4

Achieva Ordering Information/Performance
Default CCT/Lumen Setting:
4000K / Med Power



Size

| ****


Catalog Number

| ****

Lumen Setting

| ****


CCT

| ****

CRI

(Min)

| Delivered Nominal Lumens| ****


Watts

| ****

Efficacy

(lm/W)

---|---|---|---|---|---|---|---







2×4

| ****






24ARS-L3C3-NUV

| ****


Low

| 3500K| 80| 3436| 24.6| 140
4000K| 80| 3581| 24.1| 149
5000K| 80| 3597| 24.9| 144


Medium

| 3500K| 80| 4610| 34.2| 134
4000K| 80| 4816| 33.2| 145
5000K| 80| 4749| 34.3| 138


High

| 3500K| 80| 5887| 45.9| 128
4000K| 80| 6202| 44.2| 140
5000K| 80| 6078| 46.3| 131







2×2

| ****






22ARS-L3C3-NUV

| ****

Low

| 3500K| 80| 2766| 20.5| 135
4000K| 80| 2859| 20.0| 142
5000K| 80| 2841| 20.7| 137


Medium

| 3500K| 80| 3578| 27.4| 130
4000K| 80| 3728| 26.5| 140
5000K| 80| 3648| 27.5| 133


High

| 3500K| 80| 4458| 35.0| 127
4000K| 80| 4721| 33.8| 140
5000K| 80| 4593| 35.5| 129







1×4

| ****






14ARS-L3C3-NUV

| ****

Low

| 3500K| 80| 2810| 20.3| 138
4000K| 80| 2910| 19.9| 146
5000K| 80| 2893| 20.5| 141


Medium

| 3500K| 80| 3657| 27.2| 134
4000K| 80| 3799| 26.4| 144
5000K| 80| 3733| 27.3| 136


High

| 3500K| 80| 4793| 35.2| 136
4000K| 80| 5036| 33.9| 148
5000K| 80| 4875| 35.4| 138

Achieva Options

Catalogue Description Example Notes
EL7W 7W EM Pack, Installed 22ARS-L3C3-UNV-EL7W Integrated Indicator/Test

Switch into the end cap
EL14W| 14W EM Pack, Installed| 24ARS-L3C3-UNV-EL14W| Integrated Indicator/Test Switch into the end cap


A3/8-5/18GDIM

| 6′ Length, 3/8″ Cable, 3 Wire, 3 Dimming Leads, Ground| ****

24ARS-L3C3-UNV-A3/8-5/18GDIM

|
EL7W-A3/8-5/18GDIM EL14W-A3/8-5/18GDIM| 7W/14W EM Pack, Installed, and 6′ Flex, 3/8″ Cable, 3 Wire, 2 Dimming Leads, Ground| 24ARS-L3C3–UNV- EL7W-A3/8-5/18GDIM

22ARS-L3C3–UNV-EL14W-A3/8-5/18GDIM

| EL7W and EL14W only use 5/18G flex with emergency. EM pack is always specified before (to the left of) the flex, in the catalog number.
WLS| WaveLinx LITE Wireless Integrated Sensor| 22ARS-L3C3-UNV-WLS| Sensor Integrated into the end cap
WPS| WaveLinx PRO Wireless Integrated Sensor| 24ARS-L3C3-UNV-WPS| Sensor Integrated into the end cap

Achieva Shipping Data



Size

| Fixture Net Weight| Fixture Gross Weight| ****


Fixture Dimension

| ****


Carton Dimension

| Fixtures per Carton| Pallet QTY

(Cartons)

| Pallet QTY

(Fixtures)

---|---|---|---|---|---|---|---
2′ x 2′| 6.8 lbs.| 9 lbs.| 23.7″ L x 1.8″ W x 23.7″ H| 25.7″ L x 2.8″ W x 26.2″ H| 1| 54| 54
2′ x 4′| 11.3 lbs.| 15.8 lbs.| 47.7″ L x 1.8″ W x 23.7″ H| 50.4″ L x 2.8″ W x 26″ H| 1| 27| 27
1′ x 4′| 7 lbs.| 10.2 lbs.| 47.7″ L x 1.8″ W x 11.7″ H| 50.4″ L x 2.8″ W x 15.2″ H| 1| 27| 27

Accessories

Accessories (order separately)

  • DF-14W-U= 1′ x 4′ Drywall Frame Kit
  • DF-22W-U= 2′ x 2′ Drywall Frame Kit
  • DF-24W-U= 2′ x 4′ Drywall Frame Kit
  • SK-22-WS= 2′ x 2′ Shallow Surface Mount Kit
  • SK-24-WS= 2′ x 4′ Shallow Surface Mount Kit
  • SK-14-WT=1 ‘ x 4’ Tall Surface Mount Kit
  • SK-22-WT= 2′ x 2′ Tall Surface Mount Kit
  • SK-24-WT= 2′ x 4′ Tall Surface Mount Kit

Photometric Data

14ARS-L3C3-NUV-4000K-HI Electronic Driver

  • Linear LED 4000K
  • Spacing criterion: (II) 1.26 x mounting height, (⊥) 1.28 x mounting height
  • Lumens: 5036
  • I nput Watts : 34W
  • Efficacy: 14 8.1 LPW
  • T est Report: 14ARS-L3C3-NUV-4000K-HI.IES

24ARS-L3C3-NUV-4000K-HI Electronic Driver

  • Linear LED 4000K
  • Spacing criterion: (II) 1.27 x mounting height, (⊥) 1.29 x mounting height
  • Lumens: 6202
  • Input Watts: 44.2W
  • Efficacy: 140.3 LPW
  • Test Report: 24ARS-L3C3-NUV-4000K-HI.IES

22ARS-L3C3-NUV-4000K-HI Electronic Driver

  • Linear LED 4000K
  • Spacing criterion: (II) 1.26 x mounting height, (⊥) 1.27 x mounting height
  • Lumens: 4721
  • Input Watts: 33.8W
  • Efficacy: 139.7 LPW
  • Test Report: 22ARS-L3C3-NUV-4000K-HI.IES

Product Specifications

Construction

  • Die formed of code gauge prime cold rolled steel in one-piece housing design
  • Four auxiliary fixture end suspension points
  • Integral-formed one-piece housing improves aesthetic design removing end plate light gaps
  • Integrated T-Grid clip design for screw installation to the grid where required by code and in “earthquake” zones

Integrated Controls

  • Standard 0-10V dimming driver down to 5%
  • Integrated WaveLinx options provide wireless individual fixture control and enable code compliance, increased energy savings, grouping of fixtures, and connection to the WaveLinx control system

LED and Light Engine

  • Selectable Color temperature choices 3500K, 4000K, and 5000K
  • Selectable lumen output up to 8000 lumens, with choices of low, medium, high
  • TM21 life at 60,000 hours up to L94 and calculated L70 exceeds 290,000 hrs.
  • Driver 120-347V Standard

Emergency Options

  • Optional emergency battery available in 7W and 14W
  • 90-minute backup period factory-installed
  • Factory installed integral test switch visible from the room side

Finish

  • Powder Coat matte white
  • 90% reflective, matte white enamel finish
  • Full fixture housing painted after fabrication

Shielding

  • Rounded ribbed frosted lens standard
  • Square ribbed frosted option coming Q1 (Consult Factory)

Compliance

  • IC rated for insulation contact
  • cULus listed for damp locations
  • RoHS compliant
  • Tested to IESNA LM-79 and LM-80
  • Stated life tested to TM21 standards
  • Can be used for the State of Cahigh-efficacye 24 high efficacy luminaire
  • Can be used for Non-residential T24
  • DesignLights Consortium® Qualified and classified for DLC Standard and DLC Premium (refer to www. designlights.org)

Limited Warranty

  • Five-year warranty standard. Optional ten-year war isranty available.

Dimensional and Mounting Details

24ARS-L3C3-NUV-Achieva-Selectable-Troffer-FIG-8 24ARS-L3C3-NUV-Achieva-Selectable-Troffer-FIG-9Control Solutions

  • WaveLinx LITE wireless
  • WaveLinx PRO wireless
  • WaveLinx CAT wired
  • WaveLinx Wired

Integrated Sensor Coverage Pattern

24ARS-L3C3-NUV-Achieva-Selectable-Troffer-FIG-10

Note : Installation of integrated sensors within 3-ft (1m) of HVAC air vents is not recommended. The pattern shown is intended solely as a general guide and is not to scale.

The ARS with WaveLinx offers no-hassle lighting control with multiple luminaire level control solutions.

WaveLinx PRO is a wireless lighting control solution, for connected spaces, that significantly reduces a building’s energy consumption. From a single floor to an entire campus, WaveLinx PRO connects more than lighting assets; it shares aggregated sensor data with the WaveLinx CORE platform and other building systems, so building owners can improve operations, space environment, and tenants’ experience. WaveLinx PRO offers a rich portfolio of wireless devices, WaveLinx PRO-enabled luminaires, and an intuitive WaveLinx mobile app for office, education, warehouse, and parking garage applications.

WaveLinx LITE is a cost-effective, wireless digital lighting control solution, with out-of-the-box functionality, that saves energy and meets code. It’s designed for applications that require occupancy-based, daylighting, or manual light control. Customize installations for office, education, warehouse and parking garages using the secure, simple mobile app.

Add a hidden WaveLinx sensor node (WPN, WLN) to your space lighting design!

Allows to:

  • Keeps luminaire aesthetics
  • Connect fixtures without the real estate to include sensor options such as downlights
  • Connect sealed fixtures without a standard sensor option such as products for clinical space.

Integrated Controls Options

Integrated Controls Options



Option

| ****

Out of the Box Functionality

| Luminaire Level Lighting Control (LLLC)| Automatic Dimming Photocell| ****

Occupancy Sensing

| ****

CCT

Control

WLS| X| X| X| X|
WLN| | X| | |
WPS| | X| X| X| X
WPN| | X| | | X

Note: WaveLinx utilizes scenes to allow users to change an area’s fixtures Correlated Color

  • Temperature (CCT) and intensity using commissioned manual wireless wallstation scene control.
  • To enable CCT adjustments through WaveLinx, include WPS or WPN devices in addition to VividTune or BioUp technologies for integrated fixture control.

Systems comparison chart

Cooper Lighting Solutions provides many lighting system solutions designed to satisfy code requirements and meet the unique needs of any project.

24ARS-L3C3-NUV-Achieva-Selectable-Troffer-FIG-15

Luminaire with

standalone

| Standalone

Spaces

| Standalone

Spaces

| Networked

Spaces

| Enterprise

WaveLinx

---|---|---|---|---
sensor| WaveLinx LITE| WaveLinx CAT| WaveLinx PRO| CORE
Occupancy ** Yes| Yes| Yes| Yes| Yes
Daylighting ** Yes| Yes| Yes| Yes| Yes
Wallstations ** –| Yes| Yes| Yes| Yes
Gateways ** –| –| –| 1 WAC| 300 WACs
Devices (MAX) ** –| 40 per Area (1120 per space)| 40 per Area| 200 per WAC2| 32,500 per CORE Enterprise
Software ** –| WaveLinx LITE Mobile App| WaveLinx CAT Mobile App| WaveLinx Mobile App| CORE
Areas ** –| 28 per Space| Unlimited| 50 per WAC2| up to 3,000
Zones ** –| 16 per Area| 16 per Area| 16 per Area| up to 9,000
Scheduling ** –| –| –| Local| Global
VividTune™ ** –| –| –| Yes| Yes
Plug-Load Control ** –| Yes| Yes| Yes| Yes
Low-Voltage Power –| –| Yes| Yes| Yes
Integration ** –| –| –| –| BACnet, API
Dashboards ** –| –| –| –| Energy, Occupancy
Configuration ** –| Installer| Installer| Technician| Technician / IT

Cooper Lighting Solutions
1121 Highway 74 South Peachtree City, GA 30269
P: 770-486-4800
www.cooperlighting.com

© 2024 Cooper Lighting Solutions
All Rights Reserved.
Specifications and dimensions are subject to change without notice.

FAQ

  • Q: What is the default CCT/Lumen setting for the Achieva Selectable Troffer?
    • A: The default CCT/Lumen setting is 4000K / Med Power.
  • Q: What are the dimensions and weights of the different size options?
    • A: The fixture dimensions and weights are as follows:
    • 1′ x 4′: Net Weight – 7 lbs, Gross Weight – 10.2 lbs
    • 2′ x 2′: Net Weight – 6.8 lbs, Gross Weight – 9 lbs
    • 2′ x 4′: Net Weight – 11.3 lbs, Gross Weight – 15.8 lbs

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

METALUX User Manuals

Related Manuals