NOVUS N1100 Universal Process Controller Instructions
- June 8, 2024
- Novus
Table of Contents
NOVUS N1100 Universal Process Controller
Features and specifications
Universal multi-sensor input without the need for hardware change or recalibration.
-
Outputs: 2 SPST relays, 1 SPDT relay (optional), linear 4-20 mA and up to 3 logic pulse outputs (2 optional).
-
The outputs can be configured as control, alarm and analog retransmission (4-20 mA).
-
Up to 2 timer relay alarms, settable from 0 to 6500 s, ideal for servo-positioning with up/down function.
-
Alarm functions: low, high, differential, low differential, high differential, sensor break, ramp and soak event, and inoperable.
-
PV or Setpoint 0-20 mA analog retransmission.
-
Auto/Manual “bumpless” transfer.
-
Up to 3 digital inputs with 5 programmable functions.
-
Sensor break protection in any condition.
-
4 to 20 mA Remote Setpoint input.
-
Programmable Soft Start (0 to 9999 seconds).
-
Ramp and Soak: Seven 7-segment profiles, can be linked to make longer programs of up to 49 segments.
-
RS-485 digital Communication, MODBUS RTU protocol, 19200 baud rate.
-
Heater break protection (option).
-
Up to 247 slave controllers in a network.
-
Auto tuning PID.
-
Consistent menu adapts to the installed options.
-
Unique electronic 8-digit serial number can be viewed at the display.
-
Silicone rubber keypad.
-
Front panel: IP65, Polycarbonate UL94 V-2.
-
Back panel: IP20, ABS+PC UL94 V-0.
Keypad protection prevents unauthorized parameters changes. -
Circuitry can be removed from the front panel.
-
Terminal connection: 18 screws accepting 6.3 mm fork lugs.
-
Accepts J, K, T, N, R, S thermocouples; Pt100, 4-20 mA, 0-50 mVdc, 0-5 Vdc.
-
Internal resolution: 32.767 levels.
-
Measuring resolution: 12000 levels.
-
Dual LED display: red 10 mm height PV upper display, green 8 mm height SV display.
-
Sampling rate: 5 per second.
-
Control output update: 200 Ms.
-
Isolated 4-20 mA output with 1500 level high resolution,550 Ohms maximum load.
-
2 SPST relays and 1 SPDT relay (optional) 3A @250 Vac.
-
Power supply: 85 to 250 Vac, 50/60 Hz; optionally 24 Vdc/ac.
-
Maximum consumption: 3 VA.
-
Ambient conditions: 0 to 55ºC, 20 to 95% RH
-
Dimensions: 48 x 48 x 110 mm.
-
Panel cutout: 45,5 x 45,5 mm.
-
Weight: 150 g.
Electrical Connections
How to Specify
The basic unit includes universal input, 2 SPST relays and one 4-20 mA output
that can be configured as logic pulse output or digital input.
Option 1: SPDT relay (for control or alarm output). Option 2: 2 Digital
I/Os. Option 3: Heater break detection. Option 4: RS-485 digital
communication.
Note: Options 1, 2 e 3 are exclude.
Accessory 1: Current transformer for heater break protection.
A factory manufacturing Calibration Certificate can be issued under request.
www.novusautomation.com/en/n1100
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>