APRVTIO ALD100 Halogen Refrigerant Leak Detector User Manual

June 4, 2024
APRVTIO

APRVTIO ALD100 Halogen Refrigerant Leak Detector

Automatic Circuit

When the unit is first powered on, it will set itself to ignore the current level of halogen in the atmosphere. This allows the unit to identify leaks by the higher concentration of halogen present at the leak location.

Specifications

  • Application: Rl2, R11, RS00, R22, Rl23, Rl24, R502, Rl34a, R404a, Rl25 refrigerants and blends such as HP62 and MP39.
  • Operating temperature: 0°C – 52°C (30°F- 125°F)
  • Maximum sensitivity: 3 g/yr., for all halogenated refrigerants
  • Battery life: approx. 50 hours of normal use
  • Response time: instant
  • Work mode: continuous, no limitations
  • Fixed probe length: 14 in
  • Direct dimension: 9 x 2.5 x 2.5 in
  • Power supply: 2C Alkaline batteries

Packing List

  • Leak detector x 1
  • Sensing tips x 2
  • Aluminum case x 1
  • Flexible probe x 1
  • C batteries x 2
  • User Manual x 1

Notes

  • Do not let children handle the product, keep them away from the working area.

  • Do not submerge the product in water.

  •  Do not expose the product to temperatures exceeding 60°C.

  •  Do not leave the product in direct sunlight belong periods of time.

  •  Do not dismantle or attempt repairs of the product without authorization.

  • Remove the batteries when not used for extended periods of time.

  •  Keep the sensing tip clean from dust, moisture and grease.

  • If dirty, clean the tip by immersing in mild solvent such as alcohol for
    several seconds then using compressed air or a towel to dry.

  • Do not use solvents such as gasoline, turpentine minerals etc. to clean the product.

  • Turn the tool off before replacing the sensing tip to avoid mild electric shock.

Main Features

  • Detect leaks in all NC refrigerant systems. Respond to all halogenated refrigerants.
  • 7 levels of sensitives
  • 18 alarm levels (Single color visual and audible)
  • Battery test function with voltage indication
  • Fast and easy reset function

Setup

  1. Turn on the device by pressing the ON button. The display will show the indication for 3 seconds.
  2. Ensure the battery level is good.
  3. The device will go to sensitivity level 5; A continuous beep tone will indicate the unit is normally functioning.
  4. Press the arrow up or down button to change the sensitivity.
  5.  Start searching the leaks. When a leak is located, the beep tone will change to a siren tone. Also, you will see the LED display the alarm.
  6.  During the use, the sensitivity can be adjusted at any time by pressing the arrow key.
  7.  If a full alarm is indicated before you have found the source of the leak, you can reset the detector to zero by pressing the reset key. This will allow you to find progressively greater concentrations, and eventually find the source of the leak.

Tips

  1. Adjust the sensitivity up only when a leak can be found. Adjust the sensitivity down only when resetting the unit does not allow you to locate the leak.
  2. In areas contaminated with leaked gas, reset the unit to zero it out and allow you to find heavier concentrations of gas. DO not move the probe while the unit is being reset.
  3. In windy areas, it may be difficult to find even a large leak. Shield potential leak sites from wind to make finding concentrations of leaked gas easier.
  4. The detector may alarm if the probe tip comes in contact with moisture or solvents .Do not allow the tip to contact these material.

Alarm Indications

The Electronic Refrigerant Leak Detector features 18 alarm levels from low to high to help you find the leak.

The alarm level will increase as the leak is being approached. Alarm levels are indicated by the last 6 LED’s lighting and changing in color from Red, Green and Orange. The LED’s will light and change color from left to right, one at a time. See alarm level chart below.

Battery Level Indicator

  • Green: good.
  • Orange: low.
  • Red: need to replace the battery

Reset Function/ Automatic Circuit

Reset
Press RESET key to reset the unit to zero.
LED will turn red for 2 seconds, this confirms the reset action completed.