prolink IPS3003 Pure Sine Wave Power Inverters User Guide
- June 5, 2024
- PROLiNK
Table of Contents
prolink IPS3003 Pure Sine Wave Power Inverters User Guide
SAFETY INSTRUCTIONS
- Before using the product, please read carefully the warning messages and instructions on labels and user manual of this 6 product and other components connected to the product.
- This product is designed to be connected with lead-acid battery only. Do not connect the product with other types of battery.
- To reduce risk of damage and injury, please use batteries with good quality.
- In the event flooded batteries are used, regular maintenance on the battery shall be performed.
- The product is design for indoor installation. Please do not expose the product to direct sunlight, rainfall, or snow.
- Before performing any maintenance on the product, please disconnect all power sources (AC mains, batteries) to avoid the risk of electrical I shock.
- Do not attempt to disassemble or repair the product. Only authorized personal are allowed to perform repair.
- While performing maintenance or cleaning (especially on the batteries where hazardous liquid might be touched), it’s recommended to wear necessary personal protections (e.g. gloves and goggle). The product and external batteries shall not be installed anywhere near smoke, spark, and flame.
- In the event a generator with auto-start function is connected with the product, before performing maintenance or cleaning I should disconnect it.
PRODUCT OVERVIEW
This is a DC-to-AC inverter, which can be used as a long run-time UPS (Uninterruptible Power Supply), an energy-saving solution or an automotive inverter (hereinafter referred to as “inverter”). The inverter accepts input power source from AC mains (utility), batteries and switches between various operation modes automatically depending on the operational conditions. When used as an UPS, battery acts as back-up power source to supply loads during the outage of AC mains. The battery can be charged by both AC mains with intelligent charging control.
Key features:
- Automatic line-to battery switchover
- Built-in enhanced AC charger
- High efficiency DC-to-AC conversion with minimized energy loss
- Rack design & wall-mounted design for flexible installation
- Intelligent 3-stage charger control for efficient charging and preventing overcharge
- Auto restart upon AC recovery
- User-friendly LCD and LED indications with setting function
- With the environmental temperature control charge management
- Multiple protections: low battery alarm, low battery shutdown, over charger protection, overload protection, over temperature protection, short circuit protection
PRODUCT OUTLOOK
Top panel
- LED indicators
- LCD
- Function buttons
Rear Panel
- DC input terminals
- AC input terminals
- AC output terminals
- AC input breaker
- Power on/off button
- RS-232 communication port
INSTALLATION
Unpacking and Inspection
This product package include following items. Please call your supplier or dealer if any items are missing.
-
1 X Inverter
1 X User’s manual -
2 X Setting screws
Safety Clearance
The minimum clearance to the wall shall be larger than 30cm in order to ensure
proper ventilation.
In the event the ambient temperature is high, it’s recommended to increase the distance of safety clearance to improve the heat dissipation.
Mounting Inverter on the wall
The inverter is designed to either be placed on horizontal surface or be
mounted on the wall with various ways (as shown below). When mounting the
inverter on the wall,
The wall shall be solid and strong enough to carry the inverter;
The location of installation shall allow the user to read the LCD easily;
Two screws shall be firstly fixed on the wall (distance as shown below) so
that the inverter can be hung on the screws, recommended screw size is
M4”50-65mm.
After mounting the inverter, make sure it’s firmly mounted and won’t easily
fall off in the event of unexpected earthquake or vibration.
Batteries
Determine the size of battery
The inverter is designed with pre-set charging current and voltage. Given a
fixed charging current, under-sized batteries may shorten the battery life
while over-sized batteries may result in unreasonable recharging time.
It’s recommended the batteries capacity shall be no less than 200AH.
Connect the battery cables
The gauge of battery cables shall be no less than 6 AWG with 105”C rating.
No matter how the batteries are connected (in series or in parallel), make
sure the cables’ terminal voltage is consistent with the inverter’s
specification (24V for 3000VA model and 48V for SOOOVA model).
It’s recommended to cover the battery terminals during the connection.
Check the polarity the cables before connecting to the inverter.
Connect the Inverter DC cables with battery terminals as shown below.
While connecting multiple batteries, use the same brand/type for all batteries. Do not mix the battery bank with different brand/type of batteries.
The user may connect the batteries in series in order to double the voltage connected to inverter. The diagram below illustrate how to connect two 12V batteries in series to make up 24V (for 3000VA model) and four 12V batteries in series to make up 48V (for 5000VA model)
Connect to Utility and charge Connect AC Input Cables and loads
Connect the AC input cables and loads to the receptacles as shown below. Plug in the AC input power cord to the wall outlet. The unit will automatically charge the connected external battery even though the unit is off.
AC input voltage range selector “NARROW “setting:
Configure LCD to “NARROW ” when connected with loads which are more sensitive on voltage range. With this setting. the inverter is more sensitive to the voltage disturbance on the AC input and input voltage range is set at 170-280VAC while output voltage follows input voltage.
“ WIDE “setting : Configure LCD to ‘WIDE when connected with loads which are less sensitive on voltage range (e. g. light bulb, fan, fluorescent tube, or TV). With this setting, the input voltage range is set at 90-280VAC while output voltage follows input voltage.
Please note that the inverter’s transfer time switching from Line Mode to Backup Mode gets longer as the input voltage gets low. Under the circumstance, connecting the inverter with loads which are sensitive to transfer time (e.g. computer) might result in power interruption.
OPERATION
After connecting batteries, AC input cables, and loads, the inverter is now ready to work.
Power on/off
Once the inverter has been properly installed, press the power switch to turn
on the unit. The unit will work automatically in line mode or inverter mode
according to input utility power’s status. When press the power switch again,
the unit will be turned off.
LED Indicators
The operation mode of the inverter can be easily understood by LED indicators.
Please see the table below for details.
LED indicators| Information|
---|---|---
| GREEN| Line mode 1 (Battery is empty)| Green flashing every 2 seconds|
Line mode 1 (Battery is full)| Green solid lighting|
Off-charge mode with AC| Green flashing as cycle:
0.5s On—.0.5s Off-00.5s On—*3.5s Off
|
| YELLOW| Battery mode Bat low| Yellow solid lighting Flashing every 2 second|
| BLUE| Not use| NA|
/
Not use| NA|
| RED| Overload| Red flashing every 0.5 second|
Fault| Red lighting|
Function Keys
Function key | Description |
---|---|
ESC | To exit setting mode |
UP | To go to previous selection |
DOWN | To go to next selection |
ENTER | To confirm the selection in setting mode or enter setting mode |
LCD Display
LCD displays the power flow and input/output readings in a visualized graphic design which allows the user to understand the operation status easily. The backlight of LCD remains on whenever the inverter is working (including Standby Charging Mode and Fault Mode).
Icon | Function |
---|
Input source information
| Indicates utility power
Configuration Program and Fault Information
| Indicates the setting
programs
| Indicates the warning and fault codes
| Indicates mute
| Indicates standby mode
| Indicates power on mode
Other Information
Battery Level
| Indicates battery level in battery mode and charging status
| Indicates the load level.
LCD Setting
When the power switch is turned on, pressing and holding “ENTER” button
immediately for 3 seconds, the unit will into the setting mode. Press “UP” or
“DOWN” button to select setting programs. And then, press “ENTER” button to
confirm the selection or “ESC” button to exit. The unit will exit setting mode
if no operating for 30s.
Function | LCD Display | Options | Default | Description |
---|---|---|---|---|
Buzzer enable | ON OFF ESC | Buzzer on | Buzzer is enable default, you can set |
it disable to turn off alarm sounding.
AC input voltage range| | Hi(wide) Lo(narrow) ESC| | If select Hi, AC input
voltage will be within 90-280VAC. If select Lo, AC input voltage will be
within 170-280VAC.
AC output voltage select|
| 220V 230V ESC| 230V|
Maximum AC charging current| | 10/20/30/40A ESC| NA| Depends
on the value of selection.
Auto restart voltage| | For 24V model:
Any/21.0/22.0/23.0/24. 0/25.0 /26.0/FUL .ESC For 48V model:
Any/42.0/44.0/46.0/48. 0/50.0 /52.0/FUL .ESC| Any| Utility power come back
after inverter shut down at battery low condition, the inverter will auto
restart if battery voltage is charging up to setting point.
Battery shutdown voltage setting| | Available options in 3000VA
model : 20.0/20.4/20.8/21.2/ 21.6/22.0V .ESC Available options in SOOOVA
model : 40.0/40.8/41.6/42.4/ 43.2/44.0V .ESC| 21.2V for 3000VA 42.4V for
SOOOVA
| Setting range is from 20.0V to 22.0V for 24V model and 40.0V to 44.0V for
48V model. Low cut-off voltage will be fixed to setting value no matter what
percentage of load is connected.
Battery model Energy -Saving setting| | No Yes| No| User can set Energy
-Saving model in this program to reduce the consumption in battery mode.
---|---|---|---|---
Initialize| | No Yes| No| If necessary, user can restore factory settings in
this program.
Operating Mode Description
Operating mode | LCD Display |
---|---|
Standby charging mode Battery can be charged without switching on the unit. |
Utility input bypass to output, and charge the battery.
Line mode| Utility input bypass to output, and battery can be charged when
switching on the unit
Battery mode| The backup power to load comes only from battery.
Fault and warning code
Alarm Code | Event | Audible Alarm |
---|---|---|
A56 | batlow | Beep 1 time in every 2 second |
A59 | bat open/disconnect | Beep 4 times every 10 seconds |
A62 | battery bad(less than 5V per unit) | NA |
A63 | energy saving | Beep 1 time in every 2 second |
A64 | Overload | Rapid beeping every 1/2 second |
A68 | High Temperature | Beep every second |
A69 | fan lock | Constant tone |
A92 | Inv Output Low | NA |
Fault Code | Event | Audible Alarm |
E05 | INV soft start fail | Constant tone |
E07 | INV volt high | Constant tone |
E08 | INV Volt low | Constant tone |
E09 | INV Short | Constant tone |
E13 | Over Charge | Constant tone |
E14 | Overload Fault | Constant tone |
E18 | Fan Fail | Constant tone |
E19 | Over temperature | Constant tone |
E26 | Reverse connection of mains input and | |
output | Constant tone |
TROUBLE SHOOTING
Problem | Possible Cause | Remedial Action |
---|---|---|
No LCD display | Battery voltage is low | Re-charge the battery and check if the |
battery cables are well-connected
Battery is defective| Replace the batteries
Power button is not pressed| Press and hold the power button
Mains are normal but works in backup mode| AC input is absent| Check the
connection of AC input
Backup time is short| Overloading| Disconnect non-critical loads
Battery voltage is too low| Re-charge battery for at least 8 hours
Battery is bad| Replace good quality batteries
Alarm buzzer beeps continuously| Inverter entered into fault mode| Refer to
the fault code to identify the fault and report to service representative for
further assistance
SPECIFICATION
Model | 3K | 5K |
---|---|---|
CAPACITY | VA/W | 3000VA/2400W |
NOMINAL BATTERY VOLTAGE | 24Vdc | 48Vdc |
LINE MODE
INPUT| Nominal Voltage| 220/230/240Vac
Voltage Range| Wide mode: 90VAC-280VAC(default) Narrow mode: 170VAC-280VAC
Normal Frequency| 50/60Hz
OUTPUT| Voltage| 220/230/240Vac
Frequency| Follow the Utility
Output Waveform| Follow the Utility
EFFICIENCY| >96%(full R load, battery full charged)
TRANSFER TIME| Wide mode: 40ms max, Narrow mode: 8ms max
BATTERY MODE
OUTPUT| Voltage| 220/230/240Vac
Frequency| 50/60Hz(Auto detection)
Output Waveform| Pure sine-wave
EFFICIENCY| >80%
OVERLOAD PROTECTION| 1min@ >110%, 0s@>120%
PROTECTION| Discharge, over-charged, over-load, short-circuit protection
BATTERY CHARGER(powered by AC)
CHARGING ALGORITHM| 3-stage charging
AC CHARGE CURRENT| 10/20/30/40A (selectable)
FLOATING CHARGING VOLTAGE| 27V| 54V
OVER CHARGING VOLTAGE| 32V| 64V
Physical
Total # of INVERTER Receptacles| (1) Terminal Block
Maximum Dimensions| 354mm(W) 380mm(H) 148mm(D)
Weight| 28.78kg| 31.88kg
Warning Diagnostics
Indicators| INVERTER Status Display,
Audible Alarms| Low Battery, Overload, Fault
Environmental
Operating Temperature| 0°C to 50°C
Operating Relative Humidity| 0 to 90% NON-CONDENSING
Management
Auto-Charger| Yes
Auto-Restart| Yes
DIPOSAL
In the event the product reaches the end of its service life, please contact the local dealer for disposal instructions.
The product must not be disposed of with the household waste.
Disposal of the product at the end of its service life shall be done in accordance with applicable regulations for electronic waste
Worldwide Customer Care Centers
INDONESIA Office
PT PROLiNK INTIDATA NUSANTARA
Walk-In : Jl. Cideng Barat No. 79, Jakarta Pusat 10150, Indonesia.
Telephone : +62 21 3483 1777
Sale Enquiries : sales.id@prolink2u.com
Technical Support :
support.id@prolink2u.com
MALAYSIA Office
FIDA SYSTEMS (M) SDN BHD
Walk-In : 29 Jalan USJ 1/31, 47600 Subang Jaya, Selangor Darul Ehsan,
Malaysia.
Telephone : +60 3 8024 9151
Sale Enquiries : sales.my@prolink2u.com
Technical Support :
support.my@prolink2u.com
SINGAPORE Office
FIDA INTERNATIONAL (S) PTE LTD
Walk-In : Block 16 Kallang Place #06-02, Kallang Basin Industrial Estate,
Singapore 339156.
Telephone : +65 6357 0668
Sale Enquiries : sales@prolink2u.com
Technical Support : support@prolink2u.com
Technical Support Hotline
INDONESIA : +62 21 3483 1717
MALAYSIA : +60 3 8023 9151
SINGAPORE : +65 6357 0666
Note: Closed on Saturdays, Sundays and local/regional Public Holidays.
Warranty Registration
Register online for your Product Warranty atwww.prolink2u.com
Prolink is a registered trademark of Fida International (S) Pte Ltd. Other brands and product names are trademarks or registered trademarks of their respective holders. Product images are purely for illustrative purposes and may defer from the actual product. Specifications are subjected to changes without prior notice. Copyright © 2022 Fida International (S) Pte Ltd.