ABH 2300-US28 Surface Magnetic Door Holder Instruction Manual

June 10, 2024
ABH

2300 ELECTROMAGNETIC DOOR HOLDER,
SURFACE WALL MOUNT

2300-US28 Surface Magnetic Door Holder

ABH 2300 US28 Surface Magnetic Door Holder - Product Overview
1

ELECTRICAL DATA:

THIS PRODUCT IS AN ELECTROMAGNETIC HOLDING DEVICE, INTENDED FOR USE IN FIRE DOOR APPLICATIONS, BUT CAN BE USED FOR OTHER MAGNETIC APPLICATIONS. WIRE INTO PROPER TERMINALS AS NOTED BELOW:

SERIES VOLTAGE DC/mA DC/VA AC/mA ACNA TERMINALS
2300 12 DC 60 .72 Com & 12 v
24 AC/DC 30 .72 30 .72 Corn & 24 v
120 AC 30 3.60 Corn & 120 v

ABH 2300 US28 Surface Magnetic Door Holder - Product Overview
4

SCREW DETAIL

| QTY| SCREW
MAGNETIC WALL PORTION| 2| 6-32 x 1″ OVAL HEAD MACHINE SCREW
MAGNETIC COVER| 2| 6-32 x 1″ FLAT HEAD MACHINE SCREW
DOOR ARMATURE| 2| 10-32 x 1′ PAN HEAD MACHINE SCREW
10-32 x 1-1/4″ SNB

WALL PORTION INSTALLATION:

  1. Measure distance from pivot centerline to wall (Dim. “A”).

  2. Determine door width (Dim. “B”).

  3. Use table below to locate magnet box on wall (Dim. “C”).
    a. Example : Dim. “A” = 10″ Dim. “B” = 42″ Result Dim. “C” = 39″.
    b. If Dim. “A” or Dim. “B” Falls between dimensions listed in the table below, allow for difference.
    Example : Dim. “A”= 7” Dim. “B” = 36″ Estimated Dim.”C” = 33-7/16″ \
    c. If Dim. “A” and Dim. “B” intersect in the shaded area, DO NOT INSTALL magnet box.
    The degree of door opening will not allow for proper alignment between armature and wall magnet.

  4. Suggested vertical location is on top rail approximately 5″ from top of the door.

  5. Check degree of door opening shown in table and coordinate with door closer and other door hardware.

  6. Total projection of door hardware must not be more than 5-5/8″ on the pull side of door.
    If greater, you will need to use additional extensions, sold separately.
    ABH 2300 US28 Surface Magnetic Door Holder - WALL PORTION INSTALLATION
2

  7. From corner of wall, measure the appropriate Dim. “C” determined in step 3.

  8. Proper electrical wire routing must be done before installing electrical box.

  9. The electrical box should be installed with reinforcement to withstand a minimum 50 Ib. pull.

  10. Before installing magnetic wall portion, consult ” ELECTRICAL DATA” on page 1.

IMPORTANT : Check that power voltage equals one of the voltages labeled on back of magnet.

DOOR ARMATURE INSTALLATION:

  1. Place and center the door armature on the surface of the magnet with the two holes of the base aligned horizontally.
  2. Gently close the door and adjust the angle of the door armature so the base lays flat against the door.
  3. While keeping slight pressure on the door, mark location of door armature through the two base holes.
  4. Drill through the door where the two marks are located with 5/16″ drill.
    Fasten armature with the (2)10-32 machine screws & sex bolts provided.

NOTE:

  1. All dimensions are provided in inches, unless noted otherwise.
  2. Additional extensions can be ordered separately to increase the door armature projection : 3/8″, 1/2″, 3/4″, 1″, 2″, 4″ or 6″.
  • For 2-5/8″ Door Projection, use 1″ Extension provided complimentary

www.abhmfg.com
E-mail: abhinfo@abhmfg.com
Architectural Builders Hardware Mfg., Inc.
1222 Ardmore Ave., Itasca, IL 60143
630.875.9900; FAX 800.9FAXABH (932.9224)

ABH is a minority
owned and operated
manufacturing company.
© 2015 ABH Mfg., Inc.
printed in USA
2300-2-04.DWG
2300
REVISED 07-09-15

Read User Manual Online (PDF format)