2300 ELECTROMAGNETIC DOOR HOLDER,
SURFACE WALL MOUNT
2300-US28 Surface Magnetic Door Holder
ELECTRICAL DATA:
THIS PRODUCT IS AN ELECTROMAGNETIC HOLDING DEVICE, INTENDED FOR USE IN FIRE DOOR APPLICATIONS, BUT CAN BE USED FOR OTHER MAGNETIC APPLICATIONS. WIRE INTO PROPER TERMINALS AS NOTED BELOW:
SERIES | VOLTAGE | DC/mA | DC/VA AC/mA | ACNA | TERMINALS |
---|---|---|---|---|---|
2300 | 12 DC | 60 | .72 | Com & 12 v | |
24 AC/DC | 30 | .72 | 30 | .72 | Corn & 24 v |
120 AC | 30 | 3.60 | Corn & 120 v |
SCREW DETAIL
| QTY| SCREW
MAGNETIC WALL PORTION| 2| 6-32 x 1″ OVAL HEAD MACHINE SCREW
MAGNETIC COVER| 2| 6-32 x 1″ FLAT HEAD MACHINE SCREW
DOOR ARMATURE| 2| 10-32 x 1′ PAN HEAD MACHINE SCREW
10-32 x 1-1/4″ SNB
WALL PORTION INSTALLATION:
-
Measure distance from pivot centerline to wall (Dim. “A”).
-
Determine door width (Dim. “B”).
-
Use table below to locate magnet box on wall (Dim. “C”).
a. Example : Dim. “A” = 10″ Dim. “B” = 42″ Result Dim. “C” = 39″.
b. If Dim. “A” or Dim. “B” Falls between dimensions listed in the table below, allow for difference.
Example : Dim. “A”= 7” Dim. “B” = 36″ Estimated Dim.”C” = 33-7/16″ \
c. If Dim. “A” and Dim. “B” intersect in the shaded area, DO NOT INSTALL magnet box.
The degree of door opening will not allow for proper alignment between armature and wall magnet. -
Suggested vertical location is on top rail approximately 5″ from top of the door.
-
Check degree of door opening shown in table and coordinate with door closer and other door hardware.
-
Total projection of door hardware must not be more than 5-5/8″ on the pull side of door.
If greater, you will need to use additional extensions, sold separately.
-
From corner of wall, measure the appropriate Dim. “C” determined in step 3.
-
Proper electrical wire routing must be done before installing electrical box.
-
The electrical box should be installed with reinforcement to withstand a minimum 50 Ib. pull.
-
Before installing magnetic wall portion, consult ” ELECTRICAL DATA” on page 1.
IMPORTANT : Check that power voltage equals one of the voltages labeled on back of magnet.
DOOR ARMATURE INSTALLATION:
- Place and center the door armature on the surface of the magnet with the two holes of the base aligned horizontally.
- Gently close the door and adjust the angle of the door armature so the base lays flat against the door.
- While keeping slight pressure on the door, mark location of door armature through the two base holes.
- Drill through the door where the two marks are located with 5/16″ drill.
Fasten armature with the (2)10-32 machine screws & sex bolts provided.
NOTE:
- All dimensions are provided in inches, unless noted otherwise.
- Additional extensions can be ordered separately to increase the door armature projection : 3/8″, 1/2″, 3/4″, 1″, 2″, 4″ or 6″.
- For 2-5/8″ Door Projection, use 1″ Extension provided complimentary
www.abhmfg.com
E-mail: abhinfo@abhmfg.com
Architectural Builders Hardware Mfg., Inc.
1222 Ardmore Ave., Itasca, IL 60143
630.875.9900; FAX 800.9FAXABH (932.9224)
ABH is a minority
owned and operated
manufacturing company.
© 2015 ABH Mfg., Inc.
printed in USA
2300-2-04.DWG
2300
REVISED 07-09-15
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>