HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed Light Instruction Manual

June 9, 2024
HEALTHCARE LIGHTING

HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed Light

HEALTHCARE-LIGHTING-HST-LED-Troffer-Flange-Surgical-Suite-Recessed-Light-
PRO

IMPORTANT SAFETY INSTRUCTIONS

READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION

  • To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and otherhazards please read all warnings and instructions included with and on the fixture box and all fixture labels.
  • Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions.
  • Installation and service of luminaires should be performed by a qualified licensed electrician.
  • Maintenance of the luminaires should be performed by person(s) familiar with the luminaires’ construction and operation and anyhazards involved. Regular fixture maintenance programs are recommended.
  • It will occasionally be necessary to clean the outside of the refractor/lens. Frequency of cleaning will depend on ambient dirt leveland minimum light output which is acceptable to user. Refractor/lens should be washed in a solution of warm water and anymild, non-abrasive household detergent, rinsed with clean water and wiped dry. Should optical assembly become dirty on theinside, wipe refractor/lens and clean in above manner, replacing damaged gaskets as necessary.
  • DO NOT INSTALL DAMAGED PRODUCT! This luminaire has been properly packed so that no parts should have been damagedduring transit. Inspect to confirm. Any part damaged or broken during or after assembly should be replaced.
  • If the lamp is marked (Hg) it contains Mercury. Follow all disposal laws. See www.lamprecycle.org.
  • These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meetin connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s or owner’s purposes, this matter should be referred to Acuity BrandsLighting, Inc.

WARNING
RISK OF ELECTRIC SHOCK

  • Disconnect or turn off power before installation or servicing.
  • Verify that supply voltage is correct by comparing it with the luminaire label information.
  • Make all electrical and grounded connections in accordance with the national electrical Code (NEC) and any applicable local code requirements.
  • All wiring connections should be capped with UL approved recognized wire connectors.

WARNING
RISK OF BURN

  • Allow lamp/fixture to cool before handling.Do not touch enclosure or light source.
  • Do not exceed maximum wattage marked luminaire label.
  • Follow all manufacturer’s warnings, recommendations, and restrictions for driver type, burning position, mounting locations/methods, replacement and recycling.

CAUTION
RISK OF INJURY

  • Wear gloves and safety glasses at all times when removing luminaire from cartons,installing, servicing or performing maintenance.
  • Avoid direct eye exposure to the light source while it is on.

CAUTION
RISK OF FIRE

  • Keep combustible and other materials thatcan burn, away from lamp/lens.
  • Do not operate in close proximity to persons,combustible materials or substancesaffected by heat or drying.

CAUTION: RISK OF PRODUCT

  • Never connect components under load.
  • Do not mount or support these fixtures in a manner that can cut the outer jacket or damage wire insulation.
  • Unless individual product specifications deem otherwise: Never connect an LED product directly to a dimmer packs, occupancy sensors, timing devices, or other related control devices. LED fixtures must be powered directly off a switched circuit.
  • Unless individual product specifications deem otherwise: Do not restrict fixture ventilation. Allow for some volume of airspace around fixture. Avoid covering LED fixtures with insulation, foam, or other material that will prevent convection or conduction cooling.
  • Unless individual product specifications deem otherwise: Do not exceed fixtures maximum ambient temperature.
  • Only use fixture in its intended location.
  • LED products are Polarity Sensitive. Ensure proper Polarity before installation.
  • Electrostatic Discharge (ESD): ESD can damage LED fixtures. Personal grounding equipment must be worn during all installation or servicing of the unit.
  • Do not touch individual electrical components as this can cause ESD, shorten lamp life, or alter performance.
  • Some components inside the fixture may not be serviceable. In the unlikely event, your unit may require service, stop using the unit immediately and contact an ABL representative for assistance.
  • Always read the fixtures complete installation instructions prior to installation for any additional fixture-specific warnings.

Please see product-specific installation instructions for additional warnings or any applicable FCC or other regulatory statements. Failure to follow any of these instructions could void product warranties.
For a complete listing of product Terms and Conditions, please visit www.acuitybrands.com.

Acuity Brands Lighting, Inc. assumes no responsibility for claims arising out of improper or careless installation or handling of its products.

HSTLED SINGLE FIXTURE INSTRUCTIONS

Fixtures come with two removable end flanges that are attached to fixtures with 8-32 nuts (Figure 1). For Row Mount and Row Mount Pattern these end flanges can be removed and replaced with mounting flanges to attach fixture together in desired shape.

Note hinge side of the fixture should be facing away from the bed.HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed
Light-img-33 \(33\)

Step 1
Cut rectangle in the ceiling for single fixture following Table 1 and Figure 2 below.HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed
Light-img-33 \(32\)

Step 2
Ensure end flanges of fixture are properly secured to housing with nuts before lifting into place. For ease of installation remove door by opening door perpendicular to housing, unscrew nuts holding safety cable to housing, then lift and remove from hinge. The fixture can be secured to plenum by two methods, threaded rod or suspension wire.

Threaded Rod

Step 1
Remove the four thumb nuts that retain side covers (Figure 3).HEALTHCARE
LIGHTING HST LED Troffer Flange Surgical Suite Recessed Light-img-33
\(31\)

Step 2
With side covers removed knock out the four 13/32” diameter knockouts at the four corners of the housing (Figure 4).
Step 3
Threaded rod up to 3/8” diameter may be used to hang fixture. Secure threaded rod to floor of fixture with a washer and nut on the inside and outside of the fixture floor (Figure 5). Tighten nuts against each other. Repeat in all four corners. Secure upper ends of threaded rods to building structure with suitable attachment means. For spacing between knockouts see Table 2 and Figure 6.HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed
Light-img-33 \(30\)

Step 4
With fixture secured to ceiling reinstall side covers and install door on housing hinge. Attach the two safety cables and one ground wire from the door to the housing before screwing door close.

Suspension Wire

Step 1
Knock out the eight (two in each corner) 0.25”x0.50” oblong knockouts. For spacing between knockouts see Table 3 and Figure 7.HEALTHCARE LIGHTING HST
LED Troffer Flange Surgical Suite Recessed Light-img-33
\(29\)

Step 2
Pass suitable sized wire through oblongs from the outside and return it though the adjacent oblong from the inside. Wrap the end of the wire around the supporting length to secure fixture to building support (Figure 8)HEALTHCARE
LIGHTING HST LED Troffer Flange Surgical Suite Recessed Light-img-33
\(28\)

Care should be taken to avoid trapping an electrical wire in the suspension wire loop inside the fixture

Step 3
With fixture secured to ceiling reinstall side covers and install door on housing hinge. Attach the two safety cables and one ground wire from the door to the housing before screwing door close.

Swing Arms
This fixture comes with four Swing Arms that can be used to level fixture. To bring the arms down screw clockwise from below using a flat head screw driver (Figure 9). The swing arm can travel roughly 1.25” to accommodate various ceiling support systems (Figure 10).
NOTE Swing Arms cannot be used with Plaster Frame Kit. Do not remove tape from swing arm.HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite
Recessed Light-img-33 \(27\)

HSTLED ROW MOUNT INSTRUCTIONS

STEP 1
Cut rectangle in ceiling for single fixture following Table 4 and Figure 11 below.HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed
Light-img-33 \(26\) HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite
Recessed Light-img-33 \(25\)

Step 2
For the first fixture in the row open the housing and carefully remove the reflector and door to allow for easier installation (Figure 3 Page 4). Remove one end flange and replace it with a row mount bracket as seen in Figure 12.HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed Light-
img-33 \(24\)

Step 3
Carefully mount fixture to ceiling using either threaded rod or suspension wire shown on Page 4 and 5.

Step 4
For the next fixture remove the door, reflector and both end flanges and attach one row mount bracket (Figure 13)HEALTHCARE LIGHTING HST LED Troffer
Flange Surgical Suite Recessed Light-img-33 \(23\)

Step 5
Carefully take the next fixture and mount it to the first fixture using 8-32 nuts (Figure 14). Repeat Step 3 for the second fixture.
The mounting bracket is not designed to support the weight of the fixture. Tie wire or threaded rods MUST BE USED to support the weight of the fixturesHEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed
Light-img-33 \(22\)

Step 6
Repeat Steps 4 and 5 for additional fixtures until the last one in the row then go to Step 7.

Step 7
For the last fixture in the row ensure only one end flange is installed (Figure 15)HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite
Recessed Light-img-33 \(21\)

Step 8
Carefully take the last fixture and mount it to the second to last fixture in the row using 8-32 nuts (Figure 16). Repeat Step 3 for the last fixture and install doors on fixtures.HEALTHCARE LIGHTING HST LED Troffer Flange
Surgical Suite Recessed Light-img-33 \(20\)

HSTLED ROW MOUNT PATTERN INSTRUCTIONS

Contact company for cutout dimensions in ceiling. HSTLED22 Cannot be side mounted (only end to end)*

Step 1
Place the first fixture on a flat and clear workspace with the door facing upwards towards the ceiling. Next remove the door and side covers following Figure 3 on Page 4.

Step 2
Remove one end flange and replace it with a row mount bracket as seen in Figure 12 on Page 7.

Step 3
Using a screw driver or other tool proceeded to punch out three of the knockouts labeled in Figure 17.HEALTHCARE LIGHTING HST LED Troffer Flange
Surgical Suite Recessed Light-img-33 \(19\)

Step 4
With the holes knocked out install the side mounting joiner using 8-32 nuts to secure it to the housing (Figure 18).HEALTHCARE LIGHTING HST LED Troffer
Flange Surgical Suite Recessed Light-img-33 \(18\)

Step 5
Carefully mount fixture to ceiling using either threaded rod or suspension wire shown on Page 4 and 5 (Figure 19).HEALTHCARE LIGHTING HST LED Troffer
Flange Surgical Suite Recessed Light-img-33 \(17\)

Step 6
Install next fixture end to end with first one following Steps 4 through 6 under Row Mount Instructions on Page 7 until next fixture is going to be installed in the corner.

Step 7
For the fixture at the corner there are two possible scenarios. Scenario 1 (Figure 20) has the next fixture mounted end to end while Scenario 2 (Figure 21) has the next fixture mounted end to side.HEALTHCARE LIGHTING HST LED
Troffer Flange Surgical Suite Recessed Light-img-33
\(16\)

Scenario 1

Step 1
Follow Step 7 on Page 8 and ensure one end flange is attached to fixture (Figure 15)

Step 2
Using a screw driver or other tool proceeded to punch out three of the knockouts labeled in Figure 22 and attach a side mount joiner scene in Step 4 on Page 8HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed
Light-img-33 \(15\)

Step 3
Mount fixture following Step 5 on page 8 to put fixture in corner. (Figure 14).

Step 4
Return to Step 6 on Page 10 and continue installing fixtures until next fixture is going in corner.

Scenario 2

Note the fixture before the corner a side mount bracket must be installed in fixture instead of a row mount bracketHEALTHCARE LIGHTING HST LED Troffer
Flange Surgical Suite Recessed Light-img-33 \(14\)

Step 1
Follow Step 2 on Page 7 and remove one end flange and replace it with a row mount bracket (Figure 12).

Step 2
Follow Step 3 on Page 9 and use a screw driver or other tool proceeded to punch out three of the knockouts (Figure 17).

Step 3
Carefully take the fixture and mount it using 8-32 nuts (Figure 24)HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed Light-
img-33 \(13\)

Step 5
Return to Step 6 on Page 10 and continue installing fixtures until next fixture is going in corner.

Step 6
With all fixtures mounted install doors and side covers on fixtures.

Plaster Frame Mounting Instructions

Note all Rails should have the pattern shown below. If not please contact factory HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed
Light-img-33 \(11\)

Before cutting ceiling ensure all components are accounted for. See Table 5 for quantities of components for a given fixture.

HSTLED PLASTER FRAME MOUNTING INSTRUCTIONS

Step 1
Cut rectangle in ceiling for single plaster frame following Table 6 and Figure 25.HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite Recessed Light-
img-33 \(9\)

Step 2
Begin by placing down the two end rails, two side rails, and four outer corner brackets seen in Figure 26. Each corner bracket is secured with four ¼-20 serrated hex nuts seen in Figure 27HEALTHCARE LIGHTING HST LED Troffer
Flange Surgical Suite Recessed Light-img-33 \(8\)

Step 3
With rectangle frame assembled slide top rail into groves shown in Figure 28 and secure top rail to frame with two ¼-20 serrated hex nuts per top rail (Figure 29).HEALTHCARE LIGHTING HST LED Troffer Flange Surgical Suite
Recessed Light-img-33 \(7\)

Step 4
Secure assembled frame to suitable building structural members using the holes provided in the top rails.

CAUTION: IT IS THE RESPONSIBILITY OF THE PERSON INSTALLING THE PLASTER FRAME TO ENSURE THAT THE MATERIALS, HARDWARE AND BUILDING STRUCTURAL MEMBERS THAT ARE SELECTED WILL SUPPORT THE LIGHT FIXTURE(S) AND THAT THEY MEET ALL APPLICABLE BUILDING AND SAFETY CODES

Step 5
With assembled frame secured follow the Threaded Rod instructions on Page 4 to secure fixture to plaster frame (Figure 30)HEALTHCARE LIGHTING HST LED
Troffer Flange Surgical Suite Recessed Light-img-33
\(6\)

Plaster Frame Row Mounting Instructions

Step 1
Cut rectangle in ceiling for row mount following Table 7 below.HEALTHCARE
LIGHTING HST LED Troffer Flange Surgical Suite Recessed Light-img-33
\(5\)

Step 2
Begin by placing down two end rails and two side rails per fixture in row shown in Figure 31 (3 HSTLED24). Each side rail is joined to the adjacent side rail with a joiner bracket and four ¼-20 serrated hex nuts seen in Figure 32. The four corner brackets are secured with four ¼-20 serrated hex nuts seen in Figure 27 on Page 13.HEALTHCARE LIGHTING HST LED Troffer Flange Surgical
Suite Recessed Light-img-33 \(4\)

Step 3
With rectangle frame assembled slide top rail into groves for each fixture shown in Figure 33 and secure top rail to frame with 2 ¼-20 serrated hex nuts per top rail (Figure 29 Page 13).HEALTHCARE LIGHTING HST LED Troffer Flange
Surgical Suite Recessed Light-img-33 \(3\)

Step 4
Secure assembled frame to suitable building structural members using the holes provided in the top rails.
CAUTION: IT IS THE RESPONSIBILITY OF THE PERSON INSTALLING THE PLASTER FRAME TO ENSURE THAT THE MATERIALS, HARDWARE AND BUILDING STRUCTURAL MEMBERS THAT ARE SELECTED WILL SUPPORT THE LIGHT FIXTURE(S) AND THAT THEY MEET ALL APPLICABLE BUILDING AND SAFETY CODES

Step 5
With assembled frame secured follow the Threaded Rod instructions on Page 4 and the Row Mount Instructions on Page 7.HEALTHCARE LIGHTING HST LED Troffer
Flange Surgical Suite Recessed Light-img-33 \(2\)

Kilmer Rd,
Edison,
NJ 08817 1-855-868-6980
www.healthcare-lighting.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HEALTHCARE LIGHTING User Manuals

Related Manuals