- AC Voltage: 600V rms maximum, 50 to 60Hz
- DC Voltage: 600V maximum
- Continuity Testing
- VolTect™ Non-contact Voltage Detection
- Flashlight
- DETAILED SPECIFICATIONS
- MAINTENANCE
- Caution – To prevent damage to the VPC-12:
- Cleaning
- Replacing the Battery
- Limited Warranty and Limitation of Liability
- Repair
- In-warranty Repairs and Replacement – All Countries
- Non-warranty Repairs and Replacement – United States and Canada
- Non-warranty Repairs and Replacement – Europe
- Read More About This Manual & Download PDF:
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
AMPROBE Voltage Continuity Tester VolTect Non-contact Voltage Detection
User Manual
VPC-12
Voltage & Continuity Tester
with VolTect™ Non-contact Voltage Detection
-
Positive DC voltage LED indicator
-
Negative DC voltage LED indicator
-
DC voltage range
-
AC voltage range
-
AC voltage LED indicator
-
Continuity LED indicator
-
Hazardous voltage LED indicator VPC-12 Voltage & Continuity Tester with VolTect™ Non-contact Voltage Detection
-
a Non-Contact voltage detection button
8b Voltect(TM) Non-Contact Voltage Sensor -
Flashlight button
-
Measuring probe (COM)
-
Measuring probe (+)
SYMBOLS
SAFETY INFORMATION
The meter complies with:
IEC/EN 61010-1 3rd Edition, UL61010-1 3rd Ed., CAN/CSA C22.2 No. 61010-1- 12 +
CAN/CSA C22.2 No. 61010-2-033 to CAT IV 600 V, pollution degree 2.
IEC/EN 61010-2-033 IEC/EN 61010-2-31 for test leads EMC IEC/EN 61326-1
This product has been tested to the requirements of CAN/CSA-C22.2No. 61010-1-12 third edition, or a later version of the same standard incorporating the same level of testing requirements
CENELEC Directives
The instruments conform to CENELEC Low-voltage directive 2014/35/EU and Electromagnetic compatibility directive 2014/30/EU
Warning
- To prevent possible electrical shock, fire, or personal injury:
- Carefully read all instructions. Read safety information before using or servicing the tester.
- Comply with local and national safety codes. Use personal protective equipment (approved rubber gloves, face protection, and flame retardant clothing) to prevent shock and arc blast injury where hazardous live conductors are exposed.
- In CAT III or CAT IV environments, use the test probes with the probe cap on. This decreases the exposed probe tip to reduce the possibility of arc flash from short circuits. When the probe cap off, the probe tip is 18 mm and rated to 1000V CAT II.
- Use the product only as specified, or the protection supplied by the product can be compromised.
- Do not work alone.
- Do not use the tester or test leads if they appear damaged. Examine the instrument and test leads for damaged insulation or exposed metal. Check test lead continuity.
- Do not touch voltages >30 V AC rms, 42 V AC peak, or 60 V DC. These voltages pose electrical shock hazards. Keep fingers behind the finger guard on the probe.
- To avoid false readings, which could lead to possible electric shock or personal injury, check the battery and verify operation on a known source prior to measuring hazardous voltages (voltages above 30 V AC rms, 42 V AC peak and 60 V DC).
- indicates hazardous voltage present if the LED turns on.
- Do not exceed the measurement category (CAT) rating of the lowest rated individual component of a product, probe, or accessory.
- If the tester is used in a manner not specified in the user manual, the protection provided by the equipment may be impaired.
- Measurements can be adversely affected by impedances of additional operating circuits connected in parallel or by transient currents.
- Disconnect the test leads from energized circuits and from the tester before replacing the battery.
- Do not use the tester with battery door removed.
- Do not use the instrument around explosive gas, vapor, or in damp or wet environments.
- For indoor use only.
UNPACKING AND INSPECTION
Your shipping carton should include:
1 VPC-12 Voltage & Continuity tester with VolTect™ non-contact voltage
detection
3 Batteries 1.5V IEC LR03 AAA
1 User manual If any of the items are damaged or missing, return the complete
package to the place of purchase for an exchange.
FEATURES
The Amprobe VPC-12 voltage and continuity tester is designed to be rugged and
easy to use for testing voltage and continuity. It offers seven different
voltage indicators clearly differentiating between key voltage levels and a
buzzer alert indicating the presence of dangerous voltages and continuity.
-
Check for voltage presence in receptacles, light fixtures or extension cords
-
Test continuity of fuses, light bulbs and electrical connections
-
Automatically selects AC voltage, DC voltage or continuity
-
LED lights indicate 7 levels of AC and DC voltages:
– V AC: 24, 120, 208, 240, 277, 480, 600
– V DC: 6, 12, 24, 36, 48,110, 220 -
Full range polarity detection
-
Continuity buzzer and visual continuity indication
-
Built-in VolTect™ non-contact voltage detection and flashlight
OPERATING THE TESTER
Warning
-
Do not use on a voltage source higher than AC 600 V and/or DC 600V between any terminal and earth ground.
-
Connecting test lead.
• Connect the common (COM) test lead to the circuit before connecting the live lead.
• After measuring, remove live lead before removing the common (COM) test lead from the circuit. -
Test on a known live source within the rated AC/DC voltage range of the instrument, both before and after use to ensure the instrument is in good working condition.
-
Indicates hazardous voltage levels if the LED turns on.
-
Do not touch voltages >30 V AC rms, 42 V AC peak, or 60 V DC. These voltages pose electrical shock hazards. Keep fingers behind the finger guard on the probe.
Automatic Operation
The tester automatically turns on when you place the probes across a complete circuit. The tester selects AC or DC voltage or continuity mode based on the resistance or voltage between the probes. The tester automatically turns off when you remove the probes from the circuit being measured.
Voltage Measurement
Connect test leads across the source or load to be measured. The LEDs turn on
at between 70% and 100% of their rated voltages.
Note: The maximum testing voltage of this product is 600Vac/220Vdc. It will
indicate 600Vac/220Vdc LED even if the testing voltage is greater than this
limit. In this case, users should beware of electric shock, and operate with
care or stop testing.
AC Voltage: 600V rms maximum, 50 to 60Hz
Figure 1: AC Voltage measurement
Figure 2: Check for voltage presence in electrical outlets
DC Voltage: 600V maximum
Figure 3: +DC voltage measurement
Figure 4: -DC voltage measurement
Continuity Testing
Disconnect circuit power and discharge all high-voltage capacitors before testing continuity. Short circuit=0-45kΩ
Figure 5: Continuity testing
VolTect™ Non-contact Voltage Detection
Press and hold down “NCV” button while placing the tester near AC voltages
within the specified voltage range. The tester will continually beep
and vibrate while AC voltage is detected.
Figure 6: Checking for the presence of AC voltage
Flashlight
Press to turn on the flashlight. Press again to switch it off.
DETAILED SPECIFICATIONS
LED voltage range| 24…600 VAC
6…220 VDC
---|---
LED indicator| AC volts: 24 V, 120 V, 208 V, 240 V, 277 V, 480 V, 600 V
DC volts: 6 V, 12 V, 24 V, 36 V, 48 V, 110 V, 220 V
Frequency range| 50 to 60 Hz
Acoustic and vibration indication| ³ 24 VAC, ³ 6 VDC
Tolerances LEDs| -30% to 0% of reading
Voltage detection| Automatic
Range detection| Automatic
Hazardous voltage indication| ³ 24 V AC, ³ 48 V DC
Polarity detection| Full range
Continuity range| 0 – 45 kW
Continuity tolerances| 0% to +50%
Continuity buzzer| 3 kHz
Continuity indication| LED, buzzer and vibration 0 – 45 kW ON; >85 kW
OFF
VolTect™ non-contact voltage detection| 90 – 600 VAC
Sensitivity: beeps and vibrates £ 10 mm (0.39 in) distance from a wire carrying 100 VAC.
Flashlight| Yes
Input impedance| 1 MW
Operating time| 30 seconds ON maximum and wait for 5 minutes before
making another measurement
Operating altitude| Up to 2000 m / 6561 feet
Operating temperature| 41 O F to 122 O F / 5 O C to 50 O
C
Storage conditions| -22 O F to 140 O F / -30 O C to 60 O
C
Humidity
(without condensation)
| £ 80% RH at 41 O F to 104 O F / 5 O C to 40 O C;
£ 50% RH at 104 O F to 122 O F / 40 O C to 50 O C
---|---
Pollution degree| 2
Power supply| Three 1.5 V batteries, AAA, LR03, UM4
Battery life| 40 hours (alkaline) (typical)
Dimensions (H x W x D)| 5.90 x 2.13 x 1.34 in
150 x 54 x 34 mm
Weight| Approximately 0.45 lb (205 g) with batteries installed
Electrical safety
| CAN/CSA-C22.2 No. 61010-1-12, UL Std. No. 61010-
1 (3rd Edition),
CAN/CSA-C22.2 No. 61010-031-07,UL 61010-031
(1st Edition – 2007),
CAN/CSA-C22.2 No. 61010-2-030-12, UL 61010-2-
030(1st Edition -2012)
Overvoltage category| CAT IV 600 V
EMC| Conforms to IEC 61326-1
Agency approvals| ) P
MAINTENANCE
Caution – To prevent damage to the VPC-12:
- Do not attempt to repair or service the VPC-12 unless qualified to do so.
- Make sure that the relevant calibration, performance tests, and service information is being utilized.
- Do not use abrasives or solvents.
Cleaning
The only maintenance the VPC-12 requires is inspection and cleaning. Periodically wipe the case with a mild solution of detergent and water. Apply sparingly with a soft cloth and allow time to dry completely before using. Do not use aromatic hydrocarbons, gasoline or chlorinated solvents for cleaning.
Replacing the Battery
Replace the batteries immediately if the continuity LED doesn’t turn on when touching both probes together.
Warning
- To avoid electric shock, disconnect the test leads from the source before opening the VPC-12 for battery replacement.
- To avoid false readings, which could lead to possible electric shock or personal injury, replace the battery as soon as the battery is low or dead.
The VPC-12 uses three 1.5V batteries. To replace the batteries, follow these
steps and refer to Figure 7:
- Disconnect test leads from any power source.
- Place the VPC-12 face down on a non-abrasive surface and loosen the battery-door screw with a Phillips screwdriver.
- Lift the battery cover away from the VPC-12.
- Replace the battery as shown in Figure 7. Observe the battery polarity shown in the battery compartment.
- Secure the battery cover back in position with the screw.
Limited Warranty and Limitation of Liability
Your Amprobe product will be free from defects in material and workmanship for
one year from the date of purchase unless local laws require otherwise. This
warranty does not cover fuses,
disposable batteries or damage from accident, neglect, misuse, alteration,
contamination, or abnormal conditions of operation or handling. Resellers are
not authorized to extend any other warranty on the behalf of Amprobe. To
obtain service during the warranty period, return the product with proof of
purchase to an authorized Amprobe Service Center or to an Amprobe
dealer or distributor. See Repair Section for details. THIS WARRANTY IS YOUR
ONLY REMEDY. ALL OTHER WARRANTIES – WHETHER EXPRESS, IMPLIED OR STATUTORY –
INCLUDING IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, ARE HEREBY DISCLAIMED. MANUFACTURER SHALL NOT BE LIABLE FOR
ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES, ARISING
FROM ANY CAUSE OR THEORY. Since some states or countries do not allow the
exclusion or limitation of an implied warranty or of incidental or
consequential damages, this limitation of liability may not apply to you.
Repair
All Amprobe tools returned for warranty or non-warranty repair or for
calibration should be accompanied by the following: your name, company’s name,
address, telephone number, and
proof of purchase. Additionally, please include a brief description of the
problem or the service requested and include the test leads with the meter.
Non-warranty repair or replacement
charges should be remitted in the form of a check, a money order, credit card
with expiration date, or a purchase order made payable to Amprobe.
In-warranty Repairs and Replacement – All Countries
Please read the warranty statement and check your battery before requesting
repair. During the warranty period, any defective test tool can be returned to
your Amprobe distributor for an
exchange for the same or like product. Please check the “Where to Buy” section
on amprobe.com for a list of distributors near you. Additionally, in the
United States and Canada,
in-warranty repair and replacement units can also be sent to an Amprobe
Service Center (see address below).
Non-warranty Repairs and Replacement – United States and Canada
Non-warranty repairs in the United States and Canada should be sent to an
Amprobe Service
Center. Call Amprobe or inquire at your point of purchase for current repair
and replacement rates.
USA: Canada:
Amprobe Amprobe
Everett, WA 98203 Mississauga, ON L4Z 1X9
Tel: 877-AMPROBE (267-7623) Tel:
905-890-7600
Non-warranty Repairs and Replacement – Europe
European non-warranty units can be replaced by your Amprobe distributor for a
nominal
charge. Please check the “Where to Buy” section on beha-amprobe.com for a list
of
distributors near you.
Beha-Amprobe
In den Engematten 14
79286 Glottertal, Germany
Tel.: +49 (0) 7684 8009 – 0
beha-amprobe.com
(Correspondence only – no repair or replacement available from this address. European customers please
contact your distributor.)
Read More About This Manual & Download PDF:
References
- Amprobe | Electrical Test and Measurement Tools
- Beha-Amprobe: The answer to all electronics, electrical and predictive maintenance questions
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>