ULINE Mobile Eyewash Station Instructions

June 7, 2024
ULINE

ULINE - logo

H-6224 MOBILE EYEWASH STATION

1-800-295-5510
uline.com

ULINE Mobile Eyewash Station

ULINE Mobile Eyewash Stationtank

SAFETY INFORMATION

  • Read instructions to ensure proper installation, then file with the owner or maintenance department. Compliance and conformity to drain requirements and other local codes and ordinances is the responsibility of the installer.
  •  Separate parts from packaging and make sure all parts are present before discarding any packaging. If any parts are missing, do not begin installation until you obtain the missing parts.
  •  Test the unit for leaks and adequate water flow. The inspection and testing results of this equipment should be recorded weekly to verify proper operation. This equipment should be inspected annually to ensure compliance with ANSI Z358.1.
  • Workers who come in contact with potentially hazardous materials should be trained regarding placement and proper operation of emergency equipment per ANSI Z358.1.
    This unit is to be used with tepid, potable water, as defined by ANSI Z358.1.
    NOTE: Avoid prolonged exposure to ambient heat sources above 100°F and below 60°F.

LOCATION AND INSTALLATION

MOUNT EYEWASH PEDESTAL TO WALL (OPTIONAL)

 CAUTION! Eyewash station weighs 60 lbs. when filled to capacity. Two-person installation is recommended to safely install the unit. Mounting bracket screws and wall anchors (not included) must be strong enough to support the filled unit.
1. Secure the mounting bracket to the wall with screws and wall anchors (not included).
2. Attach the pedestal to the mounting bracket by the handles on the back of the unit. (See Figure 1)
3. Check the condition of a gasket; ensure clamps are out of the way.

NOTE: When mounting the eyewash unit to the mounting bracket, make sure the unit is level and the spray heads are at a height of 33-53″ from the floor and situated at least 6″ from the wall or nearest obstruction (per ANSI Standard Z358.1-2014). (See Figure 1)

ULINE Mobile Eyewash Station figure 1

FILL AND MOUNT TANK

  1. Pour clean, potable, tepid water into the tank; continue pouring until the tank is 1/3 to 1/2 full.
  2.  Add water preservative (S-21107, sold separately) to the eyewash tank. Follow the manufacturer’s instructions for the proper use of water preservatives.
  3. Add clean, potable, tepid water to the tank until the water level reaches the fill line.
  4. Insert one-liner into the cap (with hole) and attach the cap to the top of the tank. (See Figure 2)

ULINE Mobile Eyewash Station figure 2

NOTE: To ensure proper installation, the tank should be placed on the pedestal from the front of the unit.
5. Invert the tank and place it on top of the pedestal. The piercing on the pedestal will puncture a hole in the cap liner and allow the solution to flow.
6. Raise the tray to snap fit in an upright position. A slight adjustment to the position of the tank may be required for proper level placement of the tank on the pedestal.
7. Secure the tank to the pedestal using the side tank clamps. Make sure the latches are pulled down tight to the pedestal. See diagram on page 1.
8. Lower the tray to activate the water flow. Allow the water to flow until air bubbles form in the tank. Raise the tray and snap closed in the upright position. The system is now ready for use.

NOTE: After the tank is mounted to the pedestal, minor spillage may occur. Allow the fluid to stabilize completely before inspecting the unit for leaks.

OPERATION

TEST EYEWASH UNIT

  1.  After completing the installation, test the eyewash station for proper operation by pulling down the tray. Check for proper water flow and quickly close the tray. Visually inspect the eyewash unit weekly for cleanliness and proper solution level (per ANSI Standard Z358.1-2014). When the water level drops below the 15-minute fill line, the tank must be emptied and then refilled. (See Figure 3)
  2. Attach the eyewash inspection tag (included) to the eyewash unit. This tag is to be used for weekly inspection documentation. Hook-and-loop fasteners are provided to attach the tag to the unit.
  3. If the eyewash unit is not working properly, remove it from the hazard area and contact Uline immediately.

ULINE Mobile Eyewash Station figure 3

OPERATE EYEWASH UNIT

  1. Pull down the tray.
  2.  Hold eyelids open with thumbs and forefingers. Rotate eyes back and forth to ensure a complete rinse.
  3. Allow water to bathe both eyes simultaneously for a minimum of 15 minutes.
  4. Seek medical attention immediately after use.

**CAUTION! Do not lean on the eyewash tray when in the opened position.

Damage to the unit may result.**

ULINE Mobile Eyewash Station figure 4

MAINTENACE

NOTE: Follow the preservative manufacturer’s instructions for the proper use of water preservatives.
INSPECT EYEWASH UNIT

  1. Visually inspect the eyewash unit weekly for cleanliness and proper solution level (per ANSI Standard Z358.1-2014).
  2.  Activate the eyewash unit each time the solution is replaced to ensure proper operation. If the unit is not working properly, remove it from the hazard area and contact Uline immediately.
    •Check the spray heads water spray pattern for an even, continuous flow. The spray heads are attached to the tray with screws and can be detached from the tray for cleaning or obstruction removal, if necessary, and reattached. Use a 9/64″ hex-head Allen wrench to remove and reinstall the spray heads.
    •Check the water supply hose at the basin of the eyewash unit for cracks, leaks, or wear.
    •Check the entire unit for possible water leakage.
    •Check the solution for contamination and replace it with a fresh solution, if necessary.

CLEAN EYEWASH UNIT
When using potable water and water preservative (recommended):

  1. Carefully remove the eyewash tank from the pedestal and drain the water solution from the tank (dispose of the solution properly).
  2.  Clean the inside of the tank using warm water and a mild soap product; rinse thoroughly.
  3. Refill the eyewash tank. Follow instructions of the preservative manufacturer for the proper use of water preservatives.
  4. Reinstall the eyewash tank.

When using potable water only:

  1.  Empty the tank any time from once per week to once per month, depending on the quality of your water supply. The manufacturer and Uline are not responsible for variations in the water supply.
  2. Clean the inside of the tank using warm water and mild soap. Rinse the tank thoroughly with warm water.
  3. Refill the eyewash tank with tepid, potable water.

1-800-295-5510
uline.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>