Honeywell W7220 JADE Economizer Module Installation Guide

June 7, 2024
Honeywell

W7220 JADE Economizer Module

JADETM Economizer Module
(MODEL W7220)

INSTALLATION INSTRUCTIONS

PRODUCT DESCRIPTION
The JADETM Economizer System is an expandable economizer control system, which includes a W7220 Economizer Module (controller) with an LCD and keypad. The W7220 can be configured with optional sensors.
The W7220 Economizer Module can be used as a standalone economizer module wired directly to a commercial set back space thermostat and sensors to provide Outdoor Air dry-bulb economizer control.
The W7220 Economizer Module can be connected to optional Sylk Bus sensors for single or differential enthalpy control. The W7220 Economizer Module provides power and communications on the Sylk Bus for the Sylk Bus sensors.

The W7220 Economizer Module automatically detects sensors by polling to determine which sensors are present. If a sensor loses communications after it has been detected, the W7220 Economizer indicates a device fail error on its LCD.
System Components
The JADETM Economizer System includes an Economizer Module, 20k mixed air sensor, damper actuator, an optional CO2 sensor, and either a 20k outdoor air temperature sensor or Sylk Bus sensors for measuring Outdoor Air and return air enthalpy, temperature, and humidity.
Economizer Module
This is the core of the JADETM Economizer System and includes the user interface for the system. The W7220 Economizer Module provides the basic inputs and outputs to provide simple economizer control. When used with the optional Sylk Bus sensors, the Economizer Module provides more advanced economizer functionality.
Sylk Bus Sensors (optional)
The Sylk Bus Sensor is a combination temperature and humidity sensor which is powered by and communicates on the Sylk Bus. Up to three sensors may be configured with the JADETM Economizer Module. See page 2 for details.
CO2 Sensor (optional)
A CO2 sensor can be added for Demand Control Ventilation (DCV). Either an analog (2-10 Vdc) or a wallmount Sylk bus TR40 CO2 sensor can be used with the Jade economizer.

Contents
Product Description …………………………………………………………. 1 Specifications ……………………………………………………………………. 2 Before Installation ……………………………………………………………. 3 Installation and Setup ……………………………………………………… 3 Mounting ……………………………………………………………………………. 3 Wiring ………………………………………………………………………………….. 4 Wiring Application Examples …………………………………………. 9 Interface Overview ……………………………………………………………. 18 Setup and Configuration …………………………………………………. 18 Checkout …………………………………………………………………………….. 31 Troubleshooting ………………………………………………………………… 32

63-2700-11

JADETM ECONOMIZER MODULE

PC MOD Tool (optional)
The PC MOD tool is connected to a personal computer and communicates with the Jade economizer controller via the Sylk bus. The W7220 PCMOD tool software is free and can be downloaded from the url in the Accessories section.
Some features on the Jade controller can only be enabled or disabled using the W7220 PC MOD tool. See the PC MOD tool options section in Table 5.

SPECIFICATIONS

W7220A Economizer Module
The module is designed for use with any Honeywell 2 to 10 Vdc or Honeywell Sylkbus communicating actuator. The module includes terminals for a CO2 sensor, Mixed Air sensor, and an Outdoor Dry Bulb sensor. Enthalpy and other options are available with Sylk Bus sensors.
User Interface: Provides status for normal operation, setup parameters, checkout tests, and alarms and error conditions with a 2-line 16 character LCD display and a four button keypad.
Electrical

Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz Transformer: 100 VA maximum system input

Nominal Power Consumption (at 24 Vac, 60 Hz): 11.5 VA without sensors or actuators

Relay Digital Output Rating at 30 Vac (maximum power from Class 2 input only): 1.5A run;
3.5A inrush @ 0.45PF (200,000 cycles) or 7.5A inrush @ 0.45PF (100,000 cycles)

External Sensors Power Output: 21 Vdc +/- 5% @ 48mA

IMPORTANT All inputs and outputs must be Class 2 wiring.

Inputs

SENSORS:

NOTE:

A Mixed Air (MA) analog sensor is required on all W7220 units; either an Outdoor Air (OA) sensor for dry bulb change over or an OA Sylkbus sensor for outdoor enthalpy change over is required in addition to the MA sensor. An additional Return

ORDERING INFORMATION

Air (RA) Sylkbus sensor can be added to the system for differential enthalpy or dry bulb changeover. For differential dry bulb changeover a 20k ohm sensor is required in the OA and a Sylkbus sensor in the RA. Dip switch on RA Sylkbus sensor must be set in the RA position.

Dry Bulb Temperature (optional) and Mixed Air (required), C7250A: 2-wire (18 to 22 AWG); Temperature range -40 to 150 °F (-40 to 65 °C). Temperature accuracy -0°F/+2°F

Temperature and Humidity, C7400S1000 (optional): Sylk Bus; 2-wire (18 to 22 AWG) Temperature: range -40 to 150 °F (-40 to 65 °C) Temperature accuracy -0°F/+2°F Humidity: range 0 to 100% RH with 5% accuracy.

NOTE:

Up to three (3) SYLK Bus sensors may be connected to the JADETM Economizer module. For outdoor air (OA), return air (RA) and discharge (supply) air (DA).

DCV (CO2) Sensor (C7232 or C7632): 2-10 Vdc control signal; minimum impedance

50k ohm.

4 Binary inputs: 1-wire 24 Vac + common GND (see page 6 for wiring details). 24 Vac power supply: 20 to 30 Vac 50/60Hz; 100 VA Class 2 transformer.

Outputs

Actuator signal: 2-10 Vdc; minimum actuator impedance is 2k ohm; Sylkbus two- wire output for Honeywell Sylkbus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O: All Relay Outputs (at 30 Vac):
Running: 1.5A maximum Inrush: 7.5A maximum
Environmental

Operating Temperature: -40 to 150 °F (-40 to 65 °C). Exception of display operation down to -4 °F with full recovery at -4 °F from exposure to -40 °F
Storage Temperature: -40 to 150 °F (-40 to 65 °C)
Shipping Temperature: -40 to 150 °F (-40 to 65 °C)
Relative Humidity: 5% to 95% RH non-condensing

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care 1985 Douglas Drive North Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.

63-2700–11

2

JADETM ECONOMIZER MODULE

Dimensions (See Fig. 1 on page 3): Height: 4.98 inches (126.4 mm) Width: 6.3 inches (160 mm) Depth: 1.34 inches (34 mm)
Weight: 0.58 lb. (0.265 kg) Approvals: UL listed (XAPX) for USA and Canada;
California Energy Commission (CEC) FDD ID number HJW10.
6-19/64 (160)
4-63/64 (126)

NOTE:

Jade will be in the “set up” mode for the first 60 minutes after powered. If a sensor for OA air or Sylkbus device (sensor, actuator) is disconnected during the set up mode, the Jade will not alarm that failure. The MA sensor is a system “critical” sensor, if the MA sensor is removed during the set up mode, the Jade will alarm. After 60 minutes the Jade controller will change to operation mode and all components removed or failed will alarm in the operation mode.

INSTALLATION AND SETUP
The following installation procedures should be performed in the order listed:
1. Mounting — see page 3. 2. Wiring — see page 4. 3. Interface and Programming overview ­ see page 18. 4. Setup and Configuration — see page 18 5. Checkout — see page 31.

MOUNTING HOLE (X2)

3-5/32 (80)

M32273A

Fig. 1. Dimensions in inches (mm) showing mounting holes.

Accessories
— 50048926-001 2-pin edge connector for sensors (20 pieces per bag)
— 50048926-002 6-pin edge connector for field wiring (20 pieces per bag)
— C7250A 20k sensor for MA or OA (dry bulb changeover)
— C7400S Sylkbus sensor for enthalpy control in OA and/or RA and RA for differential dry bulb changeover
— W7220 PCMOD interface tool for JADE controller and Personal Computer. For the software, go to www.customer.honeywell.com/economizertools
— 50053060-001 Duct mounting kit for sensors — C7632 or C7232 CO2 analog sensors OR one TR40
Sylk bus CO2 sensor

BEFORE INSTALLATION

Review the “Specifications” on page 2 before installing the The JADETM Economizer System.

When Installing This Product
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.

Troubleshooting and Alarms–see page 32.
MOUNTING
This section describes the mounting procedures for the JADETM Economizer module and the sensors.
Economizer Module Location and Mounting
IMPORTANT Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of the module’s circuit board, or in areas where escaping gas or other explosive vapors are present.
IMPORTANT The module must be mounted in a position that allows clearance for wiring, servicing, and removal.
Mount the Economizer module on any convenient interior location using the two mounting holes provided on the enclosure using #6 or #8 screws (screws are not provided and must be obtained separately). Use the dimensions in Fig. 1 on page 3 as a guide.
The Economizer module may be mounted in any orientation. However, mounting in the orientation shown in Fig. 1 on page 3 permits proper viewing of the LCD display and use of the keypad.
Sensor Location and Mounting
The JADETM Economizer W7220 uses digital and communicating sensors for control. The C7250 temperature sensors (MAa and OAb) are 20k NTC. A MA
a MA = Mixed Air b OA = Outdoor Air

3

63-2700–11

JADETM ECONOMIZER MODULE

sensor is required for all applications and is mounted in the mixed air section of a rooftop unit either directly to the sheet metal using self tapping sheet metal screws or in the air stream using the duct mounting kit. Duct mount kit is part number 50053060-001.
Optional OA, RAa and DAb Sylkbus sensors communicate with the W7220 on the two-wire communication bus and can either be wired using a two pin header or using a side connector. Each Sylkbus sensor includes a two pin side connector with the packaging. The SKU number of the Sylkbus sensor is C7400S. All OA, RA and DA sensors are the same SKU number. The sensor is set for the appropriate type of sensing using the three position DIP switch located on the sensor. OA position is OFF, OFF, OFF; RA is ON, OFF, OFF and DA is OFF, ON, OFF. During installation the sensors are set for the usage desired. See “Sylk Bus Sensor Wiring” on page 7 for DIP switch details.

NOTE:

The protective film on the dip switch is only necessary during the factory assembly process. Simply push through the film to set the dip switches; this will not harm the device.

Once installed, a sensor can be changed to a different application by simply changing the DIP switch setting.

Sensor Mounting
The sensors can be mounted directly on to the sheet metal of unit or can be mounted in the air stream using the duct mounting kit (order separately).

The kit contains a rod to hold the sensor in the duct, a flange to secure the sensor rod to the duct wall and fill the hole and a gasket to prevent air from leaking through the duct wall. There are five (5) kits in each bag assembly. See Fig. 2.

The rod has slots for threading the wire to prevent loose or hanging wire in the duct and can be adjusted for 6 to 12 inch length. The flange has extended relief for ease of mounting. See Fig. 3.

WIRE HOLDER

LENGTH ADJUSTS 6-12 INCHES

EXTENDED RELIEF (FOR CORRECT MOUNTING)

M32282A

Fig. 3. Duct Mounting Adjustments.

WIRING
All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. Module wiring in the field is terminated to the four screw terminal blocks located on the left and right sides.
Module wiring at the OEM factory is terminated via the header pin terminals located on the left and right sides. The header terminal pins and the terminal blocks have common terminations for the appropriate input or output. See OEM wiring diagram in Fig. 20.
The remainder of this section describes the wiring for the JADETM Economizer module, W7220A.

ROD – 1 PIECE

GASKET – 1 PIECE

FLANGE – 1 PIECE

M32281A

Fig. 2. Duct Mounting Kit (Part No. 50053060-001).

a RA = Return Air b DA = Discharge Air

WARNING
Electrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage.
CAUTION
Equipment Damage Hazard. Electrostatic discharge can short equipment circuitry. Ensure that you are properly grounded before handling the unit.

63-2700–11

4

JADETM ECONOMIZER MODULE

DISCHARGE AIR SENSOR
C7400S

TWO STAGE COOL PROGRAMMABLE THERMOSTAT

W7720A

C7250A
MIXED AIR SENSOR

1

C7400S

ENTHALPY SENSOR

DIRECT EXPANSION COIL

MS3103J MS3105J MS7505 ACTUATOR

OUTDOOR AIR

RETURN AIR

C7400S

1

ENTHALPY SENSOR

1 FOR DIFFERENTIAL ENTHALPY, THE TWO C7400S ENTHALPY SENSORS ARE CONNECTED TO THE W7720A ECONOMIZER CONTROL ONE IS MOUNTED IN RETURN AIR, AND THE OTHER IS MOUNTED IN OUTDOOR AIR. DIFFERENTIAL ENTHALPY CONTROL PROVIDES GREATER ENERGY SAVINGS THAN SINGLE ENTHALPY.
M35163

Fig. 4. Location of Outdoor Air, Return Air, Mixed Air, and Discharge Air Sensors in an economizer system.

5

63-2700–11

JADETM ECONOMIZER MODULE

Economizer Module Wiring Method
Wire the sensors and outputs, then wire the power connection.
Each terminal can accommodate the following gauges of wire: · Single wire ­ from 18 AWG to 22 AWG solid or stranded · Multiple wires ­ up to two 22 AWG stranded · For the 24 Vac connections: single wire ­ from 14 to 18
AWG solid or stranded · For S-BUS wiring, the sensors may be mounted up to
200 ft. (61 m) from the JADE controller. When the length of wire is over 100 feet use twisted pair shielded wire. · All sensor wiring to the Sylk bus and analog sensors is polarity insensitive.

Economizer Module Wiring Details
The wiring connection terminals for each module/sensor are: · “JADETM Economizer Module Wiring” on this page. · “Sylk Bus Sensor Wiring” on page 7.
JADETM Economizer Module Wiring
Use Fig. 6 and Tables 1 and 2 to locate the wiring terminals for the Economizer module.
NOTE: The four terminal blocks are removable. You can slide out each terminal block, wire it, and then slide it back into place.

Prepare wiring for the terminal blocks, as follows: 1. Remove the plastic tabs from the side of the controller where the connectors will slide onto the PWA. 2. Strip 1/2 in. (13 mm) insulation from the conductor. 3. Cut a single wire to 3/16 in. (5 mm). Insert the wire in the required terminal location and tighten the screw.
4. If two or more wires are being inserted into one terminal location, twist the wires together a minimum of three turns before inserting them to ensure proper electrical contact. See Fig. 5 on page 6.
5. Cut the twisted end of the wires to 3/16 in. (5 mm) before inserting them into the terminal and tightening the screw.
6. Pull on each wire in all terminals to check for good mechanical connection.

1. STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.

1/2 (13)

2. TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).

3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION. M24382A
Fig. 5. Attaching two or more wires at terminal blocks.

JADE CONTROLLER
AUX2-I AUX1-O

AUX2-I OCC
E-GND EXH1 AUX1-O
Y2-I Y2-O Y1-I Y1-O
C R

LEFT TERMINAL BLOCK LABEL

RIGHT TERMINAL BLOCK LABEL
M32283C

Fig. 6. W7220 Economizer module terminal connection labels.

Table 1. Economizer Module – Left hand terminal blocks.

Label

Type

Description

Top Left Terminal Block

MAT MAT

20k NTC Mixed Air Temperature Sensor

and

(polarity insensitive connection)

COM

OAT

20k NTC Outdoor Air Temperature Sensor

OAT

and

(polarity insensitive connection)

COM

S-BUS S-BUS

SYLK Bus Sylk Bus sensor (polarity insensitive connection)

Bottom Left Terminal Block

IAQ 2-10 2-10 Vdc Air Quality Sensor Input (e.g. CO2 sensor)

IAQ COM COM

Air Quality Sensor Common

IAQ 24V 24 Vac Air Quality Sensor 24 Vac Source

ACT 2-10 2-10 Vdc Damper Actuator Output (2-10 Vdc)

ACT COM COM

Damper Actuator Output Common

ACT 24V 24 Vac Damper Actuator 24 Vac Source

n/a

The bottom pin is not used.

63-2700–11

6

JADETM ECONOMIZER MODULE

Table 2. Economizer Module – Right hand terminal blocks.

Label
AUX2 I
OCC E-GND EXH1 AUX1 O
Y2-I Y2-O Y1-I Y1-O C R

Type

Description

Top Right Terminal Block

n/a

The first pin is not used

24 Vac IN

Shut Down (SD) or Heat (W) Conventional only or Heat Pump Changeover (O/B) in Heat Pump mode.

24 Vac IN Occupied / Unoccupied Input

EGND

Earth Ground – System Required

24 Vac OUT Exhaust Fan 1 Output

24 Vac OUT Programmable: Exhaust fan 2 output or ERV or System Alarm output.

Bottom Right Terminal Block

24 Vac IN Y2 in – Cooling Stage 2 Input from space thermostat

24 Vac OUT Y2 out – Cooling Stage 2 Output to stage 2 mechanical cooling

24 Vac IN Y1 in – Cooling Stage 1 Input from space thermostat

24 Vac OUT Y1 out – Cooling Stage 1 Output to stage 1 mechanical cooling

COM

24 Vac Common

24 Vac

24 Vac Power (Hot)

Sylk Bus Sensor Wiring
The labels on the sensors and controller are color coded for ease of installation. Orange labeled sensors can only be wired to orange terminals on the controller. Brown labeled sensors can only be wired to S-bus (brown) terminals. Use Fig. 7 and Table 3 to locate the wiring terminals for each Sylk Bus sensor.
Use Fig. 7 and Table 4 to set the DIP switches for the desired use of the sensor.

DIP SWITCH LABEL
DIP SWITCHES (3)

SYLK BUS TERMINALS (1 AND 2)

SYLK BUS 2 PIN SIDE CONNECTOR
M32271B

Fig. 7. Sylk Bus sensor DIP switches.

Table 3. SYLK Bus Sensor Wiring Terminations.

Terminal

Nbr Label Type

1

S-BUS SYLK

Bus

2

S-BUS SYLK

Bus

Description
Sylk Bus Communications (Sensor Bus) polarity insensitive
Sylk Bus Communications (Sensor Bus) polarity insensitive

Table 4. SYLK Bus Sensor DIP Switch Settings.

DIP Switch Positions for Switches 1, 2, & 3

Use

1

2

3

DAa

OFF

ON

OFF

RAb

ON

OFF

OFF

OAc

OFF

OFF

OFF

a DA = Discharge Air b RA = Return Air c OA = Outdoor Air

NOTE:

When using the Sylkbus sensors there will be a slight delay while the Jade controller and the sensor communicate. Analog sensors do not communicate on the Sylkbus and output a 20k ohm signal to the Jade controller so the response time is instantaneous.

NOTE:

When using the C7400S (Sylk bus enthalpy) sensor there is an operation that will allow test of the operation of the W7220 economizer when the outdoor air conditions (temperature and humidity) are too high for economizing.

7

63-2700–11

JADETM ECONOMIZER MODULE

1. Remove the C7250A dry bulb sensor from the OAT terminals IF you are using temperature only economizing change over.
2. If you are using enthalpy change over and have a C7400S sensor with a date code prior to 1301, remove the sensor and replace it with one with a date code after 1301.
3. Connect a C7400S Sylk bus sensor to the S-Bus terminals (brown colored) on the W7220A Jade using 18 AWG to 22 AWG solid or stranded wires.
4. Check the STATUS screen for actual outdoor air (OA) temperature and OA humidity readings.
5. Change the 3-position DIP switch on the C7400S sensor from 1 OFF, 2 OFF, 3 OFF to 1 ON, 2 ON, 3 ON position and immediately back to 1 OFF, 2 OFF 3 OFF position.
6. The output of the C7400S sensor to the W7220A will be 40 ºF and 40 %RH which will allow the economizer to go into free cooling mode (economizing available).
7. Make sure you have 24 Vac on terminal Y1 In to simulate a call for cooling.
8. After 15 minutes the C7400S sensor will change back to the actual OA temperature and humidity.
NOTE: If you removed a dry bulb sensor, remove the C7400S from the S-bus terminals and replace the OAT sensor onto the OAT terminals.

Actuator Wiring Options:
1. The JADE economizer controller can only have one (1) communicating actuator connected to it.
2. Up to four (4) non-communicating and two (2) 2position actuators (1 each on EXH1 and AUX1 O)
3. One (1) communicating and up to four (4) non-communicating and two (2) 2-position actuators (1 each on EXH1 and AUX1 O). When using a 2-position actuator on the AUX1 O, the AUX1 O must be programmed for Exh2 and the % open is the % open of the outdoor damper when the 2-pos actuator opens. Connect 24 V to Exh1 and/or AUX1 O and ground to the Jade “C” terminal.

CO2 Sensor Wiring
When using the C7232 Honeywell CO2 sensors the black and brown common wires are internally connected and only one is connected to “IAQ COM” on the Jade. Use the power from the Jade to power the CO2 sensor OR make sure the ground for the power supplies are common. See wiring diagram below for the C7232 and C7632 wiring diagrams.

NOTE:

When using the C7632 (or any 0-10 Vdc CO2 sensor) with the Jade you will need to set the CO2ZERO to 400 ppm and the CO2SPAN to 1600 ppm in the ADVANCED SETUP menu.

NOTE:

When using the TR40 CO2 sensor set the address on the TR40-CO2 to 6. Only one TR40 CO2 sensor can be used with the Jade economizer controller. Address 6 is for a CO2 sensor, address 11 is for a communicating actuator.

C7232 24V

RED BLACK

+ ANALOG
OUT ­

YELLOW BROWN
ORANGE GREEN

L1 (HOT) L2
1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M17543B

Fig. 8. Wiring for C7232

C7632

L1 (HOT)
L2 1

0-10 VDC
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M34095
Fig. 9. Wiring for C7632

63-2700–11

8

JADETM ECONOMIZER MODULE
WIRING APPLICATION EXAMPLES
This section shows the wiring configurations for the JADETM Economizer system.
Stand-alone Economizer
The most basic configuration is the stand-alone Economizer (see Fig. 10 and Fig. 15). A stand-alone Economizer is directly wired to sensors, actuators, thermostat, and mechanical cooling controls in the roof top unit. It does not require Sylk Bus communications.

MA TEMP SENSOR 20K NTC

MA

MA

1 OA TEMP

OAT

SENSOR

OAT

20K NTC

W7220 ECONOMIZER CONTROLLER MODULE

ROOF TOP UNIT

O/B

Y1

W1

G

OCC

Y2

W2

3 1K1 AUX2-I
OCC E-GND

AUX1-0

CO2 SENSOR 2-10 VDC (OPTIONAL)

IAQ (2-10V) IAQ COM IAQ 24V
ACT (2-10V) ACT COM ACT 24V

Y2I
Y2O Y1I Y1O C R

TR TR1
IN +

M7215

1K1 R(+)
24 VAC C(-)

IN 2
1 NOTE THAT THE C7250 20K NTC SENSOR CAN BE MOUNTED IN THE OAT ONLY IN THIS CONFIGURATION.

2 WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.

3 WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.

THERMOSTAT M28980D

Fig. 10. Stand-alone dry bulb Economizer configuration with black motor M7215.

EXH1 OR AUX1 O C

1 V
2

ACTUATOR

NOTE: ON/OFF ACTUATORS CAN BE USED ON THE EXH1 OR AUX1

O TERMINAL WITH GROUND TO THE C TERMINAL. WHEN

PROGRAMMING THE EXH1 OR AUX1 O, THE % IS THE PERCENT

OPEN POSITION OF THE OUTDOOR AIR DAMPER WHEN THE

EXH1 OR AUX1 O TERMINAL IS ENERGIZED AND THE 2-POS

DAMPER GOES OPEN. IF USING THE AUX1 O TERMINAL

PROGRAM AUX1 O FOR EXH2.

M33409

Fig. 11. 2-position actuator.

9

63-2700–11

JADETM ECONOMIZER MODULE

MS3103J1030 COMMUNICATING DCA
1 2 3 4 5

JADE W7220A1000

ON JADE CONTROLLER: 1. Y2-O CONNECT TO STAGE 2 MECHANICAL COOLING 2. Y1-O CONNECT TO STAGE 1 MECHANICAL COOLING 3. MAT IS MIXED AIR SENSOR C7250A1001 4. OAT IS TEMPERATURE CHAGEOVER C7250A1001
SENSOR OR S-BUS OA ENTHALPY SENSOR C7400S1000 5. AUX1 OUT PROGRAM TO SYS IN SYSTEM SETUP MENU
AUX2-I OCC E-GND
AUX1 OUT
Y2I Y2O Y1I Y1O C R

PRESTIGE

C

THX9421R5013

R

EIM

STATUS LEDS

POWER HEAT COOL FAN U1 U2 U3

KIT WITH PRESTIGE AND EIM YTHX9421R5051

TO THERMOSTAT CONV

RELAY

13

R822N1011 A

EIM THM5421R1013

1

TRANSFORMER

R 24

120

C VAC

VAC

SENSORS

1 THE TRANSFORMER NEEDS TO BE 100VA.
M35158

Fig. 12. Prestige and EIM with communicating actuator.

63-2700–11

10

JADETM ECONOMIZER MODULE

MA TEMP SENSOR 20K NTC
MAT MAT
S-BUS S-BUS

W7220 ECONOMIZER CONTROLLER MODULE

ROOF TOP UNIT

O/B

Y1

W1

G

OCC Y2

W2

8 1K1 AUX2-I OCC E-GND

AUX1-0

G Y1 Y2 W1

CO2 SENSOR 2-10 VDC (OPTIONAL)

IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V) ACT COM ACT 24V

Y2I
Y2O Y1I Y1O C R

1K1 C

1

2

3 S-BUS

MS3103J OR MS3105J

4 S-BUS

R(+) 24 VAC
C(-)
7

5

THERMOSTAT

W1

C7400S

OUTSIDE AIR

TEMP/HUMIDITY

(ENTHALPY)

W1

SYLKBUS SENSOR

C7400S RETURN AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR 1

C

C

2

Y1
C C
Y2 C
3 4

NOTES: SEE INSTALLATION INSTRUCTIONS 62-0331 FOR SPECIFIC W7220 JADE WIRING INFORMATION.
1 RELAY 1, DPDT RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 4 FOR HIGH SPEED FAN WITH W1 CALL.
2 RELAY 2, DPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 4 FOR HIGH SPEED FAN WITH Y2 CALL.
3 RELAY 3, SPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 1 FOR LOW SPEED FAN WITH Y1 CALL.
4 RELAY 4, SPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 1 FOR LOW SPEED FAN WITH G CALL.
5 LOW SPEED FAN IS CONFIGURED BY SETTING “MINIMUM FREQUENCY” WITH PARAMETER M1.8 OF THE STARTUP WIZARD OF THE SMARTVFD HVAC.
6 HIGH SPEED FAN IS CONFIGURED BY SETTING “PRESET FREQUENCY 1” WITH PARAMETER M3.3.12 OF THE SMARTVFD HVAC.
7 WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.

Y2 G
6 8 5
14 6

BASIC I/O BOARD

TERMINAL

SIGNAL

DEFAULT

1 +10 Vref REFERENCE OUTPUT

2

AI1+

ANALOG INPUT,

VOLTAGE OR CURRENT* VOLTAGE

3

AI1- ANALOG INPUT COMMON

(CURRENT)

4

AI2+

ANALOG INPUT,

VOLTAGE OR CURRENT

CURRENT

5

AI2 ANALOG INPUT COMMON

(CURRENT)

6

24Vout

7

GND

24V AUX. VOLTAGE I/O GROUND

8

DI1

DIGITAL INPUT 1

START FWD

9

DI2

DIGITAL INPUT 2

START REV

10

DI3

DIGITAL INPUT 3

FAULT

11

CM COMMON A FOR DIN1-DIN6**

12 24Vout

24V AUX. VOLTAGE

13

GND

I/O GROUND

14

DI4

DIGITAL INPUT 4

PRESET FREQ SELECT

15

DI5

DIGITAL INPUT 5

PRESET FREQ
SELECT 2

16

DI6

DIGITAL INPUT 6

FAULT RESE

17

C COMMON A FOR DIN1-DIN6**

18

AO1

ANALOG SIGNAL (+OUTPUT)

OP FREQ

19 AO-/GND ANALOG OUTPUT COMMON

30 +24 Vin 24V AUXILIARY INPUT VOLTAGE

A

RS485 DIFFERENTIAL RECEIVER/

TRANSMITTER

B

RS485 DIFFERENTIAL RECEIVER/

TRANSMITTER

I/O BOARD ON SMARTVFD HVAC DRIVE HVFDSD

8 WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.

M35159A

Fig. 13. Jade with Prestige IAQ thermostat, communicating actuator, CO2 and VFD.

11

63-2700–11

JADETM ECONOMIZER MODULE

M7215
ACT (2-10V) ACT COM ACT 24V
TR TR1
IN + IN ­

JADE W7220A1000

ON JADE CONTROLLER: 1. Y2-O CONNECT TO STAGE 2 MECHANICAL COOLING 2. Y1-O CONNECT TO STAGE 1 MECHANICAL COOLING 3. MAT IS MIXED AIR SENSOR C7250A1001 4. OAT IS TEMPERATURE CHAGEOVER C7250A1001
SENSOR OR S-BUS OA ENTHALPY SENSOR C7400S1000 5. AUX1 OUT PROGRAM TO SYS IN SYSTEM SETUP MENU
AUX2-I OCC E-GND
AUX1 OUT
Y2I Y2O Y1I Y1O C R

PRESTIGE

C

THX9421R5013

R

EIM

STATUS LEDS

POWER HEAT COOL FAN U1 U2 U3

KIT WITH PRESTIGE AND EIM YTHX9421R5051

TO THERMOSTAT CONV

RELAY

13

R822N1011 A

EIM THM5421R1013

1

TRANSFORMER

R 24

120

C VAC

VAC

SENSORS

1 THE TRANSFORMER NEEDS TO BE 100VA.
M35157

Fig. 14. Jade with Prestige IAQ thermostat and EIM, communicating actuator, CO2 and VFD.

63-2700–11

12

JADETM ECONOMIZER MODULE
EXH1 and EXH2 wiring:
Relay Digital Output Rating at 30 Vac (maximum powerfrom Class 2 input only): 1.5A run; 3.5A inrush @ 0.45PF (200,000 cycles) or 7.5A inrush @ 0.45PF (100,000 cycles)
If the inrush or FLA amps is above listed limits OR if the fan is a line voltage fan, an external relay will be required.
If no relay is required, the EXH1 or AUX1 out is wired to one side of the fan and the other side is wired to system common “C” on the W7220 or equipment terminal board. (W7220 powered off the system transformer).
If a relay is required, the coil of the relay would be wired between the EXH1 or AUX1 and the C terminal of the W7220.

MA TEMP SENSOR 20K NTC

1

OAT TEMP SENSOR

20K NTC

MAT MAT
OAT OAT

CO2 SENSOR 2-10 VDC (OPTIONAL)

IAQ (2-10V) IAQ COM IAQ 24V
ACT (2-10V) ACT COM ACT 24V

W7220 ECONOMIZER CONTROLLER MODULE

ROOF TOP UNIT

O/B

Y1

W1

G

OCC

Y2

W2

3
1K1 AUX2-I OCC E-GND

AUX1-0

Y2I
Y2O Y1I Y1O C R

MS7503 OR MS7505 3

1K1 R(+) 24 VAC
C(-)
2

1 NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS CONFIGURATION.
2 WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
3 WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.

THERMOSTAT M32564D

Fig. 15. Stand-alone dry-bulb Economizer configuration with Honeywell MS7503 or MS7505 Direct Coupled Actuator.

13

63-2700–11

JADETM ECONOMIZER MODULE

1
OAT TEMP SENSOR 20K NTC

MA TEMP SENSOR 20K NTC
MAT MAT OAT OAT

W7220 ECONOMIZER CONTROLLER MODULE

ROOF TOP UNIT

O/B

Y1

W1

G

OCC

Y2

W2

3 1K1 AUX2-I
OCC E-GND

AUX1-0

CO2 SENSOR 2-10 VDC (OPTIONAL)

IAQ (2-10V) IAQ COM IAQ 24V
ACT (2-10V) ACT COM ACT 24V
1
2 MS3103J
3 S-BUS OR MS3105J 4 S-BUS
5

Y2I Y2O Y1I Y1O C R
1K1
R(+) 24 VAC
C(-)
2

1 NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS CONFIGURATION.

THERMOSTAT

2 WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.

3 WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.

M32650D

Fig. 16. Stand-alone dry-bulb Economizer configuration with Honeywell MS3103J or MS3105J communicating actuators.

63-2700–11

14

JADETM ECONOMIZER MODULE
Economizer with Sylk Bus Sensors
A standalone economizer with Sylk Bus sensors uses Sylk Bus communications (see Fig. 17, Fig. 18 and Fig. 19). The Sylk Bus reduces wiring requirements while providing additional functionality.

2 MA TEMP SENSOR 20K NTC
MAT MAT
S-BUS S-BUS

W7220 ECONOMIZER CONTROLLER MODULE

ROOF TOP UNIT

O/B

Y1

W1

G

OCC

Y2

W2

4 1K1 AUX2-I
OCC E-GND

AUX1-0

CO2 SENSOR 2-10 VDC (OPTIONAL)

IAQ (2-10V) IAQ COM IAQ 24V
ACT (2-10V) ACT COM ACT 24V

TR TR1
IN + IN –

M7215

Y2I Y2O Y1I Y1O C R 1K1
R(+) 24 VAC
C(-)
3

OUTSIDE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR

THERMOSTAT
1 IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.

1

RETURN AIR

2 DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS

TEMP/HUMIDITY (ENTHALPY)

CONFIGURATION.

SYLKBUS SENSOR

3 WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS

MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.

WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION 4 RELAY BETWEEN O AND C.
M32565D

Fig. 17. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black motor.

15

63-2700–11

JADETM ECONOMIZER MODULE

2 MA TEMP SENSOR 20K NTC
MAT MAT
S-BUS S-BUS

W7220 ECONOMIZER CONTROLLER MODULE

ROOF TOP UNIT

O/B

Y1

W1

G

OCC

Y2

W2

4 1K1 AUX2-I OCC E-GND

AUX1-0

CO2 SENSOR 2-10 VDC (OPTIONAL)

IAQ (2-10V)
IAQ COM
IAQ 24V ACT (2-10V) ACT COM ACT 24V

Y2I
Y2O Y1I Y1O C R 1K1

MS7503 OR MS7505 3

R(+) 24 VAC
C(-)
3

OUTSIDE AIR

TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR

THERMOSTAT 1 IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY

(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS

SHOWN IN THE LOWER LEFT OF THIS FIGURE.

1

RETURN AIR

TEMP/HUMIDITY (ENTHALPY) 2 DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS

SYLKBUS SENSOR

CONFIGURATION.

3 WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.

4 WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION

RELAY BETWEEN O AND C.

M32566D

Fig. 18. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7503 or MS7505 Direct Coupled Actuator.

63-2700–11

16

JADETM ECONOMIZER MODULE

MA TEMP SENSOR 20K NTC
MAT MAT
S-BUS S-BUS

W7220 ECONOMIZER CONTROLLER MODULE

ROOF TOP UNIT

O/B

Y1

W1

G

OCC Y2

W2

4 1K1 AUX2-I OCC E-GND

AUX1-0

CO2 SENSOR 2-10 VDC (OPTIONAL)

IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V) ACT COM ACT 24V

Y2I
Y2O Y1I Y1O C R 1K1

1

2 3 S-BUS 4 S-BUS

2
MS3103J OR MS3105J

R(+) 24 VAC
C(-)
3

5

THERMOSTAT

C7400S OUTSIDE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR

1 IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEM/HUMIDITY (ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
2 THE S-BUS COMPONENTS MAY BE DAISY CHAINED TO ANOTHER S-BUS COMPONENT.

1

C7400S RETURN AIR

3 WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.

TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR

4 WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.

M32653D

Fig. 19. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS3103J or MS3105J communicating actuators.

2-PIN CONNECTOR NEEDED (VHR-2N)
3-PIN CONNECTOR NEEDED (VHR-3N)
4-PIN CONNECTOR NEEDED (VHR-4N)

MAT MAT OAT OAT S-BUS S-BUS S-BUS S-BUS S-BUS S-BUS
IAQ 2-10 IAQ COM IAQ 24V+ ACT 2-10 ACT COM ACT 24V+ NOT USED

JADE CONTROLLER

NOT USED AUX2-1 OCC E-GND EXH1 AUX1-O
Y2-I Y2-O Y1-I Y1-O
R C

AUX2-IIN OCC
E-GND EXH1 AAUUXX11O-OUT
6-PIN CONNECTOR NEEDED (VHR-6N)
Y2-I Y2-O Y1-I Y1-O
C R

LEFT TERMINAL BLOCK LABEL

RIGHT TERMINAL BLOCK LABEL

PART NUMBER JST VH CONNECTOR PLASTIC HOUSING VHR-2N PLUS 2 PIECES SVH-21T-P1.1 METAL CONTACT JST VH CONNECTOR PLASTIC HOUSING VHR-3N PLUS 3 PIECES SVH- 21T-P1.1 METAL CONTACT JST VH CONNECTOR PLASTIC HOUSING VHR-4N PLUS 4 PIECES SVH-21T-P1.1 METAL CONTACT JST VH CONNECTOR PLASTIC HOUSING VHR-6N PLUS 6 PIECES SVH-21T-P1.1 METAL CONTACT TYPE 42743-2

PIN COUNT 2 3 4 6 1

NOTE: THOSE ARE NOT HONEYWELL PART NUMBERS. TO PLACE AN ORDER – CONTACT YOUR SALES REPRESENTATIVE.

MANUFACTURER JST VH JST VH JST VH JST VH AMP 1/4 INCH QUICK CONNECT FOR M7215 BLACK MOTOR
M31402E

Fig. 20. OEM wiring harness information. Refer to previous wiring diagrams for detailed application wiring.

17

63-2700–11

JADETM ECONOMIZER MODULE

INTERFACE OVERVIEW
This section describes how to use the Economizer’s user interface for: · Keypad and menu navigation · Settings and parameter changes · Menu structure and selection
User Interface
The user interface consists of an LCD display and a 4-button keypad on the front of the Economizer module. The LCD is a 16 character by 2 line dot matrix display.
2 LINE LCD

MENU UP (EXIT)
BUTTON

SELECT (ENTER)

SCROLL BUTTON

(UP/DOWN)

BUTTONS

M32274A

Fig. 21. Economizer LCD and Keypad Layout.

Keypad
The four navigation buttons illustrated in Fig. 21 are used to scroll through the menus and menu items, select menu items, and to change parameter and configuration settings.

Using the Keypad with Menus
To use the keypad when working with menus: · Press the button to move to the previous menu. · Press the button to move to the next menu. · Press the button (Enter) to display the first item in the
currently displayed menu.

· Press the

button (Menu up) to exit a menu’s item

and return to the list of menus.

Using the Keypad with Settings and Parameters
To use the keypad when working with Setpoints, System and Advanced Settings, Checkout tests, and Alarms: · Navigate to the desired menu. · Press the button (Enter) to display the first item in the
currently displayed menu. · Use the and buttons to scroll to the desired
parameter. · Press the button (Enter) to display the value of the
currently displayed item.

· Press the button to increase (change) the displayed parameter value.a
· Press the button to decrease (change) the displayed parameter value.a
· Press the button to accept the displayed value and
store it in non-volatile RAM.
· CHANGE STORED displays.

· Press the

button (MenuUp/Exit) to return to the

previous menu.

a When values are displayed, pressing and holding the or button causes the display to automatically increment.

Menu Structure

Table 5 on page 19 illustrates the complete hierarchy of menus and parameters for the JADETM Economizer system.

The Menus in display order are: · STATUS · SETPOINTS · SYSTEM SETUP · ADVANCED SETUP · CHECKOUT · ALARMS

IMPORTANT
Table 5 on page 19 illustrates the complete hierarchy. Your menu parameters will be different depending on your configuration.

For example if you do not have a DCV (CO2) sensor, then none of the DCV parameters appear and only MIN POS will display. If you have a CO2 sensor, the DCV MIN and DCV MAX will appear AND if you have 2 speed fan DCV MIN (high and low speed) and DCV MAX (high and low speed will appear).

SETUP AND CONFIGURATION

Before being placed into service, the JADETM Economizer module must be setup and configured for the installed system.
IMPORTANT During setup, the Economizer module is live at all times.
The setup process uses a hierarchical menu structure that is easy to use. You press the and arrow buttons to move forward and backward through the menus and press the button to select and confirm setup item changes.

Time-out and Screensaver
When no buttons have been pressed for 10 minutes, the LCD displays a screen saver, which cycles through the Status items. Each Status items displays in turn and cycles to the next item after 5 seconds.

63-2700–11

18

JADETM ECONOMIZER MODULE

Menu STATUS

Parameter ECON AVAIL

ECONOMIZING OCCUPIED

HEAT PUMP COOL Y1-IN

COOL Y1-OUT COOL Y2-IN

COOL Y2-OUT MA TEMP
DA TEMP

OA TEMP OA HUM RA TEMP RA HUM IN CO2

DCV STATUS DAMPER OUT ACT POS ACT COUNT ACTUATOR
EXH1 OUT

Table 5. Menu Structurea.

Parameter Parameter Default Range and Value Incrementb

Notes

NO

YES/NO

YES = economizing available; the system can use Outdoor Air for free

cooling when required.

NO

YES/NO

YES = Outdoor Air being used for 1st stage cooling.

NO
n/ac OFF
OFF OFF
OFF ._ ºF

YES/NO

YES = OCC signal received from space thermostat or unitary controller. YES = 24 Vac on terminal OCC No = 0 Vac on terminal OCC.

COOL HEAT

Displays COOL or HEAT when system is set to heat pump (nonconventional)

ON/OFF

Y1-I signal from space thermostat or unitary controller for cooling stage 1. ON = 24 Vac on term Y1-I OFF = 0 Vac on term Y1-I

ON/OFF

Cool Stage 1 Relay Output to mechanical cooling (Y1-OUT terminal).

ON/OFF

Y2-I signal from space thermostat or unitary controller for second stage cooling. ON = 24 Vac on term Y2-I OFF = 0 Vac on term Y2-I

ON/OFF

Cool Stage 2 Relay Output to mechanical cooling (Y2-OUT terminal).

-40 to 150 ºF Displays value of measured mixed air from MAT sensor. Displays –.- if not connected, short, or out- of-range.

. ºF . ºF

-40 to 150 ºF Displays when Discharge Air Sylk Bus sensor is connected and displays measured discharge air temperature. Displays –.-°F if sensor sends invalid value, if not connected, short or out-of-range.
-40 to 140 ºF Displays measured value of outdoor air temperature. Displays –°F if sensor sends invalid value, if not connected, short or out-of-range.

% ._ ºF

0 to 100% 0 to 140 ºF

Displays measured value of outdoor humidity from OA Sylkbus sensor. Displays –% if not connected, short, or out- of-range.
Displays measured value of return air temperature from RA Sylkbus sensor. Displays –°F if sensor sends invalid value, if not connected, short or out-of- range.

% _ ppm
n/a 2.0V

0 to 100%

Displays measured value of return air humidity from RA Sylkbus sensor. Displays –% if sensor sends invalid value, if not connected, short or out-of- range.

0 to 2000 ppm

Displays value of measured CO2 from CO2 sensor. Invalid if not connected, short or out-of-range. May be adjusted in Advanced menu by Zero offset and Span. See note on page 6 concerning C7632 sensor.

ON/OFF

Displays ON if above setpoint and OFF if below setpoint, and ONLY if a CO2 sensor is connected.

2.0 to 10.0 V Displays output voltage or position to the damper actuator.e

n/a

0 to 100% Displays actual position of actuator.

n/a

1 to 65,535 Displays number of times actuator has cycled. 1 Cycle equals the sum

of 180° of movement in any direction.

n/a

OK/Alarm Displays Error if voltage or torque is below actuator range

(on Alarm

menu)

OFF

ON/OFF

Output of EXH1 terminal. Displays ON when damper position reaches programmed percentage setpoint. ON = 24 Vac Output; OFF = No Output.

19

63-2700–11

JADETM ECONOMIZER MODULE

Menu
STATUS CONTINUE D

Parameter EXH2 OUT
ERV

MECH COOL ON or HEAT STAGES ON
FAN SPEED

W (HEAT IN)

Table 5. Menu Structurea. (Continued)

Parameter Parameter Default Range and Value Incrementb

Notes

OFF OFF

ON/OFF ON/OFF

Output of AUX1 O terminal Displays ON when damper position reaches programmed percentage setpoint ON = 24 Vac Output, OFF = No Output; displays only if AUX1 O = EXH2
Output of AUX1 O terminal, ON = 24 Vac Output, OFF = No Output; displays only if AUX1 O = ERV

0

0, 1, or 2

Displays number of mechanical cooling stages that are active.

Displays the stage of heat pump heating that is active.

n/a

LOW or

Displays speed of fan on a 2-speed fan unit

HIGH

n/a

ON/OFF

Displays status of heat on a 2-speed fan unit.

63-2700–11

20

JADETM ECONOMIZER MODULE

Menu

Parameter

SETPOINTS MAT SET

LOW T LOCK

DRYBLB SET

DRYBLB DIF Available firmware 1.15, June 2018, and later. ENTH CURVE
DCV SET
MIN POS
VENTMAX

VENTMIN

ERV OAT SPd

Table 5. Menu Structurea. (Continued)

Parameter Parameter Default Range and Value Incrementb

Notes

53ºF 32ºF

38 to 70 ºF; The economizer will modulate the OA damper to maintain the mixed increment by air temperature at the setpoint. 1

-45 to 80 ºF; Setpoint determines outdoor temperature when the mechanical

increment by cooling cannot be turned on. Commonly referred to as the Compressor

1

lockout. At or below the setpoint the Y1-O and

Y2-O will not be energized on the controller.

63ºF 0ºF

48 to 80 ºF; Dry bulb setpoint will only appear if using dry bulb change over.

increment by Setpoint determines where the economizer will assume outdoor air

1

temperature is good for free cooling; e.g.; at 63 ºF setpoint unit will

economizer at 62 ºF and below and not economize at

64 ºF and above. There is a a 2 ºF deadband.

0 to 6ºF;

Drybulb Differential will only show if using dual drybulb, i.e., when an

increment by outdoor air temperature sensor C7250 is attached to OAT terminals,

2

and a C7400S sensor is wired to S-Bus and configured for RAT (return

air). Free cooling will be assumed whenever OA Temp is below RAT

minus this drybulb differential setting.

ES3

ES1, ES2, ES curve will only appear if using enthalpy changeover.

ES3,

Enthalpy boundary “curves” for economizing using single enthalpy.

ES4, or ES5 See page 22 for description of enthalpy curves.

1100ppm 2.8 V

500 to 2000 Displays ONLY if a CO2 sensor is connected.

ppm

Setpoint for Demand Control Ventilation of space. Above the setpoint,

increment by the OA dampers will modulate open to bring in additional OA to

100

maintain a space ppm level below the setpoint.

2 to 10 Vdc Displays ONLY if a CO2 sensor is NOT connected.

2.8 V

2 to 10 Vdc

With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan) settings are required. Default for MIN POS L is 3.2V and MIN POS H is 2.8V.
Displays only if a CO2 sensor is connected. Used for Vbz (ventilation max cfm) setpoint. VENTMAX is the same setting as MIN POS would be if you did not have the CO2 sensor.

100 to 9990 If OA, MA RA and CO2 sensors are connected and DCV CAL ENABLE is

cfm

set to AUTO mode, the OA dampers are controlled by CFM and displays

increment by from 100 to 9990 cfm.

10

2 to 10 Vdc With 2-speed fan units VENTMAX L (low speed fan) and VENTMAX H (high speed fan) settings are required. Default for VENTMAX L is 3.2V and VENTMAX H is 2.8V.

2.25 V

2 to 10 Vdc Displays only if CO2 sensor is connected. Used for Va (ventilation min cfm) setpoint. This is the ventilation requirement for less than maximum occupancy of the space.

100 to 9990 If OA, MA RA and CO2 sensors are connected and DCV CAL ENABLE is

cfm

set to AUTO mode, the OA dampers are controlled by CFM and displays

increment by from 100 to 9990 cfm.

10

2 to 10 Vdc With 2-speed fan units VENTMIN L (low speed fan) and VENTMIN H (high speed fan) settings are required. Default for VENTMIN L is 2.5V and VENTMIN H is 2.25V.

32ºF

0 to 50 ºF; Only when AUX1 O = ERV increment by 1

21

63-2700–11

JADETM ECONOMIZER MODULE

Menu

Parameter

SETPOINTS EXH1 SET CONTINUE D

EXH2 SET

SYSTEM SETUP

INSTALL
UNITS DEG EQUIPMENT

AUX2 IN

FAN SPEED

FAN CFM AUX1 OUT OCC FACTORY DEFAULT

Table 5. Menu Structurea. (Continued)

Parameter Parameter Default Range and Value Incrementb

Notes

50%

0 to 100%; Setpoint for OA damper position when exhaust fan 1 is powered by the

increment by economizer.

1

With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high speed

fan) settings are required. Default for Exh1 L is 65% and Exh1 H is

50%

75%

0 to 100%; Setpoint for OA damper position when exhaust fan 2 is powered by the

increment by economizer. Only used when AUX1 O is set to EHX2.

1

With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed

fan) settings are required. Default for Exh2 L is 80% and Exh2 H is

75%

01/01/11

ºF CONV

ºF or ºC
CONV HP

Display order = MM/DD/YY Setting order = DD, MM, then YY.
Sets economizer controller in degrees Fahrenheit or Celsius.
CONV = conventional. HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump input from thermostat or controller.

Heat (W1)g Shutdown

Note: If

(SD)

field

Heat (W1)

factory

HP(O)

default is HP(B)

available,

AUX2 IN

will default

back to

Shutdown

(SD).

2 speedh Note: If

1 speed/ 2 speed

field

factory

default is

available,

FAN

SPEED will

default

back to 1-

speed.

In CONV mode: SD = Enables configuration of shutdown (default); W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV mode for W. Shutdown is not available in the two-speed fan mode.
In HP O/B mode: HP(O) = energize heat pump on Cool (default); HP(B) = energize heat pump on Heat.
Sets economizer controller for operation of 1 speed or 2 speed supply fan. The controller does not control the fan but positions the OA and RA dampers to the heating or cooling mode. See page 23 for modes and position.
NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In.

5000cfm NONE

100 to

This is the capacity of the RTU. The value is found on the label from the

50000 cfm; RTU manufacturer. The cfm of the fan is only used with DCV CAL

increment by ENABLE AUO

100

NONE ERV EXH2 SYS

· NONE = not configured (output is not used) · ERV= Energy Recovery Ventilatord · EXH2 = second damper position 24 Vac out for second
exhaust fan. · SYS = use output as an alarm signal

INPUT NO

INPUT or ALWAYS
NO or YES

When using a setback thermostat with occupancy out (24 Vac), the 24 Vac is input “INPUT” to the OCC terminal. If no occupancy output from the thermostat then change program to “ALWAYS” OR add a jumper from terminal R to OCC terminal.
Resets all set points to factory defaults when set to YES. LCD will briefly flash YES and change to NO but all parameters will change to factory default values.

63-2700–11

22

Menu

Parameter

ADVANCED MA LO SET SETUP

FREEZE POS

CO2 ZERO

CO2 SPAN

STG3 DLY

SD DMPR POS

DA LO ALM DA HI ALM

DCVCAL ENA
MAT T CAL OAS T CAL OAS H CAL RA T CAL RA H CAL DA T CAL 2SP FAN DELAY

JADETM ECONOMIZER MODULE

Table 5. Menu Structurea. (Continued)

Parameter Parameter Default Range and Value Incrementb

Notes

45 ºF CLO

35 to 65 ºF; Temp to activate Freeze Protection (close damper or modulate to MIN increment by POS if temp falls below set value) 1º

CLO MIN

Damper position when freeze protection is active (closed or MIN POS).

0ppm 2000ppm 2.0h CLO 45 ºF

0 to 500

CO2 ppm level to match CO2 sensor start level.

ppm;

increment by

10

1000 to

CO2 ppm span to match CO2 sensor; e.g.; 500-1500 sensor output

3000 ppm; would be 500 CO2 zero and 1000 CO2 span. See note on page 6 for

increment by C7632 CO2 sensor.

50

0 min, 5 min, Delay after stage 2 for cool has been active. Turns on 2nd stage of

15 min, then mechanical cooling when economizer is 1st stage call and mechanical

15 min

cooling is 2nd stage call. Allows three stages of cooling, 1 economizer

intervals. Up and 2 mechanical.

to 4h or OFF OFF = no Stage 3 cooling.

CLO OPN

Indicates shutdown signal from space thermostat or unitary controller. When controller receives 24 Vac input on the SD terminal in conventional mode, the OA damper will open if programmed for OPN and OA damper will close if programmed for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1, etc. will shut off.

NONE

Used for alarm for when the DA air temperature is too low. Set lower

35ºF to 65ºF range of alarm, below this temperature the alarm will show on the

in 5ºF

display.

increments

80 ºF

NONE 70 ºF to 180 ºF in 5º F increments

Used for alarm for when the DA air temperature is too high. Set high range of alarm, above this temperature the alarm will show on the display

MAN

MAN (manual) AUTO

Turns on the DCV automatic control of the dampers. Resets ventilation based on the RA, OA and MA sensor conditions. Requires all sensors (RA, OA, MA and CO2). This operation is not operable with a 2-speed fan unit.

0.0 F° 0.0F° 0% RH

+/-2.5F° +/-2.5F° +/-10% RH

Allows for the operator to adjust for an out of calibration temperature sensor
Allows for the operator to adjust for an out of calibration temperature sensor
Allows for the operator to adjust for an out of calibration humidity sensor

0.0F° 0% RH 0.0 F°

+/-2.5F° +/-10% RH +/-2.5F°

Allows for the operator to adjust for an out of calibration temperature sensor
Allows for the operator to adjust for an out of calibration humidity sensor
Allows for the operator to adjust for an out of calibration temperature sensor

5 Minutes

0 to 20

When in economizing mode this is the delay for the high speed fan to

minutes in 1 try to satisfy the call for second stage cooling before the first stage

minute

mechanical cooling is enabled.

increments.

23

63-2700–11

JADETM ECONOMIZER MODULE

Menu

Parameter

CHECKOUTf DAMPER MINIMUM POSITION

DAMPER OPEN

DAMPER CLOSE CONNECT Y1-O
CONNECT Y2-O
CONNECT AUX1-O

CONNECT EXH1 ALARMS(#)
MA T SENS ERR CO2 SENS ERR OA SYLK T ERR OA SYLK H ERR RA SYLK T ERR RA SYLK H ERR DA SYLK T ERR OA SENS T ERR ACT ERROR
FREEZE ALARM
SHUTDOWN ACTIVE DMP CAL RUNNING
DA SENS ALM

Table 5. Menu Structurea. (Continued)

Parameter Parameter Default Range and Value Incrementb

Notes

n/a

n/a

n/a

n/a

The checkout for the damper minimum positions is based on the system. See Table 6.
Positions damper to the full open position. Exhaust fan contacts enable during the DAMPER OPEN test. Make sure you pause in this mode to allow for exhaust contacts to energize due to the delay in the system.

n/a

n/a

Positions damper to the fully closed position.

n/a

n/a

n/a

n/a

Closes the Y1-O relay (Y1-O). See CAUTION on page 31
Closes the Y2-O relay (Y2-O). See CAUTION on page 31

n/a

n/a

Energizes the AUX1-O output. If AUX1-O setting is: · NONE ­ no action taken · ERV ­ 24 Vac out. Turns on or signals an ERV that the
conditions are not good for economizing but are good for ERV operation.d · SYS ­ 24 Vac out. Issues a system alarm.

n/a

n/a

Closes the power exhaust fan 1 relay (EXH1)

Alarms display only when they are active. The menu title “ALARMS (#)” includes the number of active alarms in parenthesis (). When using SYLK bus sensors, “SYLK” will appear on the screen, and when using 20k OA temperature sensors, “SENS T” will appear on the screen.

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

Mixed air sensor has failed or become disconnected – check wiring then replace sensor if the alarm continues
CO2 sensor has failed, gone out of range or become disconnected check wiring then replace sensor if the alarm continues
Outdoor air enthalpy sensor has failed or become disconnected – check wiring then replace sensor if the alarm continues

n/a

n/a

n/a

n/a

Return air enthalpy sensor has failed or become disconnected – check wiring then replace sensor if the alarm continues

n/a

n/a

n/a

n/a

Discharge air sensor has failed or become disconnected – check wiring then replace sensor if the alarm continues
Outdoor air temperature sensor has failed or become disconnected check wiring then replace sensor if the alarm continues

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

Actuator has failed or become disconnected – check for stall, over voltage, under voltage and actuator count. Replace actuator if damper is moveable and supply voltage is between 21.6 V and 26.4 V. Check actuator count on STATUS menu.
Check if outdoor temperature is below the LOW Temp Lockout on setpoint menu. Check if Mixed air temperature on STATUS menu is below the Lo Setpoint on Advanced setup menu. When conditions are back in normal range then the alarm will go away.
AUX2 IN is programmed for SHUTDOWN and 24 V has been applied to AUX 2IN terminal
If DCV Auto enable has been programmed, when the Jade is completing a calibration on the dampers, this alarm will display. Wait until the calibration is completed and the alarm will go away. Must have OA, MA and RA sensors for DCV calibration; set up is in the Advanced setup menu
Discharge air temperature is out of the range set in the ADVANCED SETUP Menu. Check the temperature of the discharge air.

63-2700–11

24

JADETM ECONOMIZER MODULE

Table 5. Menu Structurea. (Continued)

Menu

Parameter

Parameter Parameter Default Range and Value Incrementb

Notes

ALARMS(#) SYS ALARM

CONTINUE

D

ACT UNDER V

n/a

n/a

n/a

n/a

When AUX1-O is set to SYS and there is any alarm (e.g., failed sensors, etc.), the AUX1-O terminal has 24 Vac out.
Voltage received by Actuator is above expected range

ACT OVER V

n/a

n/a

Voltage received by Actuator is below expected range

ACT STALLED

n/a

n/a

Actuator stopped before achieving commanded position

FEATURES ADJUSTABLE ONLY BY USE OF THE W7220 PC MOD TOOL

ACT STALL ALARM SUPPRESSION

Disabled Enabled or If enabled this feature allows the operator to suppress the stall alarm in Disabled a specific range of the actuator stroke.

SELECT TYPE OF CONTROLLER

W7220

W7220,

The operator can configure a program for a customer or job and save

W7218 or the program in the file. Found on the configuration page of the Trade

Pre-

version

programmed

special

ACTUATOR SLIPPAGE Enabled ALARM

Enabled or Disabled

Alarms if the actuator becomes disconnected from the damper or is slipping on the shaft. If Enabled, the Jade system will complete a system air temperature check. If there is the expected change in system air temperature, then Jade assumes the actuator is connected to the damper. If the expected system air temperature changes do not occur, then an actuator slippage alarm is displayed on the Jade LCD. Found on the configuration page of the Trade version.

ACTUATOR SLIPPAGE Low ALARM SENSITIVITY

Low, Standard or High

Sensitivity can be set to HIGH, STANDARD or LOW. High means the system will check 5 times for the damper to move before displaying the alarm. Standard is 10 times before the alarm is displayed. Low is 20 times before the alarm is displayed. Found on the economizer page of the Trade version.

LOCATION OF ECONOMIZER CONTROL SENSOR

Before the Before coil or The operator can choose if the economizer control sensor (normally

cooling coil AUTO

referred to as the Mixed air sensor) is placed in the mixed air (before

the coil) or Auto in the case the sensor is placed after the cooling coil.

Found on the configuration page of the Trade version.

DAMPER AIA THRESHOLD

15 degrees 5 to 40 degrees

Damper threshold feature (Adaptive Integral Action) is the difference in the mixed air temperature reported by the MAT sensor and the MAT setpoint. Lower (2 degrees) transfer rate between the actual MAT sensor reading and the MAT setpoint normally means the damper is closing and opening faster. Larger transfer rate (up to 20 degrees) between the sensor reading and the setpoint normally means the damper is opening and closing slower. Used in applications where there is a large MA space or there is a long duct between the OA and the MA causing a delay. Found on the economizer page of the Trade version.

a Table 5 illustrates the complete hierarchy. Your menu parameters may be different depending on your configuration. For example if you do not have a DCV (CO2) sensor, then none of the DCV parameters appear.
b When values are displayed, pressing and holding the or button causes the display to automatically increment. c n/a = not applicable d ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing – the ERV terminal will be
energized. In the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the
setpoint menu. e When used with Honeywell communicating actuator the damper out is reported in XX.X% open versus XX.X Vdc. f After 10 minutes without a command or mode change, the controller will change to normal operation. g Default for AUX2 IN changed from SD to W1 with 1.15 firmware (June 2018). h Default for FAN SPEED changed from 1-speed to 2-speed with 1.15 firmware (June 2018).

25

63-2700–11

JADETM ECONOMIZER MODULE

Table 6. Damper minimum position settings and readings on checkout menu.

Demand Control Ventilation

Fan Speed

(CO2 Sensor)

Setpoints

1

NO

MIN POS

1

NO

N/A

2

NO

MIN POS H

2

NO

MIN POS L

1

YES

VENT MIN

1

YES

VENT MAX

2

YES

VENT MIN H

2

YES

VENT MAX H

2

YES

VENT MINL

2

YES

VENT MAX L

Checkout VMAX-HS N/A VMAX-HS VMAX-LS VMIN-HS VMAX-HS VMIN-HS VMAX-LS N/A N/A

SEQUENCE OF OPERATION

Table 7. Dry Bulb Operation No DCV (CO2 sensor) – 1 Speed Fan.

DCV None
None

OA Good to economize? Y1-I

No

Off

On

On

Yes

Off

On

Y2-I Off Off On Off Off

FAN SPD Y1-O

High

0-v/Off

High

24-v/On

High

24-v/On

High

0-v/Off

High

0-v/Off

On

On High

24-v/On

Y2-O 0-v/Off 0-v/Off 24-v/On 0-v/Off 0-v/Off
0-v/Offa

Occupied MIN POS MIN POS MIN POS MIN POS MIN POS to FullOpen MIN POS to FullOpen

Unoccupied Closed Closed Closed Closed Closed to Full-Open
Closed to Full-Open

a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 ­O after the delay if the call for Y1-I and Y2-I have not been satisfied.

Table 8. Dry Bulb Operation With DCV (CO2 sensor) – 1 Speed Fan.

DCV

OA Good to economize? Y1-I

Below CO2 No

Off

set

On

On

Yes

Off

On

Y2-I FAN SPD Y1-O

Off High

0-v/Off

Off High On High Off High Off High

24-v/On 24-v/On 0-v/Off 0-v/Off

On

On High

24-v/On

Above CO2 No set

Off

Off High

On

Off High

0-v/Off 24-v/On

Y2-O 0-v/Off
0-v/Off 24-v/On 0-v/Off 0-v/Off
0-v/Offa
0-v/Off
0-v/Off

Occupied VENTMIN

Unoccupied Closed

VENTMIN
VENTMIN
VENTMIN
VENTMIN to FullOpen
VENTMIN to FullOpen
VENTMIN to VENTMAX
VENTMIN to VENTMAX

Closed Closed Closed Closed to Full-Open
Closed to Full-Open
Closed
Closed

63-2700–11

26

JADETM ECONOMIZER MODULE

DCV

OA Good to economize? Y1-I Y2-I FAN SPD

Y1-O

Y2-O

Occupied

Unoccupied

On

On High

24-v/On 24-v/On VENTMIN to VENTMAX

Closed

Yes

Off

Off High

0-v/Off 0-v/Off VENTMIN to

Closed

VENTMAX

On

Off High

0-v/Off

0-v/Off

VENTMIN to Full- Closed to Full-Open Open

On

On High

24-v/On 0-v/Offa VENTMIN to Full- Closed to Full-Open Open

a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 ­O after the delay if the call for Y1-I and Y2-I have not been satisfied.

Table 9. Enthalpy Operation No DCV (CO2 sensor) – 1 Speed Fan.

DCV None
None

OA Good to economize? Y1-I

No

Off

On

On

Yes

Off

On

Y2-I Off Off On Off Off

FAN SPD Y1-O

High

0-v/Off

High

24-v/On

High

24-v/On

High

0-v/Off

High

0-v/Off

On

On High

24-v/On

Y2-O 0-v/Off 0-v/Off 24-v/On 0-v/Off 0-v/Off
0-v/Offa

Occupied MIN POS MIN POS MIN POS MIN POS MIN POS to FullOpen MIN POS to FullOpen

Unoccupied Closed Closed Closed Closed Closed to Full-Open
Closed to Full-Open

a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 ­O after the delay if the call for Y1-I and Y2-I have not been satisfied.

Table 10. Enthalpy Operation With DCV (CO2 sensor) – 1 Speed Fan.

DCV

OA Good to economize? Y1-I Y2-I FAN SPD

Y1-O

Y2-O

Occupied

Unoccupied

Below set No

Off

Off High

0-v/Off 0-v/Off VENTMIN

Closed

On

Off High

24-v/On 0-v/Off VENTMIN

Closed

On

On High

24-v/On 24-v/On VENTMIN

Closed

Yes

Off

Off High

0-v/Off 0-v/Off VENTMIN

Closed

On

Off High

0-v/Off

0-v/Off

VENTMIN to Full- Closed to Full-Open Open

On

On High

24-v/On 0-v/Offa VENTMIN to Full- Closed to Full-Open Open

Above set No

Off

Off High

0-v/Off

0-v/Off

VENTMIN to VENTMAX

Closed

On

Off High

24-v/On 0-v/Off

VENTMIN L to VENTMAX

Closed

On

On High

24-v/On 24-v/On VENTMIN H to VENTMAX

Closed

Yes

Off

Off High

0-v/Off 0-v/Off VENTMIN L to

Closed

VENTMAX

On

Off High

0-v/Off

0-v/Off

VENTMIN to Full- Closed to Full-Open Open

On

On High

DELAYb 0-v/Offa VENTMIN to Full- Closed to Full-Open

24-v/On

Open

a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 ­O after the delay if the call for Y1-I and Y2-I have not been satisfied.
b With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.

27

63-2700–11

JADETM ECONOMIZER MODULE

Table 11. Dry Bulb Operation No DCV (CO2 sensor) – 2 Speed Fan.

DCV None
None

OA Good to economize? Y1-I

No

Off

On

On

Yes

Off

On

Y2-I Off Off On Off Off

FAN SPD Y1-O

Low

0-v/Off

Low

24-v/On

High

24-v/On

Low

0-v/Off

Low

0-v/Off

On

On High

DELAYb 24-v/On

Y2-O 0-v/Off 0-v/Off 24-v/On 0-v/Off 0-v/Off
0-v/Offa

Occupied

Unoccupied

MIN POS L

Closed

MIN POS L

Closed

MIN POS H

Closed

MIN POS L

Closed

MIN POS L to Full- Closed to Full-Open Open

MIN POS H to Full- Closed to Full-Open Open

aWith stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 ­O after the delay if the call for Y1-I and Y2-I have not been satisfied.
b With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.

Table 12. Dry Bulb Operation With DCV (CO2 sensor) – 2 Speed Fan.

DCV Below set

OA Good to economize? Y1-I

No

Off

On

On

Yes

Off

On

Y2-I Off Off On Off Off

FAN SPD Y1-O

Low

0-v/Off

Low

24-v/On

High

24-v/On

Low

0-v/Off

Low

0-v/Off

On

On High

24-v/On

Above set No

Off

Off Low

0-v/Off

On

Off Low

24-v/On

On

On High

24-v/On

Yes

Off

Off Low

0-v/Off

On

Off Low

0-v/Off

On

On High

DELAYb 24-v/On

Y2-O 0-v/Off 0-v/Off 24-v/On 0-v/Off 0-v/Off
0-v/Offa 0-v/Off
0-v/Off
24-v/On
0-v/Off
0-v/Off
0-v/Offa

Occupied
VENTMIN L
VENTMIN L
VENTMIN H
VENTMIN L
VENTMIN L to Full-Open
VENTMIN H to Full-Open
VENTMIN L to VENTMAX
VENTMIN L to VENTMAX
VENTMIN H to VENTMAX
VENTMIN L to VENTMAX
VENTMIN L to Full-Open
VENTMIN H to Full-Open

Unoccupied Closed Closed Closed Closed Closed to Full-Open
Closed to Full-Open
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open

aWith stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 ­O after the delay if the call for Y1-I and Y2-I have not been satisfied.
b With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.

Table 13. Enthalpy Operation No DCV (CO2 sensor) – 2 Speed Fan.

DCV
NO CO2 SENSOR

OA Good to economize? Y1-I

No

Off

Y2-I FAN SPD Y1-O

Off Low

0-v/Off

On

Off Low

24-v/On

Y2-O 0-v/Off
0-v/Off

Occupied MIN POS L
MIN POS L

Unoccupied Closed
Closed

63-2700–11

28

JADETM ECONOMIZER MODULE

DCV

OA Good to economize? Y1-I Y2-I FAN SPD

Y1-O

Y2-O

Occupied

Unoccupied

On

On High

24-v/On 24-v/On MIN POS H

Closed

Yes

Off

Off Low

0-v/Off 0-v/Off MIN POS L

Closed

On

Off Low

0-v/Off

0-v/Off

MIN POS L to Full- Closed to Full-Open Open

On

On High

DELAYb 0-v/Offa MIN POS H to Full- Closed to Full-Open

24-v/On

Open

aWith stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 ­O after the delay if the call for Y1-I and Y2-I have not been satisfied.
b With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.

Table 14. Enthalpy Operation With DCV (CO2 sensor) – 2 Speed Fan.

DCV Below set

OA Good to economize? Y1-I

No

Off

On

On

Yes

Off

On

Y2-I Off Off On Off Off

FAN SPD Y1-O

Low

0-v/Off

Low

24-v/On

High

24-v/On

Low

0-v/Off

Low

0-v/Off

On

On High

24-v/On

Above set No

Off

Off Low

0-v/Off

On

Off Low

24-v/On

On

On High

24-v/On

Yes

Off

Off Low

0-v/Off

On

Off Low

0-v/Off

On

On High

DELAYb 24-v/On

Y2-O 0-v/Off 0-v/Off 24-v/On 0-v/Off 0-v/Off
0-v/Offa 0-v/Off
0-v/Off
24-v/On
0-v/Off
0-v/Off
0-v/Offa

Occupied
VENTMIN L
VENTMIN L
VENTMIN H
VENTMIN L
VENTMIN L to Full-Open
VENTMIN H to Full-Open
VENTMIN L to VENTMAX
VENTMIN L to VENTMAX
VENTMIN H to VENTMAX
VENTMIN L to VENTMAX
VENTMIN L to Full-Open
VENTMIN H to Full-Open

Unoccupied Closed Closed Closed Closed Closed to Full-Open
Closed to Full-Open
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open

aWith stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 ­O after the delay if the call for Y1-I and Y2-I have not been satisfied.
b With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.

29

63-2700–11

JADETM ECONOMIZER MODULE

ECONOMIXING AVAILABLE NOT AVAILABLE

ENTHALPY

RA HUM (%RH)

DUAL ENTHALPY HIGH LIMIT
SINGLE ENTHALPY P2 (T,RH)
P1 (T,RH)

RA TEMP ABSOLUTE HUMIDITY

TEMPERATURE

ES5 ES4 ES3 ES2 ES1

HL

M32286A

Fig. 22. Single Enthalpy curve and boundaries.

Table 15. Single Enthalpy and Dual Enthalpy High Limit Curves.

Enthalpy Curve ES1 ES2 ES3 ES4 ES5 HL

Temp. Dry-Bulb (°F)
80.0 75.0 70.0 65.0 60.0 86.0

Temp. Dewpoint (°F)
60.0 57.0 54.0 51.0 48.0 66.0

Enthalpy (btu/lb/da)
28.0 26.0 24.0 22.0 20.0 32.4

Point P1

Point P2

Temp. °F Humidity %RH Temp. °F Humidity %RH

80.0

36.8

66.3

80.1

75.0

39.6

63.3

80.0

70.0

42.3

59.7

81.4

65.0

44.8

55.7

84.2

60.0

46.9

51.3

88.5

86.0

38.9

72.4

80.3

Two-Speed Fan Operation

Enthalpy Settings
When the OA temperature, enthalpy and dew point are below the respective setpoints, the Outdoor Air can be used for economizing. Fig. 22 shows the new single enthalpy boundaries in the W7220. There are 5 boundaries (setpoints ES1 through ES5), which are defined by dry bulb temperature, enthalpy and dew point.
Refer to Table 15 for the ENTH CURVE setpoint values.
To use enthalpy the W7220 must have a C7400S Sylkbus sensor for OA. The W7220 calculates the enthalpy and dew point using the OA temperature and humidity input from the OA sensor. When the OA temperature, OA humidity and OA dew point are all below the selected boundary, the economizer sets the economizing mode to YES, economizing is available.

The later versions of the W7220 Jade controller have the capability to work with a system using a 2-speed supply fan. The W7220 does not control the supply directly but uses the following input status to determine the speed of the supply fan and controls the OA damper to the required position.

OCC Y1 Y2 W

State

Low Low High High

Fan Speed

The W (heating mode) is not controlled by the W7220 but it requires the status to know where to position the OA damper for minimum position for the fan speed.

When conditions are above the selected boundary, the conditions are not good to economize and the mode is set to NO.
Fig. 22 shows the 5 current boundaries. There is also a high limit boundary for differential enthalpy. The high limit boundary is ES1 when there are no stages of mechanical cooling energized and HL when a compressor stage is energized.

The 2 speed fan delay is available when the system is programmed for 2 speed fan (in the System Setup menu item). The 2 speed fan delay is defaulted to 5 minutes and can be changed in the Advanced Setup menu item. When the unit has a call for Y1 In and in the free cooling mode and there is a call for Y2 In, the 2-speed fan delay starts and the OA damper will modulate 100% open, the supply fan should be set to high speed by the unit controller. After the delay one of two actions will happen:

Table 15 provides the values for each boundary limit.

· The Y2 In call will be satisfied with the damper 100% open and fan on high speed and the call will turn off

63-2700–11

30

JADETM ECONOMIZER MODULE

OR · If the call for additional cooling in the space has not
been satisfied then the first stage of mechanical cooling will be enabled through Y1 Out or Y2 Out.
CHECKOUT
Inspect all wiring connections at the Economizer module’s terminals, and verify compliance with the installation wiring diagrams.
For checkout, review the Status of each configured parameter and perform the Checkout tests.
NOTE: See “Interface Overview” on page 18. for information about menu navigation and use of the keypad.
WARNING
Electrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning wiring or making wiring connections, to prevent electrical shock or equipment damage. If any wiring changes are required, first be sure to remove power from the Economizer module before starting work. Pay particular attention to verifying the power connection (24 Vac).
Power Up
After the module is mounted and wired, apply power.
Initial Menu Display
On initial start up, Honeywell displays on the first line and Economizer W7220 on the second line. After a brief pause, the revision of the software appears on the first line and the second line will be blank.
Power Loss (Outage or Brownout)

All setpoints and advanced settings are restoreda after any power loss or interruption.
a All settings are stored in non-volatile flash memory.
Status
Use the Status menu (see Table 5) to check the parameter values for the various devices and sensors configured.
NOTE: See “Interface Overview” on page 18. for information about menu navigation and use of the keypad.
Checkout Tests
Use the Checkout menu (Table 5) to test the damper operation and any configured outputs. Only items that are configured are shown in the Checkout menu.
NOTE: See “Interface Overview” on page 18. for information about menu navigation and use of the keypad.
To perform a Checkout test: 1. Scroll to the desired test in the Checkout menu using the and buttons. 2. Press the button to select the item. 3. RUN? appears on the display. 4. Press the button to start the test. 5. The unit pauses and then displays IN PROGRESS. 6. When all parameters have been tested, press the button (Menu up) to end the test (e.g. turn off the relay).
The checkout tests can all be performed at the time of installation or any time during the operation of the system as a test that the system is operable.
CAUTION
Equipment damage may result. Be sure to allow enough time for compressor startup and shutdown between checkout tests so that you do not short-cycle the compressors.

31

63-2700–11

JADETM ECONOMIZER MODULE

TROUBLESHOOTING

Alarms
The Economizer module provides alarm messages that display on the 2-line LCD.

NOTE:

Upon power up, the module waits 60 minutes before checking for alarms. This allows time for all the configured devices (e.g. sensors, actuator) to become operational. The exception is the MA sensor which will alarm immediately.

If one or more alarms are present and there has been no keypad activity for at least 5 minutes, the Alarms menu displays and cycles through the active alarms.

You can also navigate to the Alarms menu at any time.

Clearing Alarms
Once the alarm has been identified and the cause has been removed (e.g. replaced faulty sensor), the alarm can be cleared from the display.

To clear an alarm, perform the following: 1. Navigate to the desired alarm. 2. Press the button.
3. ERASE? displays. 4. Press the button.
5. ALARM ERASED displays.

6. Press the

button (MenuUp/Exit) to complete

the action and return to the previous menu.

NOTE: If an the alarm still exists after you clear it, it redisplays within 5 seconds.

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.

Home and Building Technologies In the U.S.: Honeywell 715 Peachtree Street NE Atlanta, GA 30308 customer.honeywell.com

® U.S. Registered Trademark © 2018 Honeywell International Inc. 63-2700–11 M.S. Rev. 05-18 Printed in United States

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals