ULINE Hard Wired Exit Sign User Guide

June 7, 2024
ULINE

H-9045, H-9275
HARD-WIRED EXIT SIGN
1-800-295-5510
uline.com

ULINE Hard Wired - Cover

**TOOLS NEEDED

ULINE Hard Wired - Tools Needed** SAFETY

CAUTION! When using electrical equipment, always follow basic safety precautions, including:

  • Do not use outdoors.
  • Do not mount near gas or electric heaters.
  • Do not let power cords touch hot surfaces.
  • Use caution when servicing batteries to avoid possible shorting.
  • Mount in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
  • Use of accessories not recommended by the manufacturer may cause an unsafe condition.
  • Do not use this equipment for anything other than intended use.
  • Before wiring to AC service, turn off AC power at fuse or circuit breaker.
  • Disconnect AC power and unplug battery before servicing.
  • Only use specified lamps in the fixture.
    NOTE: Battery in unit may not be fully charged. After AC service is supplied to unit, let battery charge for at least 24 hours before performing any tests.

INSTALLATION

BACK MOUNTING

  1. Unit comes with EXIT panels on front and back. Remove back EXIT panel and replace with back plate. Drill 1/4″ holes into oblong knock outs on back plate that correspond to junction box holes to be used. (See Figure 1)
    ULINE Hard Wired INSTALLATION - Back Mounting 1

  2. Feed transformer input leads through center hole of back plate and make the proper connections. (See Figures 2-3)
    NOTE: If using 120VAC, connect black and white leads to building utility.
    NOTE: If using 277VAC, connect orange and white leads to building utility.
    NOTE: In some cases, not all leads will be used. Cap off unused wire.
    ULINE Hard Wired INSTALLATION - Back Mounting 2

  3. Feed excess wire into junction box and secure back plate to junction box. (See Figure 1)

  4. Snap in arrows on EXIT panel as required. Then snap EXIT panel to housing: top first, then bottom. (See Figure 1)
    NOTE: Use flexible conduit only. (See Figure 4)
    ULINE Hard Wired INSTALLATION - Back Mounting 3

SIDE MOUNTING

  1. Attach crossbar to junction box. Set the crossbar so longer blade is touching junction box. (See Figure 5)
    ULINE Hard Wired INSTALLATION - Side Mounting 1

  2. Open the EXIT housing. (See Figure 6) Feed the transformer input leads through side hole, being sure to secure wire into wire guides molded at edges of sign.

  3. Attach sign to canopy by inserting canopy into sign at an angle. Twist to secure. (See Figure 5)

  4. Feed transformer input leads through center hole and make the proper connections. (See Figures 2-3)
    NOTE: If using 120VAC, connect black and white leads to building utility.
    NOTE: If using 277VAC, connect orange and white leads to building utility.
    NOTE: In some cases, not all leads will be used. Cap off unused wire.

  5. Feed excess wire into junction box and align holes in canopy with holes in crossbar. Use screws supplied to tighten canopy to crossbar so canopy is securely fastened and tight against wall. (See Figure 5)

  6. Snap in arrows to EXIT panel as required. Then snap EXIT panel to housing: top first, then bottom.
    NOTE: Use flexible conduit only. (See Figure 4)

  7. Press test button to turn on LED heads. Adjust lamp heads if needed. (See Figure 7)
    ULINE Hard Wired INSTALLATION - Side Mounting 3

CEILING MOUNTING

  1. Attach crossbar to junction box. Set the crossbar so the longer blade touches junction box. (See Figure 8)ULINE Hard Wired INSTALLATION - Celing Mounting 1

  2. Open the EXIT housing. (See Figure 6) Feed the transformer input leads through top hole, being sure to secure wire into wire guides molded at edges of sign.

  3. Attach sign to canopy by inserting canopy into sign at an angle. Twist to secure. (See Figure 9)
    ULINE Hard Wired INSTALLATION - Celing Mounting 2

  4. Feed transformer input leads through center hole and make the proper connections. (See Figures 2-3)
    NOTE: If using 120VAC, connect black and white leads to building utility.
    NOTE: If using 277VAC, connect orange and white leads to building utility.
    NOTE: In some cases, not all leads will be used. Cap off unused wire.

  5. Feed excess wire into junction box and align holes in canopy to crossbar so that canopy is securely fastened and tight against the ceiling.

  6. Snap in arrows to EXIT panel as required. Then snap EXIT panel to housing: top first, then bottom.

BATTERY

CAUTION! Battery Connector is shipped disconnected. Snap connector into socket at installation. (See Figure 10)
Use Manual Battery Test Switch on side of unit to test. Red LED indicates normal operation. (See Figure 11)
ULINE Hard Wired - Bettary

1-800-295-5510
uline.com