Dwyer RSME Room Status Monitor Installation Guide
- June 3, 2024
- Dwyer
Table of Contents
RSME Room Status Monitor
Installation Guide
The Series RSME Room Status Monitor is designed for low differential pressure applications that require stringent pressure monitoring and alarming. It can be configured to monitor positive or negative pressure in clean rooms, hospital isolation rooms, laboratories, and vivariums. The RSME is a complete system with a touchscreen graphical user interface which enables access to pressure, humidity, temperature, air change, security, door status, calibration, and alarm setup. The graphical display color changes allows a clear determination of when the parameters are operating within the acceptable range (green), caution range (yellow), or have gone outside the acceptable operating range (red). The RSME room status monitor comes standard with BACnet MS/TP and Modbus® RTU communications.
INTRODUCTION
The Dwyer® Series RSME monitors room parameters in a variety of applications.
Its ease of installation and intuitive setup provide a great user experience.
While the RSME is easy to operate, it is advisable to read this manual
carefully before use. It is designed to allow the user to take full advantage
of the functionality and performance of the Series RSME.
1.1 INTENDED USE
The Series RSME is designed to monitor critical air environments, provide room
pressure indication and 3 additional user-defined parameters user-selectable
as temperature, relative humidity, air change per hour (ACH), door status,
and/or additional pressure measurements. The RSME Series has alarming and data
communication over Modbus
® RTU or BACnet MS/TP. The applications of the RSME include:
- Hospitals – patient isolation and protection rooms, operating suites, intensive care and emergency rooms.
- Pharmaceutical, semiconductor, precision manufacturing, and clean rooms.
- Laboratories – medical research, bio-safety labs (BSLs) and vivariums.
1.2 RSME FUNCTIONALITY
The Series RSME senses low differential pressure using a piezoresistive
pressure sensor. The RSME senses the differential pressure between a protected
environment, such as a clean room or isolation room, and an area outside the
room. Maintaining a constant differential pressure between the two spaces is
critical in ensuring the room is protected by ingress for the outer room or
vice-versa. The RSME can be programmed to monitor either positive or negative
room static pressure in 1 to 3 locations. In total, it can monitor up to 4
parameters: built-in differential pressure, up to 2 additional differential
pressures as inputs, relative humidity input, air change per hour (ACH) input,
and door status. The touchscreen user interface allows for easy setup of the
multi-parameter alarming and 2 levels of security protection. The BACnet
communications allows the device to communicate with other BACnet devices,
such as sensors, and allows the supervisory system to change configuration
setups and monitor alarm conditions.
SPECIFICATIONS
Service: Air.
Measurement Technology: Piezoresistive pressure sensor.
Wetted Materials: Front: PMMA window with IP65 rating; Back housing: ABS
UL 94 V-0.
Pressure Limits: 1.5 psig.
Accuracy: ±0.5% RSS (includes non-linearity: ±0.49% BFSL, hysteresis: ±0.05%
and non-repeatability: ±0.05%), or ±1% RSS (includes non-linearity: ±0.99%
BFSL, hysteresis: ±0.05% and non-repeatability: ±0.05%), after 1 hour warm-up
period.
Thermal Effect: ±0.02% FS/°F (includes zero and span).
Process Connection: Barbed, fits 1/8˝ and 3/16˝ (3 mm and 5 mm) ID rubber or
vinyl tubing.
Inputs: Two (2) user-selectable 4-20 mA, 0-5 VDC, or 0-10 VDC; USB type C used
for cloning programming; One (1) digital input for door status.
Outputs: One (1) digital output (DO) rated 5 A @ 30 VDC; One (1) 4-20 mA or
0-10 V (user selectable) corresponding to internal pressure or retransmission
of any input.
Ambient Temperature Limits: 32 to 122°F (0 to 50°C).
Power Requirements: 24 VAC/VDC.
Selectable Pressure Units: Pa, kPa, cm w.c., mm w.c., and in w.c.
Temperature Units: °F and °C.
Zero and Span Adjustments: Adjustable via touchscreen.
Power Consumption: 2.64 W max.
Electrical Connection: Removable terminal block.
Display: 4.3˝ (10.9 cm) color TFT LCD, dimmable; 480 x 272 resolution.
Communications: Modbus® RTU, BACnet MS/TP.
Audible Alarm: 69.1 dB 10 cm from display.
Weight: 13.6 oz (385.6 g).
Compliance: BTL, CE.
MOUNTING
The Series RSME is designed to be mounted flush into a wall or panel. Use the included cardboard cut-out as a template to ensure proper wall cut-out dimensions. After cutting a 5.25˝ x 3.625˝ hole (133.35 mm x 92 mm), push the junction box into the wall orienting the 2 screw tabs upward and then push the box into the cutout, as shown in Figure 1. Next, use a screwdriver to secure the 2 screw tab wall locks. After the junction box is installed firmly into the wall or panel, carefully push the RSME into the junction box as shown in Figure 2 below (after wiring the terminal block). The rear housing will snap into the junction box.
2.1 WIRING ELECTRICAL BOX
Layout the system in terms of wiring: power, analog output, BACnet, relay
output, digital inputs, analog inputs and plumbing to connect to the monitored
spaces. Run all power, earth ground, signal communications and analog output
wiring into the RSME junction box. Follow all local electrical codes and refer
to the wiring diagrams on this page and the back label of the RSME for proper
terminal locations.
The RSME includes one digital output which may be wired to a local audible or
visual alarm or may be wired to a controller to indicate an alarm condition.
The RSME contains one analog output that linearly corresponds to the reading
of the built-in pressure sensor. The RSME contains 2 built-in analog inputs.
The analog inputs are capable of accepting 4-20 mA, 0-5 VDC, or 0-10 VDC
analog transmissions. The analog inputs may be assigned as differential
pressure, temperature, relative humidity, or air change
per hour (ACH). One analog input can also be assigned as a digital input for
use as a
door status indicator. This input setup is performed in the input/output menu.
Power supply minimum requirements:
EN 55032 CISPR 32
FCC Part 15 Subpart B
2.2 ATTACHING PRESSURE TUBING
Use 1/8˝ or 3/16˝ (3 mm or 5 mm) ID rubber or vinyl tubing (adapters as
necessary) to transition from any pre-installed tubing to the barbed pressure
fittings on the RSME.
For the most stable pressure operation, a room pressure pickup installed in
the reference pressure area is also recommended.
For measuring a room maintaining a positive pressure, connect one end of
tubing to the room pressure pickup in the room and the other end to the “+”
barbed connection on the back of the RSME.
For measuring a room maintaining a negative pressure, connect one end of
tubing to the room pressure pickup in the room and the other end to the “-”
barbed connection on the back of the RSME.
BASIC OPERATION AND SOFTWARE CONFIGURATION
The RSME home screen is continuously displayed to the end-user, ensuring the room environmental conditions are clearly visible. The screen is designed to display room parameters, and enable touchscreen operation when changes in room setup are needed, additional information is desired, or if alarms need to be acknowledged. A few of the key elements of the screen are described and shown below.
-
The RSME provides visual representation where each of the parameters are either in normal (green), within the caution state (yellow), in the alarm state (red) and in cleaning mode (blue).
-
The caution (yellow) stage and alarm (red) state are programmed by the supervisor.
The caution stage can be adjusted to be within a few points from the low and high limit setting. As the monitoring parameter comes closer to the set value the display will transition from green to an yellow color to warn the staff. If any of the parameter readings go outside of the acceptable setting, it will change to a red color, start blinking, and the internal built-in audio will begin beeping. -
During the alarm state, a speaker icon will show in the middle at the top of the display if enabled. Pressing this icon will silence the audible alarm. Adjacent to the speaker icon to the left will be a bell icon representing the interlock, if enabled.
3.1 CONFIGURATION MENU
Upon applying power, the unit will display the Dwyer® logo on the screen. If
the unit is not yet configured, it will go through the initialization sequence
and begin the setup wizard. If the unit is configured, it will show the home
screen. After the unit goes through the initialization sequence, the screen
will display the home screen, which is the view that will be continuously
displayed. To access the Configuration menu from the home screen, press the
Settings (gear icon) button in the top right corner of the screen.
3.2 INITIAL SETUP WIZARD
The RSME will load the setup Wizard which will guide the user through the
initial setup.
The screen will appear in the order below and can be navigated using the
touchscreen interface.
-
Language selection
-
USB Configuration or Local Configuration
° If USB is selected, the setup wizard moves to a screen instructing how to copy parameters with the USB stick. Then the setup wizard moves to the Room Settings to allow the Room Name to be changed; followed by the Save/confirmation screen. A USB-C to USB-A drive must be used to copy parameters from one RSME to another.
° If Local is selected, it will move to the steps shown below. -
Display mode
-
Communications
-
Inputs
-
Outputs
-
Alarm
-
Room settings
-
Display settings
-
Save/confirmation screen
In the Configuration menu, one of three modes to display the parameters can be selected,
- Room: Monitoring of 4 parameters: 1 binary signal (1 door contact), 1 built-in differential pressure, and 2 analog or BACnet inputs to be selected by the user.
- Rooms: Monitoring 4 parameters: 1 built-in differential pressure, 2 analog or BACnet inputs to be selected by the user, and 2 binary contacts.
- Rooms: Monitoring 6 parameters: 1 built-in differential pressure, 2 analog or BACnet inputs to be selected by the user; and 3 binary contacts (wired in series). Examples of 1 room, 2 room, and 3 room setups are shown below.
3.2 LANGUAGE SELECTION
The RSME supports English and Spanish languages, additional languages will
become available via firmware updates. To select the desired language, press
the Settings (gear) icon on the home screen, then select “Language.”
3.3 USB CONFIGURATION
The RSME can be setup with a USB drive. A USB-C to USB-A drive must be used to
copy parameters from one RSME to another. The Duplicate Cloning menu can be
accessed by clicking on the Settings (gear) icon on the home screen, then
Maintenance, then Duplicate Cloning.
Duplicate/Cloning permits copying the RSME configuration to and from a USB
thumb drive – the purpose of this is to replicate the configuration onto other
devices. Please refer to section 6.3 for Duplicate Cloning instructions.
3.4 DISPLAY MODE
The home display is configurable and can be adjusted to the end users needs.
To access the Display Mode, click on the settings icon on the home screen,
then select Display Mode. The user can select 1 to 3 rooms and 1 to 3
sensors.
3.5 NETWORK
The RSME is capable of Modbus® RS-485 and BACnet communications. To access the
network settings, click on the settings icon on the home screen, select
configurator, then select Network. Set Modbus® or BACnet MS/TP network
information in the Network screen.
3.6 INPUTS
The RSME is capable of accepting 2 analog inputs and 1 digital input. Analog
inputs from the transmitters can be selected as: 4-20 mA, 0-5 VDC or 0-10 VDC.
The RSME contains a digital input contact for door status monitoring.
Additionally, 1 analog input can be setup as a digital input. The Inputs menu
can be accessed by clicking on the settings icon on the home screen, then
select Configurator, followed by Input/Output, then selecting Input.
The inputs can be assigned to any room. The factory installed differential
pressure sensor is identified as “Built-in Pressure”. The two remote analog
inputs are user selectable, identified as “User Input 2” and “User Input 3”.
While the binary input is identified as “Binary Input 1”. User Input 2 and
User Input 3 can be set to display temperature, relative humidity, air changes
per hour (ACH), another differential pressure input, or configured to be set
as a binary input.
Binary Input 1 can only be a digital input, it cannot be configured to another
input type.
Configuration of the Built-in Pressure selection is limited to selecting the
units and number of decimal places, the range cannot be configured.
To enter a numerical value, select the field and a floating keyboard will appear. Press the green checkmark key to change the value of the field and make the keyboard disappear as shown below. To change a value you must backspace (orange button) over the existing value first.
At the
Input screen select the input to be configured. Define the signal type based
on the transmitter output to be either milliamp (mA), DC voltage (VDC), or
contact (digital).
The input signal can then be scaled using Minimum and Maximum signal values
that match the full-scale range of the applicable transmitter. For example, 0
VDC corresponds to the minimum range of the sensor and 5 VDC corresponds to
the maximum range of the sensor.
In the Measurement box, the user can define the type of measurement
(temperature, humidity, etc) and the desired engineering units to be
displayed.
If the measurement type “Air Change Hour” (ACH) is selected and the unit is
one of “FPM” or “m/s”, then the duct cross-sectional area and room volume must
be entered.
The analog input must be scaled to the appropriate velocity range. If the unit
is one of “CFM” or “m 3/h”, then only the room volume is required and the
analog input must be scaled to the appropriate flow range
The user can adjust low and high pre-alarm trigger and alarm set points for
the ACH measurement.
Set the Low and High Measurement Values that correspond to the full-scale
range of the transmitter and the desired number of decimals places to be
displayed for the measurement value.
Tap “Go to Alarms” to set the limits for warnings and alarms.
The below figures show BI1 (digital input only). When UI2/UI3 are set as
Digital Inputs, they will show the same configuration screen.
If the signal input type for UI3 is set as “Digital,” and “DOOR” is selected as the usage, then UI3 will represent a door contact or door status switch. Selecting Normal olarity means the switch is open when the door opens, and the switch is closed when the door is closed. Selecting Reverse Polarity means the switch is open when the door is closed, and the switch is closed when the door is open. For a digital input, the delay time allows the user to set a time delay before a visual indication is shown on the screen that the door is opened.
3.8 ALARMS
The Alarm Settings menu is where all the alarm and warning functions are
defined.
Both low and high limits can be changed to Enabled or Disabled individually
and set to audio only, visual only, or both audio and visual. The alarm menu
can be accessed by clicking on the settings icon on the home screen, selecting
Configurator, then selecting Alarm.
For a positive pressure room a high limit may not be required. If this is the
case, the High Alarm can be set to Disabled. For a negative room, a low limit
may not be required. If this is the case, the Low Alarm can be set to
Disabled.
“Alarm Delay” is the time between when one of the parameter values falls
beyond an alarm condition (Low or High Limit) and when an audible, visual, or
output alarm condition occurs. Use the “Alarm Delay” when time is needed for
door entry and personnel access. “Return to Normal” delay is the opposite;
when a parameter value goes out of alarm and now falls within normal range,
the audible, visual, and output alarm conditions will persist for this period
of time or until the alarm condition is cleared.
“Alarm Deadband” is a value that is added or subtracted to a limit when
determining if a parameter has returned to a normal state. For example, if a
temperature parameter is set with a low alarm limit of 66.5 degrees and the
deadband set at 1.0 degrees, and the temperature falls to 66.5 and goes into
an alarm, the temperature must then return to a value greater than 67.5 to
trigger the alarm state to change from alarm to normal function. Alarms are
available for all parameters.
3.8 ALARMS (continued)
For Analog Parameters:
For Digital Parameters:
The high and low alarm levels are enabled by choosing “ON”. The alarm levels
are set by entering the value desired. These settings apply to all alarm
behaviors.
The warning alert set point for the analog parameters is when the display
changes from green to yellow to provide a visual warning that the parameter is
getting close to the unacceptable or alarm condition. The warning alert set
point is the amount above the low limit alarm, or below the high limit alarm
set points when the display color change is desired.
The Interlocking function causes an alarm condition to persist even when the
parameters have returned to normal operating ranges. For the interlocked alarm
to be cleared, it must be acknowledged at the touchscreen of the RSME. This
function is useful when it is important for staff present in the room to
acknowledge the alarm by responding.
Enabling the Audible Alarm causes the audible alarm within the RSME unit to
sound when in alarm condition. If disabled, the alarm icon will still be
visible on the RSME screen. If the RSME is set up over the network, it will
activate the alarm via the binary output relay; the binary output relay is
configurable.
Audible Alarms could have the potential to be disruptive. If Audible Alarms
are needed, test several settings to optimize an appropriate volume for the
environment. The internal buzzer will beep briefly after volume selection to
provide a sample of the volume level.
Mute Timeout is the amount of time an acknowledged alarm will be silent. When
an audible alarm occurs, a staff member can silence the alarm by tapping the
Mute Sound icon. Upon pressing it, the Mute Timeout starts counting down from
the number of seconds configured. When the countdown time goes to zero and the
cause of the alarm condition persists, the audible alarm will sound again.
The amount of seconds should be long enough for the staff to acknowledge it,
but not be overly disruptive.
3.9 ROOM SETTINGS
Room Settings is where each input is assigned a name and where the source of
the data is selected. After defining in Display Mode the room numbers and the
parameters to show, selection of where the parameter values come from is
required. There are two possibilities: the analog sensors are wired into the
RSME unit or they are connected through the BACnet network. To access room
settings, click the settings icon on the home screen, click configurator, then
click ROOM SETTINGS.
In the example above, the sensor position must be tapped and the sensor type
selected as well.
Selecting the Room Name input box produces a keyboard to input the name.
Select the sensor display position in the box on the left side, then select the sensor assigned to the display position via the “Select Sensor”. If the BACnet option is selected, the user has to input the BACnet address and sensor type of the remote sensor.
Select the sensor display position in the box on the left side, then select the sensor assigned to the display position using the “Select Sensor”. If the BACnet option is selected, the user has to input the BACnet address and sensor type of the remote sensor.
Select the sensor display position in the box on the left side, then select the sensor assigned to the display position via the “Select Sensor”. If the BACnet option is selected, the user has to input the BACnet address and sensor type of the remote sensor.
Select the sensor display position in the box on the left side, then select
the sensor assigned to the display position by using the “Select Sensor”. If
the BACnet option is selected, the user has to input the BACnet address and
sensor type of the remote sensor.
After completing the room settings, the user can select each parameter from
each room in order to use it at the alarm configuration or output
configuration. Each parameter is named with the room name and the selected
sensor. For the above example the parameter is named “Packaging A1_DP”.
3.10 DISPLAY SETTINGS
The RSME has display parameters that are user-adjustable. To access display
settings, click the settings icon on the home screen, click Configurator, then
click DISPLAY SETTING.
Adjust the backlight intensity bar to increase/decrease the display
brightness.
Brightness levels can be set individually for when the room is occupied or
unoccupied/cleaning. The backlight intensity can also be adjusted via BMS
control over BACnet on a schedule.
SECURITY
The Security menu is where the user sets the password access to the RSME
functions.
If Password Security is not enabled, anyone will have full, unrestricted
access to any function of the RSME unit via the touchscreen. When security is
enabled, a Supervisor and Operator Password are enforced for the Operating and
Setup screens. When a user attempts to access the set points, the Operator
Password is requested. When a user attempts to access any functions from the
Setup screen (such as I/O or network configuration), the Supervisor Password
will be requested.
Note: If the Supervisor Password has been setup and forgotten, the only
recovery method is to perform a factory reset of the unit, which will wipe out
all configuration settings. To perform a factory reset, press and hold the
button located on the back of unit above terminal block pins 4 and 5. The
connector for the second terminal block may need to be removed for easier
access.
Passcode Setup
The Operator security level allows access only to alarm acknowledgement and to
change the room modes from occupied, unoccupied and cleaning. The operator
should be defined as the person(s) that has day-to-day interaction with the
monitor to change room operating modes (when no alarms are active). The
operator and staff can also respond to local audible and visual alarms. If
Operator Password is enabled then a password will be needed before changes can
be made. The Supervisor Level allows full access to all levels of the menu
structure. This mode, if enabled, is used during initial configuration and
follow-up reconfiguration.
5.1 DIAGNOSTICS
The Diagnostics menu performs I/O and BACnet tests on the unit. The
Diagnostics menu can be accessed by clicking the settings icon on the home
screen, then selecting Diagnostic.
I/O Testing
In the I/O Testing menu, the screen will show the Inputs and Outputs
selections. The unit has the capability to choose the input desired from the
pull-down menu; the input value (volts or mA) and the corresponding calculated
output value (in the Eng. units selected) will be displayed if a sensor is
properly connected. If the user chooses the Output BI1 they can view the
output value and the user can also change the state.
MAINTENANCE
The Maintenance menu provides several functions that help ensure the RSME is
configured and operating correctly with proper parameters. To access the
Maintenance menu from the home screen, press the Settings icon in the top
right corner and select the Maintenance button.
Within the Maintenance menu, the following maintenance functions can be
accessed:
- Calibration of the built-in pressure sensor
- Date and Time allows manual or BACnet setting of date/time and customization of the date/time display
- Duplicate/Cloning permits copying the RSME configuration to and from a USB thumb drive – the purpose of this is to replicate the configuration on other devices or units that may be replaced in the field
- Software Update – in the event of software upgrades or new features that could become available from Dwyer Instruments
- Reset To Factory Default – restores the unit’s original factory configuration.
6.1 PRESSURE CALIBRATION
Pressure Calibration is used to ensure accurate and reliable pressure sensing
occurs continuously in the room environment. To access pressure calibration
from the home screen, press the Settings icon in the top right corner. From
the Maintenance menu, select Pressure Calibration.
Depending on connection, the unit will display the live value of the room
pressure being sensed at the time of menu access. Zero Adjustment can be used
for either an on- board sensor (DP) or external sensor (UI2 and UI3). To
access the on-board sensor, remove the RSME display from the wall surface and
remove the pressure tubes from the “+” (HIGH) and “-” (LOW) side of the
sensor on the back of the unit.
Leave both the “+” and “-” ports open/unblocked and press the Apply the Zero
Function button. The same can be done for external pressure transmitters at
their location.
Span Adjustment is used for calibration of the internal or external pressure
transducer sensors and testing operation of hardware circuitry. Calibration
should only be performed by qualified personnel, using a pressure calibrator.
- Select the sensor (DP, UI2, UI3) desired for recalibration. The indicated pressure will be shown.
- Disconnect the two pressure tubes from the unit.
- Connect tubing from the calibrator to the “-” LOW and “+” HIGH ports identified on the back of the RSME unit.
- Apply full range pressure. For example ±0.5 in w.c. range use +0.5 in w.c. pressure.
- When pressure reaches full range, press Span Adjustment.
- The output at full range must be within 10% of the factory calibration to allow readjustment.
Selecting Reset permits the user to discard any changes that may have been done unintentionally, leaving the unit as it was before any Zero Adjustments or Span Adjustment modifications.
6.2 DATE AND TIME
The Date and Time allows the unit date and time to be manually set, or sourced
via BACnet. The display of the date and time on the home screen can be
customized. Since there is no internal battery, if the power is lost, the
date and time will be erased.
If the device is connected by Modbus® or BACnet, the values will be restored
via the network. To access Date and Time from the home screen, press the
Settings icon in the top right corner. From the Maintenance menu, select Date
and Time.
6.3 DUPLICATE CLONING
To access Duplicate Cloning from the home screen, press the Settings icon in
the top right corner. From the Maintenance menu, select Duplicate Cloning. The
Copy to USB function is used to capture a RSME configuration onto a USB thumb
drive. This function is useful to store configurations on a personal computer,
where a controlled inventory of one or more units can be maintained. In the
event that a RSME password has to be reset or the unit needs replacement, the
proper configuration file can be retrieved and loaded. The Copy from USB
function is used to copy a RSME configuration from a USB thumb drive to
another RSME unit. A RSME configuration previously captured can then be
“cloned,” or copied to other units to reduce setup time. Once copied, the
“cloned” unit then only needs room-specific parameters setup, such as room
name, IP address, and other unique parameters.
6.4 RESET TO FACTORY DEFAULTS
The function Reset to Factory Default is used in the event a RSME unit must be
put into a known state for either service or a configuration reload. To access
Reset from the home screen, press the Settings icon in the top right corner.
From the Maintenance menu, select Reset.
A factory reset may help establish a baseline of original functionality from
which to build the specific configuration for a given application. New
configurations can then be added by either touchscreen entry, Copy from USB,
or over the BACnet network.
Selecting NO will cause the RSME unit to remain in its current state of
configuration.
Selecting YES will cause the RSME to erase all configuration information and
restore the RSME to its original factory configuration. Once YES is selected,
this function cannot be reversed or undone.
An alternative way to reset the unit to factory default settings is to insert
a paperclip and press and hold the button located on the back of unit above
terminal block pins 4 and 5. The connector for the second terminal block may
need to be removed for easier access. Resetting with the button on the back of
the unit will also clear all passwords established. This resetting method
should only be used if the password(s) are forgotten or lost.
6.5 FIRMWARE UPDATE
To update the device firmware, a USB-C to USB-A drive will be required.
Download the updated device firmware onto the USB drive via a laptop or
desktop computer. Do not change the name of the firmware file, it will end in
“.kld”. Once the firmware file is on the USB-C to USB-A drive, insert the
USB-C connection into the back side of the RSME unit while it’s powered off.
Power on the RSME with 24 VAC/DC with the USB drive plugged in. Wait for the
device to power on completely. The firmware will be updated automatically.
Once the device has successfully powered on and shows the homescreen, power
off the device and remove the USB drive from the RSME.
6.5 UNIT INFORMATION
The Unit Information menu displays the model number, serial number,
calibration date, and firmware version. To access the Unit Information menu,
press the Settings icon in the top right corner of the home screen and select
the ‘Unit Information’ button.
MAINTENANCE/REPAIR
Upon final installation of the Series RSME, no routine maintenance is
required. The Series RSME is not field serviceable and is not possible to
repair the unit. Field repair should not be attempted and may void warranty.
Do not dispose of as unsorted domestic or municipal waste. Consult retailer or
local authorities for recycling information. This symbol indicates waste
electrical products should not be disposed of with household waste. Please
recycle where facilities exist. Check with your Local Authority or retailer
for recycling advice.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website.
Contact customer service to receive a Return Materials Authorization number
before shipping the product back for repair. Be sure to include a brief
description of the problem plus any additional application notes.
©Copyright 2021 Dwyer Instruments, Inc.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219-879-8000
Fax: 219-872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>