OWNER’S MANUAL
SLIM DUCTED INDOOR UNIT
SPLIT-STYLE AIR CONDITIONER
DRAD09F1A, DRAD12F1A, DRAD18F1A, DRAD24F1A
Model Number:
Serial Number:
Purchase Date:
Installing Contractor Company Name:
TIP
Capture relevant information about your Durastar mini-split equipment before
it is installed and write it above for future reference.
INTRODUCTION
To better serve you, please do the following before contacting customer service:
- If you received a damaged product, immediately contact the retailer or dealer that sold you the product.
- Read and follow this owner’s manual carefully to help you use and maintain your air conditioner.
- Read the troubleshooting section of this manual as it will help you diagnose and solve common issues.
- Visit us on the web at www.durastar.com to download product guides and up-to-date information.
- If you need warranty service, our friendly customer service representatives are available via email at questions@durastar.com or by telephone at 1-888-320-0706.
WARNINGS
Symbols Used in This Manual
The warning symbol indicates cautionary information for the user. Extra care
and precautions should be taken to ensure the user’s safety.
The pencil indicates any manufacturer notes relating to surrounding content.
These may include further clarifications or call-outs.
A light bulb symbol indicates suggested manufacturer tips for the user to get
the most out of the Durastar equipment and to accommodate the best user
experience.
IMPORTANT SAFETY PRECAUTIONS
Improper handling can cause serious damage or injury. Please read the following safety information in its entirety.
The operation, Cleaning, and Maintenance Safety Precautions
- Children and people with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge should only use this air conditioner if they are given supervision or instructions concerning the use of the air conditioner in a safe way and understand the hazards involved.
- Children should not play with the air conditioner.
- Never stick fingers or any other body parts into the air conditioner openings. The internal fan may be rotating at high speeds, and may result in injury.
- After removing the filter, do not touch the fins in order to avoid injury.
- Maintenance must be performed by qualified professionals. Otherwise, you may experience personal injury or damage to the air conditioner and surrounding property.
- Do not repair the air conditioner by yourself. It may cause electric shock or damage. Please contact a qualified service representative when you need to repair the air conditioner.
- Do not block the air outlet or air inlet. This could cause a malfunction.
- Do not spill water on the wired thermostat as this can permanently damage the controls.
- If the below problems occur, please turn off the air conditioner and disconnect power at the circuit breaker immediately. Then contact your dealer or a qualified professional for service.
- The power cord is overheating or damaged.
- There is an abnormal sound during operation.
- The circuit breaker trips frequently.
- The air conditioner gives off a burning smell.
- The indoor unit is leaking.
- If the air conditioner operates under abnormal conditions, it may cause malfunctions, electric shock, or fire hazards.
- When turning the unit on or off via the emergency operation switch, press the switch with an insulated object other than metal.
- Do not step on the top panel of the unit, or put heavy objects on the top panel. This could cause damage or personal injury.
- Cleaning and user maintenance should not be performed by children without supervision.
- Do not spray water on the indoor unit. This could cause electric shock or a unit malfunction.
- Do not use flammable materials such as hair spray, lacquer, or paint near the air conditioner as they may catch fire.
- Do not operate the air conditioner in places near combustible gases. Emitted gases may collect around the air conditioner and cause an explosion.
- Do not use fire or a hairdryer to dry the filter. This could cause a deformation or fire hazard.
- Do not wash the air conditioner with water as this could cause an electric shock.
- Disconnect the power supply by turning it off at the circuit breaker when cleaning the air conditioner. Otherwise, you could risk electric shock.
Electrical Safety
- Only use the specified power cord. If the power cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a hazard.
- Keep the power plug clean. Remove any dust or grime that accumulates on or around the plug. Dirty plugs can cause fire or electric shock.
- Do not pull the power cord to unplug unit. Hold the plug firmly and pull it from the outlet. Pulling directly on the cord can damage it, which can lead to fire or electric shock.
- Do not connect the air conditioner to a multi-purpose socket. Doing so could cause a fire hazard.
- Do not modify the length of the power supply cord or use an extension cord to power the unit.
- If the supply cord is damaged, it must be replaced by the manufacturer, a service agent, or a similarly qualified person in order to avoid a safety hazard.
- Do not share the electrical outlet with other appliances. The improper or insufficient power supply can cause fire or electrical shock.
- The product must be properly grounded at the time of installation, or electrical shock may occur.
- For all electrical work, follow all local and national wiring standards and regulations. Connect cables tightly, and clamp them securely to prevent external forces from damaging the terminal. Improper electrical connections can overheat and cause fire, and may also cause shock. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units.
- All wiring must be properly arranged to ensure that the control board cover can close properly. If the control board cover is not closed properly, it can lead to corrosion and cause the connection points on the terminal to heat up, catch fire, or cause electrical shock.
- The air conditioner’s circuit board (PCB) is designed with a fuse to provide overcurrent protection. The specifications of the fuse are printed on the circuit board.
Installation Safety
- Installation must be performed by an authorized dealer or specialist. Improper installation can cause water leakage, electrical shock, or fire. (In North America, installation must be performed in accordance with NEC and CEC requirements by authorized personnel only.)
- Installation must be performed according to the installation instructions. Improper installation can cause water leakage, electrical shock, or fire.
- This air conditioner shall be installed in accordance with national and local wiring regulations.
- Contact an authorized service technician for repair or maintenance of this unit.
- Only use the included accessories, parts, and specified parts for installation. Using nonstandard parts can cause water leakage, electrical shock, fire, and can cause the unit to fail.
- Install the unit in a firm location that can support the unit’s weight. If the chosen location
- cannot support the unit’s weight, or the installation is not done properly, the unit may fall and cause serious injury and damage.
- Install drainage piping according to the instructions in the installation manual. Improper drainage may cause water damage to your home and property.
- For units that have an auxiliary electric heater, do not install the unit within 1 meter (3 feet) of any combustible materials.
- Do not install the unit in a location that may be exposed to combustible gas leaks. If combustible gas accumulates around the unit, it may cause a fire.
- Do not turn on the power until all work has been completed.
- When moving or relocating the air conditioner, consult experienced service technicians for disconnection and reinstallation of the unit.
Additional Precautions
- Turn off the air conditioner and disconnect the power if you are not going to use it for a long time.
- Turn off and unplug the unit during storms.
- Make sure that water condensation can drain unhindered from the unit.
- Do not operate the air conditioner with wet hands. This may cause electric shock.
- Do not use this device for any other purpose than its intended use.
- Do not climb onto or place objects on top of the outdoor unit.
- Do not allow the air conditioner to operate for long periods of time with doors or windows open, or if the humidity is very high.
PARTS IDENTIFICATION
INDOOR UNIT
OUTDOOR UNIT
NOTE
Outdoor units may vary in appearance.
INCLUDED ACCESSORIES
The air conditioning system comes with the following accessories.
Accessory| Quantity| Image| Accessory| Quantity|
Image
---|---|---|---|---|---
Manual| 1-2| | Display Panel| 1|
Soundproof
Insulation
Sheath| 1| | Wired
Thermostat| 1|
Cord Protector| 1| | Magnetic Ping
(Some Models)| 1|
Drain Pipe
Adapter| 1| | Drain Pipe
Worm Clamp| 2|
Copper Nut| 2| |
OPERATING TEMPERATURES
Your air conditioner is designed to operate in the following indoor and
outdoor temperatures.
When your air conditioner is used outside of the following temperature ranges,
certain safety features may activate and turn off the unit to protect it from
damage.
TEMPERATURE RANGES
| COOL Mode| HEAT Mode| DRY Mode
---|---|---|---
Indoor Air| 62°F – 90°F| 32°F – 86°F| 50°F – 90°F
Temperature| (17°C – 32°C)| (0°C – 30°C)| (10°C – 32°C)
Outdoor Air| -13°F – 122°F| -13°F – 86°F| 32°F – 122°F
Temperature| (-25°C – 50°C)| (-25°C – 30°C)| (0°C – 50°C)
To further optimize the performance of your unit, do the following:
- Keep doors and windows closed.
- Limit energy usage by using TIMER ON and TIMER OFF features.
- Do not block air inlets or outlets.
- Regularly inspect and clean air filters.
NOTE
Your Durastar air conditioner’s outdoor unit is equipped with a base pan
heater, allowing it to continue to operate at freezing temperatures as low as
-13°F (-25°C). When outdoor air temperatures are at or below 32°F (0°C), we
strongly recommend keeping the unit plugged in at all times to ensure smooth
ongoing performance.
NOTE
Keep the room’s relative humidity below 80%. If the air conditioner operates
in excess of this, the surface of the air conditioner may attract
condensation. To help prevent condensation from forming and dripping, set the
vertical airflow louver to its maximum angle (vertically to the floor) and set
the fan to HIGH.
WIRED THERMOSTAT
-
ON/OFF Button
Press to turn the air conditioner ON and OFF. -
UP Button
Press to increase the set temperature in 1°F / 1oC increments. -
DOWN Button
Press to decrease the set temperature in 1°F / 1oC increments. -
SWING Button
The function is not available for this model. -
ECO Button
For details on ECO mode, see the ECO feature section of this manual. -
FAN SPEED Button
Press to select the following fan speeds:
-
LOCK Button
Used to lock/unlock the thermostat settings. -
RESET Button
Used to restore the system to its default settings. -
AUXILIARY ELECTRICAL HEATER BUTTON
For use with third-party electrical heaters. Not included with this unit. -
FOLLOW ME Button
For details, see the FOLLOW ME feature section of this manual. -
TIME OFF Button
Press to initiate the TIMER OFF feature. For details, see the TIMER feature section of this manual. -
TIME ON Button
Press to initiate the TIMER ON feature. For details, see the TIMER feature section of this manual. -
MODE Button
Press to select the operating mode.
NOTE
Press the Temp Up and Down buttons (#2 & #3) simultaneously to switch between
Fahrenheit and Celsius (some models).
NOTE
The FAN speed cannot be adjusted in AUTO or DRY Mode.
NOTE
Press and hold the UP and DOWN buttons simultaneously for 3 seconds to switch
between F and C.
OPERATING MODES
SETTING TEMPERATURE
This unit can be set at any temperature between 62 and 86°F (17-30°C) in cool,
heat, and dry modes. You can increase or decrease the set temperature in 1°F
(1°C) increments using the TEMP up ( ) or TEMP down ( )button.
AUTO
In AUTO mode, the unit will automatically select the COOL, FAN, HEAT, or DRY
modes to maintain the set temperature.
- Press the MODE button and select AUTO.
- Set your desired temperature using the TEMP down or TEMP up button.
- Press the ON/OFF button to start the unit.
COOL
- Press the MODE button and select COOL.
- Set your desired temperature using the TEMP down or TEMP up button.
- Press the FAN SPEED button to select the fan speed: AUTO, LOW, MED or HIGH.
- Press the ON/OFF button to start the unit.
FAN
- Press the MODE button and select FAN.
- Press the FAN SPEED button to select the fan speed: AUTO, LOW, MED or HIGH.
- Press the ON/OFF button to start the unit.
NOTE
You cannot adjust the temperature in FAN mode. As a result, your thermostat’s
LCD display will not display a temperature.
DRY (DEHUMIDIFY)
- Press the MODE button and select DRY.
- Set your desired temperature using the TEMP down or TEMP up button.
- Press the ON/OFF button to start the unit.
HEAT
- Press the MODE button and select HEAT.
- Set your desired temperature using the TEMP down or TE MP up button.
- Press FAN button to select the fan speed: AUTO, LOW, MED or HIGH.
- Press the ON/OFF button to start the unit.
NOTE
As outdoor temperature drops, the performance of your unit’s HEAT function may
be affected.
NOTE
Two or more indoor units can be operated by one outdoor unit. When several
indoor units are operated simultaneously, cooling/dry/fan and heating
operations cannot be done at the same time. When COOL/DRY/FAN is selected with
one unit and HEAT with another or vice versa, the unit selected last goes into
standby mode.
ADVANCED FEATURES
TIMER
The TIMER feature establishes the amount of time that will elapse before the
unit will automatically turn on/off.
Press the TIMER ON button to initiate the auto-on time sequence. Each
subsequent press of this button will increase the setting in 30-minute
increments up to 10 hours. Once the setting time displays 10.0, each
additional press will increase the setting in 60-minute increments. To cancel
the auto-timed program, simply adjust the timer to 0.0.
Press the TIMER OFF button to initiate the auto-off time sequence. Each
subsequent press of this button will increase the setting in 30-minute
increments up to 10 hours. When the setting time displays 10.0, each
additional press will increase the setting in 60-minute increments. To cancel
the auto-timed program, simply adjust the timer to 0.0.
TIMER ON and OFF setting example.
Keep in mind that the time periods you set for both the on and off feature
refer to hours after the current time.
If the current time is 1:00 PM and the TIMER ON setting is adjusted to 2.5
hours, the auto-on time sequence will turn the air conditioner on 2.5 hours
later at 3:30 PM. Setting the TIMER OFF auto off sequence to 5.0 hours will
turn off the air conditioner 5 hours later at 6:00
PM.
ECO
The ECO feature is designed to decrease energy use while you sleep. This
feature can only be activated by the wired thermostat. The ECO feature is not
available in FAN or DRY mode.
Press the ECO button when you are ready to go to sleep. When in COOL mode, the
unit will increase the temperature by 2°F (1°C) after 1 hour and will increase
an additional 2°F (1°C) after another hour. When in HEAT mode, the unit will
decrease the temperature by 2°F (1°C) after 1 hour, and will decrease an
additional 2°F (1°C) after another hour.
The ECO feature will turn off after 8 hours and the system will return to
normal functioning.
FOLLOW ME
This feature uses the temperature at the thermostat’s location, instead of the
indoor unit’s location, to optimize the temperature around you and ensure
maximum comfort. Press the FOLLOW ME button to turn on this feature and the
thermostat will display the temperature at its location. When using AUTO,
COOL, and HEAT modes the air conditioner will continue running until the
temperature at the thermostat’s location is satisfied. Press the FOLLOW ME
button again to turn off this feature.
AUTO-RESTART
The auto-restart feature is enabled when power is interrupted to the unit.
After power is restored, the unit will automatically return to its prior
settings before power was lost. No buttons need to be pressed to set this
feature – it is automatic.
LED DISPLAY INDICATORS
The following is a list of possible indicators that may appear on the indoor unit’s display panel. Not all the display indicators may be available on the unit purchased.
Feature | Indicator | Notes |
---|---|---|
TIMER ON, SWING, TURBO, SILENCE | ON | Displays for 3 seconds when the TIMER ON |
feature is set or the SWING, TURBO, or SILENCE feature is turned on. If the
unit is off, ON will continue to be shown if the TIMER ON feature is set.
TIMER OFF, SWING, TURBO, SILENCE| OF| Displays for 3 seconds when the TIMER
OFF feature is set or the SWING, TURBO, or SILENCE feature is turned off.
SELF CLEAN| SC| Displays when the SELF CLEANING feature is on.
FP| FP| Displays when the FP feature is on.
FORCED COOLING| FC| Displays when the FORCED COOLING mode is selected with the
manual control button. See Manual Operation section.
ANTI-COLD AIRFLOW| cF| The unit is designed not to blow cold air in HEAT mode.
When HEAT mode is selected the unit will display “cF” until the set
temperature is reached and the unit can blow warm air.
DEFROST| dF| Displays when the unit is defrosting. This may last 5-10 minutes
depending on the outdoor temperature and the amount of frost buildup on the
outside unit.
MANUAL OPERATION (USE WITHOUT THERMOSTAT)
The manual override button is intended for testing purposes and emergency operations. Please do not use this button unless the wired thermostat is unresponsive and it is absolutely necessary. The unit must be turned off before manual operation.
To operate your unit manually:
- Locate the MANUAL button on the display panel of the unit.
- Press the MANUAL button one time to activate the FORCED AUTO mode.
- Press the MANUAL button again to activate the FORCED COOLING mode.
- Press the MANUAL button a third time to turn the unit off.
CARE AND MAINTENANCE
CAUTION
- Always turn off the unit and disconnect power before cleaning or maintenance.
- Only use a soft, dry cloth to wipe the unit clean. If the unit is especially dirty, you can use a cloth soaked in warm water to wipe it clean.
CLEANING INDOOR UNIT
- Do not use chemicals or chemically treated cloths to clean the unit.
- Do not use benzene, paint thinner, polishing powder or other solvents to clean the unit. They can cause the plastic surface to crack or deform.
- Do not use water hotter than 104°F (40°C) to clean the front panel. This can cause the panel to deform or become discolored.
CLEANING THE AIR FILTER
A dirty air filter can reduce the cooling efficiency of your unit, and can
also be bad for your health.
Make sure to clean the filter once every two weeks.
- Remove the screw holding the air filter in place.
- Remove the air filter.
- Clean the air filter by gently vacuuming the surface or washing it in warm water with a mild detergent.
- Rinse the filter with clean water and allow it to air dry. Do not dry the filter in direct sunlight.
- Reinstall the air filter.
- Reinstall the screw.
|
---|---
If using water, the inlet side should face down and away from the water
stream.| If using a vacuum cleaner, the inlet side should face the vacuum.
CAUTION
- Before changing the filter or cleaning, turn off the unit and disconnect its power supply.
- When removing the filter, do not touch the metal parts in the unit. The sharp metal edges can cut you.
- Do not use water to clean the inside of the indoor unit. This can destroy insulation and cause electrical shock.
- Do not expose the filter to direct sunlight when drying. This can shrink the filter.
MAINTENANCE – LONG PERIODS OF NON-USE
If you do not plan to use your air conditioner for an extended period of time,
do the following:
- Clean all filters.
- Turn on the FAN until the unit dries out completely.
- Turn off the unit and disconnect the power.
MAINTENANCE – PRE-SEASON INSPECTION
After long periods of non-use, or before periods of frequent use, do the
following:
- Inspect for damaged wires
- Clean all filters.
- Check for leaks.
- Replace batteries.
- Make sure nothing is blocking any air inlets or outlets.
TROUBLESHOOTING
SAFETY PRECAUTIONS
If ANY of the following conditions occurs, turn off your unit immediately!
- The power cord is damaged or abnormally warm
- You smell a burning odor
- The unit emits loud or abnormal sounds
- A power fuse blows or the circuit breaker frequently trips
- Water or other objects fall into or out of the unit
DO NOT ATTEMPT TO FIX THESE YOURSELF! CONTACT AN AUTHORIZED SERVICE
PROVIDER IMMEDIATELY!
COMMON ISSUES
The following problems are not a malfunction and in most situations will not
require repairs.
ISSUE | POSSIBLE CAUSES |
---|---|
Unit does not turn on when pressing ON/OFF button | The unit has a 3-minute |
protection feature that prevents the unit from overloading. The unit cannot be
restarted within three minutes of being turned off.
The unit changes from COOL/HEAT mode to FAN mode| The unit may change its
setting to prevent frost from forming on the unit. Once the temperature
increases, the unit will start operating in the previously selected mode
again.
The set temperature has been reached, at which point the unit turns off the
compressor. The unit will continue operating when the temperature fluctuates
again.
The indoor unit emits white mist| In humid regions, a large temperature
difference between the room’s air and the conditioned air can cause white
mist.
Both the indoor and outdoor units emit white mist| When the unit restarts in
HEAT mode after defrosting, white mist may be emitted due to moisture
generated during the defrosting process.
The indoor unit makes noises| A rushing air sound may occur when the louver
resets its position.
A squeaking sound may occur after running the unit in HEAT mode due to the
expansion and contraction of the unit’s plastic parts.
Both the indoor unit and outdoor unit make noises| Low hissing sound during
operation: This is normal and is caused by refrigerant gas flowing through
both indoor and outdoor units.
---|---
Low hissing sound when the system starts, has just stopped running or is
defrosting: This noise is normal and is caused by the refrigerant gas stopping
or changing direction.
Squeaking sound: Normal expansion and contraction of plastic and metal parts
caused by temperature changes during operation can cause squeaking noises.
The outdoor unit makes noises| The unit will make different sounds based on
its current operating mode.
Dust is emitted from either the indoor or outdoor unit| The unit may
accumulate dust during extended periods of non-use, which will be emitted when
the unit is turned on. This can be mitigated by covering the unit during long
periods of inactivity.
The unit emits a bad odor| The unit may absorb odors from the environment
(such as furniture, cooking, cigarettes, etc.) which will be emitted during
operations.
The unit’s filters have become moldy and should be cleaned.
The fan of the outdoor unit does not operate| During operation, the fan speed
is controlled to optimize product operation.
Operation is erratic, unpredictable, or unit is unresponsive| Interference
from cell phone towers and remote boosters may cause the unit to malfunction.
In this case, try the following:
•Disconnect the power, then reconnect.
•Press the ON/OFF button on the thermostat to restart the operation.
NOTE
If problem persists, contact a local dealer or your nearest customer service
center.
Provide them with a detailed description of the unit malfunction as well as
your model number.
When troubles occurs, please check the following points before contacting a repair company.
PROBLEM | POSSIBLE CAUSES | SOLUTION |
---|---|---|
Poor cooling performance | Temperature setting may be higher than ambient room | |
temperature | Lower the temperature setting | |
The heat exchanger on the indoor or outdoor unit is dirty | Clean the affected |
heat exchanger
The air filter is dirty| Remove the filter and clean it according to
instructions
The air inlet or outlet of either unit is blocked| Turn the unit off, remove
the obstruction and turn it back on
Doors and windows are open| Make sure that all doors and windows are closed
while operating the unit
Excessive heat is generated by sunlight| Close windows and curtains during
periods of high heat or bright sunshine
Low refrigerant due to leak or long-term use| Check for leaks, re-seal if
necessary, and top off refrigerant
Too many sources of heat in the room (people, computers, electronics, etc.)|
Reduce the amount of heat sources
Poor heating
performance| The outdoor temperature is extreme& low| Use the auxiliary
heating device
Cold air is entering through doors and windows| Make sure that all doors and
windows are closed during use
Low refrigerant due to leak or long-term use| Check for leaks, re-seal if
necessary and top off refrigerant
The unit
starts
and stops frequently| There’s too much or too little refrigerant in the
system| Check for leaks and recharge the system with refrigerant
Incompressible gas or moisture has entered the system| Evacuate and recharge
the system with refrigerant
The compressor is broken| Replace the compressor
The voltage is too high or too low| Install a manostat to regulate the voltage
Indicator lamps
continue flashing or error code appears| The unit may stop operation or
continue to run safely. If the indicator lamps continue to flash or error
codes appear, wait for about 10 minutes. The problem may resolve itself.
If not, disconnect the power, then connect it again. Turn the unit on.
If the problem persists, disconnect the power and contact your nearest
customer service center.
The unit is not working| Power failure| Wait for the power to be restored
---|---|---
The power is turned off| Turn on the power
The fuse is burned out| Replace the fuse
The unit’s 3-minute protection has been activated| Wait three minutes after
restarting the unit
Timer is activated| Turn timer off
ERROR CODES (Only Appear on the Unit’s Display Panel)
CODE | ERROR |
---|---|
EO | Indoor EEPROM malfunction |
El | Communication malfunction between indoor and outdoor unit |
E2 | Zero-crossing signal detection error |
E3 | Indoor fan speed malfunction |
E4 | Ambient temperature sensor (T1) malfunction |
ES | Evaporator temperature sensor (T2) malfunction |
EC | Refrigerant leakage detection |
FO | Current overload protection |
Fl | Outdoor temperature sensor (T4) malfunction |
F2 | Outdoor condenser pipe temperature sensor (T3) malfunction |
F3 | Discharge air temperature sensor (TP) malfunction |
F4 | Outdoor EEPROM malfunction |
F5 | Outdoor fan speed malfunction |
F6 | T2B sensor malfunction (Multi-zone outdoor units only) |
PO | IPM malfunction or IGBT current protection |
P1 | Voltage protection – DC voltage between P&N out of range |
P2 | High-temperature protection of IPM module or compressor |
P3 | Outdoor temperature too low |
P4 | Inverter compressor drive error |
P6 | High/Low-pressure protection |
NOTE
If your problem persists after performing the checks and diagnostics above, or
the error code remains, turn off your unit immediately and contact an
authorized service center.
LIMITED WARRANTY – PARTS
TEN (10) YEARS PARTS
Subject to all of the terms of this Limited Warranty, including, but not
limited to, the specific exclusions set forth below and subject to the
Manufacturer’s right to inspect and validate the warranty claim as set forth
below, Manufacturer will repair or replace, at its option, ANY PART of Covered
Equipment that is found to be defective in materials or workmanship. If an
exact replacement part is not available, an equivalent part or credit will be
provided.
The parts are warranted for a period of ten (10) years to the original owner
of the mini-split equipment under normal use and service. For a period of ten
(10) years from the date of installation, if any parts prove defective due to
improper workmanship and/or material, Durastar with replace any defective part
without charge for the part. Replacement parts carry the balance of the
original 10-year parts warranty.
To qualify:
- The mini-split equipment must be installed in a residential single-family home.*
- The original mini-split equipment owner must reside in the single-family home.
- The mini-split equipment must be properly installed. This includes installation by a contractor licensed for HVAC installation following all local and state laws.
- Any part to be replaced must be made available in exchange for the replacement.
*Single-family home is defined as any single-family dwelling, which includes apartments, condominiums, duplexes, and homes.
EFFECTIVE DATE OF WARRANTY
The Effective Date of warranty coverage is determined as follows: (a) If the
original installation date can be verified by the installer’s invoice then the
Effective Date of warranty coverage is the original installation date as shown
on the installer’s invoice. For residential new construction installations,
the final occupancy permit, or proof of purchase from the builder can be
substituted for the installer’s invoice. (b) if the original installation date
cannot be verified by the installer’s invoice, or proof of purchase from the
builder in residential new construction applications, then the Effective Date
of warranty coverage is the Covered Equipment’s manufacture date (as verified
by the product’s serial number) plus ninety (90) days.
There is NO LABOR component provided with this warranty. This Limited Warranty
does NOT cover any labor costs or expenses for service, NOR for removing or
reinstalling parts. You are responsible for all labor costs or expenses,
unless a labor service agreement exists between you and your contractor.
This Limited Warranty does NOT cover shipping costs. You are responsible for
the cost of shipping warranty replacement parts from our factory to the
Manufacturer’s distributor and from the distributor to the location of your
Covered Equipment. You also are responsible for the cost of shipping failed
parts to the distributor and for incidental costs incurred locally, including
handling charges. (If in Alaska, Hawaii
or Canada, you also must pay the shipping costs of returning the failed part
to the port of entry into the continental United States.)
EXCLUSIONS
In addition to the other exclusions identified in this Limited Warranty, this
Limited Warranty excludes:
- Damages, malfunctions, or failures resulting from failure to properly install, operate, or maintain Covered Equipment in accordance with the Manufacturer’s instructions.
- Damages, malfunctions, or failures resulting from misuse, accident, contaminated, or corrosive atmosphere, vandalism, freight damage, fire, flood, freeze, lightning, acts of war, acts of God and the like.
- Parts installed with Covered Equipment or used in connection with normal maintenance, such as cleaning or replacing air filters, refrigerant, thermostats, tubing, or concrete pads.
- Covered Equipment that is not installed in the United States.
- Covered Equipment that is not installed by a qualified, trained HVAC professional in accordance with applicable codes, ordinances, and good trade practices.
- Damages, malfunctions, or failures resulting from the use of any attachment, accessory, or component not authorized by the Manufacturer or resulting from alteration or modification of the unit.
- Covered Equipment moved from the original installation location.
- Covered Equipment when operated with system components (indoor unit, outdoor unit, coil, and refrigerant control devices) or accessories which do not match or meet the specifications recommended by the Manufacturer.
- Any Covered Equipment manufactured that has been sold to the consumer via the Internet or auction website, and has not been installed by a trained, qualified HVAC professional.
- Covered Equipment that is not part of a properly matched system as specified by the Air Conditioning, Heating & Refrigeration Institute (AHRI).
COMMERCIAL WARRANTY
Installations in commercial applications carry a ONE (1) YEAR PARTS warranty
following the other provisions in this Limited Warranty.
OBTAINING WARRANTY SERVICE
If you believe your product is defective, contact the licensed contractor who
installed your mini-split system. Alternatively, contact a licensed
contractor, dealer, or distributor.
Durastar Customer Support is available for troubleshooting assistance. Before
contacting Customer Support, please locate your model number, serial number,
and proof of purchase. These items will be required to complete any warranty
service. A Durastar authorized representative will verify warranty eligibility
and determine appropriate service options. Service will be provided during
normal business days and hours.
THIS WARRANTY IS IN LIEU OF ANY OTHER WARRANTY, EXPRESS OR IMPLIED, INCLUDING
WITHOUT IMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE.
TO THE EXTENT ANY IMPLIED WARRANTY IS REQUIRED BY LAW, IT IS LIMITED IN
DURATION TO THE EXPRESS WARRANTY PERIOD ABOVE. NEITHER THE MANUFACTURER NOR
ITS DISTRIBUTORS SHALL BE LIABLE FOR ANY INCIDENTAL, CONSEQUENTIAL, INDIRECT,
SPECIAL, OR PUNITIVE DAMAGES OF ANY NATURE, INCLUDING WITHOUT LIMITATION, LOST
REVENUES OR PROFITS, OR ANY OTHER DAMAGE WHETHER BASED ON CONTRACT, TORT OR
OTHERWISE. IN NO EVENT AND UNDER NO CIRCUMSTANCE OF ANY TYPE OR KIND SHALL THE
SELLER, MANUFACTURER, AND/OR DISTRIBUTOR BE LIABLE FOR ANY REASON, UNDER ANY
THEORY, FOR MORE THAN THE BASIC COST OF THE PRODUCT TO THE PURCHASER OR END-
USER. SOME STATES DO NOT ALLOW THE EXCLUSION OF INCIDENTAL OR CONSEQUENTIAL
DAMAGES, SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU. THIS WARRANTY GIVES YOU
SPECIFIC LEGAL RIGHTS. YOU MAY HAVE OTHER RIGHTS THAT VARIES FROM STATE TO
STATE.
THIS PAGE WAS INTENTIONALLY LEFT BLANK.
DURASTAR.COM
©2020 Durastar
V1.0