MCOHOME MCOEA8-9 9 in 1 Home Multi Sensor User Guide
- June 6, 2024
- MCOHOME
Table of Contents
MCO Home
9 in 1 MULTI-SENSOR
SKU: MCOEA8-9
Quickstart
This is a secure Alarm Sensor for Europe. To run this device please
connect it to your mains power supply. To add this device to your network
execute the following action:
- Hold F1 to choose interface for Add or Remove Z-Wave network.
- Click F2 five times until arrows icon turns blue
- Hold F2 and the device enters into learning mode, the radio icon turns blue and the device is added into the Z-Wave network.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law. The manufacturer,
importer, distributor, and seller shall not be liable for any loss or damage
resulting from failure to comply with the instructions in this manual or any
other material. Use this equipment only for its intended purpose. Follow the
disposal instructions. Do not dispose of electronic equipment or batteries in
a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This device is suited for use in the region mentioned in the Quickstart
section. Z-Wave ensures reliable communication by reconfirming every message (
two-way communication ) and every mains powered node can act as a repeater
for other nodes ( meshed network ) in case the receiver is not in direct
wireless range of the transmitter. This device and every other certified
Z-Wave device can be used together with any other certified Z-Wave device
regardless of brand and origin as long as both are suited for the same
frequency range. If a device supports secure communication it will
communicate with other devices secure as long as this device provides the same
or a higher level of security. Otherwise, it will automatically turn into a
lower level of security to maintain backward compatibility. For more
information about Z-Wave technology, devices, white papers, etc. please refer
to www.z-wave.info.
Product Description
MCOHome A8-9 is a Z-Wave enabled multiple environmental monitoring sensor,
with a 3.5 inches TFT clear display and compliant to Z-Wave Plus standard. It
is built-in with Temperature, Humidity, PM2.5, CO2, VOC, PIR, illumination,
Noise, Smoke sensor. Device can be added into any Z-Wave network and is
compatible with any other Z-Wave certified devices.
Prepare for Installation / Reset
Please read the user manual before installing the product. In order to include
(add) a Z-Wave device to a network, it must be in a factory default state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave controller is able to perform this operation however it is recommended
to use the primary controller of the previous network to make sure the very
device is excluded properly from this network.
Reset to factory default
This device also allows being reset without any involvement of a Z-Wave
controller. This procedure should only be used when the primary controller is
inoperable.
- Press & hold F1 to enter the Z-Wave setting interface, then press & hold F1 again to enter the parameters setting interface
- Press & hold F2 to enter the setting interface and select default
- Click F2 3 times and displays OFF–>ON–>OK–>OFF, factory setting is restored.
Safety Warning for Mains Powered Devices
ATTENTION : only authorized technicians under consideration of the
country-specific installation guidelines/norms may do works with mains power.
Prior to the assembly of the product, the voltage network has to be switched
off and ensured against re-switching.
Installation
Device is suggested to be installed indoors, a place with around 1.5m height
above the floor where represents the average CO2 concentration. It should be
away from direct sunlight, any cover, or any heat source, to avoid false
signals for temperature control.
Notice!
- Device must be wall-mounted vertically. Do not lay it flat or upside down while working.
- Do not mount it in a wind gap, or cover its bottom, which may affect the detected data.
Step 1 : Remove the steel frame from the backside of the device, and then
fix it onto the installation box with 2 screws.
Step 2 : Wire the adaptor.
Step 3 : Put the device back onto the steel frame, it will attach with
the frame firmly by built-in magnets.
Step 4 : Check the installation and power, the device is ready for work.
Inclusion/Exclusion
On factory default, the device does not belong to any Z-Wave network. The
device needs to be added to an existing wireless network to communicate
with the devices of this network. This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion. Both processes are initiated by the primary controller of the
Z-Wave network. This controller is turned into exclusion respective inclusion
mode. Inclusion and Exclusion is then performed doing a special manual action
right on the device.
Inclusion
- Hold F1 to choose interface for Add or Remove Z-Wave network.
- Click F2 five times until arrows icon turns blue
- Hold F2 and the device enters into learning mode, then radio icon turns blue and the device is added into the Z-Wave network.
Exclusion
- Hold F1 to choose interface for Add or Remove Z-Wave network.
- Click F2 five times until arrows icon turns blue
- Hold F2 and the device enters into learning mode, then radio icon turns blue and the device is removed into the Z-Wave network.
Product Usage
Power on/off
Wire the adaptor and the device is powered on. It will display all detected
information by the sensors.
Display interface
Hold Key F1 can switch among the following 4 display interfaces:
- Data detecting: display all sensors data
- Network: Z-Wave Add/Remove
- Data calibration: to calibrate the detected data manually
- Local time setting
Data Calibration
- Hold F1 to choose interface for data calibration.
- Then hold F2 to switch among the sensors.
- Choose one and click F2, F1 to change the data.
- After finished, hold F1 can return data detecting interface.
Local time setting
- Hold F1 to choose interface for local time setting.
- Then hold F2 to switch among Hour-Minute-Second-Year-Month-Date.
- Click F2, F1 can change the data of the flashing item.
- After finished, hold F1 can return data detecting interface.
Quick troubleshooting
Here are a few hints for network installation if things don’t work as
expected.
- Make sure a device is in a factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise, you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Don’t poll FLIRS devices.
- Make sure to have enough mains powered devices to benefit from the meshing
Association – one device controls another device
Z-Wave devices control other Z-Wave devices. The relationship between one
device controlling another device is called association. In order to control a
different device, the controlling device needs to maintain a list of devices
that will receive controlling commands. These lists are called association
groups and they are always related to certain events (e.g. button pressed,
sensor triggers, …). In case the event happens all devices stored in the
respective association group will receive the same wireless command wireless
command, typically a ‘Basic Set’ Command.
Association Groups:
Group Number | Maximum Nodes | Description |
---|---|---|
1 | 1 | Lifeline group |
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however,
certain configurations can adapt the function better to user needs or unlock
further enhanced features.
IMPORTANT: Controllers may only allow configuring signed values. In order
to set values in the range 128 … 255 the value sent in the application shall
be the desired value minus 256. For example: To set a parameter to 200it may
be needed to set a value of 200 minus 256 = minus 56. In the case of a two-
byte value, the same logic applies: Values greater than 32768 may need to be
given as negative values too.
Parameter 1: PM2.5 Delta Level
This is the PM2.5 Delta Level which determines when to report the current
PM2.5 value. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 – 127 | Indicates to report current PM2.5 value when change >n * 1ug/m3 |
Parameter 2: CO2 Delta Level
This is the CO2 Delta Level which determines when to report the current CO2
value.
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 – 127 | Indicates to report current CO2 value when change > n * 5ppm |
Parameter 3: Temperature Delta Level
This is the temperature Delta Level which determines when to report the
current temperature value.
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 – 127 | Indicates to report current temperature value when change > n * 0.5 |
Parameter 4: Humidity Delta Level
This is the humidity Delta Level which determines when to report the current
humidity value.
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 – 127 | Indicates to report current humidity value when change >n% |
Parameter 5: VOC Delta Level
This is the VOC Delta Level which determines when to report the current VOC
value.
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 – 127 | n*5ppb Report change |
Parameter 6: Lux Delta Level
This is the brightness Delta Level which determines when to report the current
brightness value.
Size: 2 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 – 32767 | Indicates to report current Illumination value when change >n*1 Lux |
Parameter 7: dB Delta Level
This is the noise Delta Level which determines when to report the current
noise value.
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 – 127 | Indicates to report current Noise value when change >n*1 dB |
Parameter 8: PIR Delta Level
This is the temperature Delta Level which determines when to report the
current temperature value. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 | Indicates report change |
Parameter 9: SMOKE Delta Level
Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
0 | Indicates Turn off report |
1 | Indicates report change |
Parameter 10: Smoke Timer
Size: 2 Byte, Default Value: 60
Setting | Description |
---|---|
0 | Turn off report |
35 – 32767 | Report every n*1s |
Parameter 11: PIR Timer
Size: 2 Byte, Default Value: 60
Setting | Description |
---|---|
0 | Turn off report |
35 – 32767 | Report every n*1s |
Parameter 12: PM2.5 Timer
Size: 2 Byte, Default Value: 120
Setting | Description |
---|---|
0 | Turn off report |
35 – 32767 | Report every n*1s |
Parameter 13: CO2 Timer
Size: 2 Byte, Default Value: 120
Setting | Description |
---|---|
0 | Turn off report |
35 – 32767 | Report every n*1s |
Parameter 14: Temperature Timer
Size: 2 Byte, Default Value: 180
Setting | Description |
---|---|
0 | Turn off report |
35 – 32767 | Report every n*1s |
Parameter 15: Humidity Timer
Size: 2 Byte, Default Value: 180
Setting | Description |
---|---|
0 | Turn off report |
35 – 32767 | Report every n*1s |
Parameter 16: VOC Timer
Size: 2 Byte, Default Value: 180
Setting | Description |
---|---|
0 | Turn off report |
35 – 32767 | Report every n*1s |
Parameter 17: LUX Timer
Size: 2 Byte, Default Value: 300
Setting | Description |
---|---|
0 | Turn off report |
35 – 32767 | Report every n*1s |
Parameter 18: db Timer
Size: 2 Byte, Default Value: 300
Setting | Description |
---|---|
0 | Turn off report |
35 – 32767 | Report every n*1s |
Parameter 47: Temperature unit
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | °C |
1 | °F |
Parameter 50: Temperature Offset
Size: 1 Byte, Default Value: 100
Setting | Description |
---|---|
0 – 127 | ((n-100)/10)=(-10~2.7)℃ |
-128 (255) – -1 (128) | ((156+n)/10)=(2.8~15.5)℃ |
Parameter 51: Humidity Offset
Size: 2 Byte, Default Value: 20
Setting | Description |
---|---|
0 – 40 | n-20=(-20~20)% |
Parameter 52: CO2 OffSet
Size: 2 Byte, Default Value: 500
Setting | Descripti on |
---|---|
0 – 1000 | (n-500)=(-500~500)ppm |
Parameter 53: PM2.5 Offset
Size: 1 Byte, Default Value: 100
Setting | Description |
---|---|
0 – 127 | n-100=(-100~27)ug/m3 |
-128 (255) – -1 (128) | 156+n=(28~155)ug/m3 |
Parameter 54: Lux_OffSet
Size: 2 Byte, Default Value: 5000
Setting | Description |
---|---|
0 – 10000 | n-5000=(-5000~5000)lux |
Parameter 55: VOC Correct
Size: 1 Byte, Default Value: 100
Setting | Description |
---|---|
0 – 127 | n-100=(-100~27)ppb |
-128 (255) – -1 (128) | 156+n=(28~155)ppb |
Parameter 65: dB Correct
Size: 1 Byte, Default Value: 50
Setting | Description |
---|---|
0 – 100 | (n-50)=-50~50 |
Parameter 255: Factory Reset (set only)
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
85 | Factory Reset |
170 | Restore default Parameter |
Technical Data
Dimensions | 0.1090000×0.1090000×0.0420000 mm |
---|---|
Weight | 404 gr |
Hardware Platform | ZM5202 |
EAN | 4.25E+12 |
IP Class | IP 20 |
Voltage | 12 V |
Device Type | Notification Sensor |
Network Operation | Always On Slave |
Z-Wave Version | 6.71.03 |
Certification ID | ZC10-20096971 |
Z-Wave Product Id | 0x015F.0xA803.0x135A |
Color | White |
Frequency | Europe – 868,4 Mhz |
Maximum transmission power | 5 mW |
Supported Command Classes
- Association Grp Info
- Association V2
- Configuration
- Device Reset Locally
- Firmware Update Md V4
- Manufacturer Specific V2
- Powerlevel
- Security 2
- Sensor Multilevel V10
- Supervision
- Transport Service V2
- Version V2
- Zwaveplus Info V2
Explanation of Z-Wave specific terms
- Controller — is a Z-Wave device with capabilities to manage the network. Controllers are typically Gateways, Remote Controls, or battery-operated wall controllers.
- Slave — is a Z-Wave device without capabilities to manage the network. Slaves can be sensors, actuators, and even remote controls.
- Primary Controller — is the central organizer of the network. It must be a controller. There can be only one primary controller in a Z-Wave network.
- Inclusion — is the process of adding new Z-Wave devices into a network.
- Exclusion — is the process of removing Z-Wave devices from the network.
- Association — is a control relationship between a controlling device and a controlled device.
- Wakeup Notification — is a special wireless message issued by a Z-Wave device to announce that is able to communicate.
- Node Information Frame — is a special wireless message issued by a Z-Wave device to announce its capabilities and functions.
(c) 2021 Z-Wave Europe GmbH, Antonstr. 3, 09337 Hohenstein-Ernstthal, Germany,
All rights reserved, www.zwave.eu. The template is
maintained by Z-Wave
Europe GmbH. The product content is maintained by Z-Wave Europe GmbH, Support
team, support@zwave.eu. Last update of the product
data: 2021-01-08
12:28:40
References
- Z-Wave Europe - The leading european distributor for Smart Home products.
- Z-Wave Europe - The leading european distributor for Smart Home products.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>