namron 4512744 Thermostat Touch Z-Wave 16A Instruction Manual
- June 6, 2024
- NAMRON
Table of Contents
INSTRUCTION MANUAL
NAMRON THERMOSTAT
TOUCH Z-WAVE 16A
INSTRUCTION MANUAL
Namron termostat touch Z-Wave 16A
Technical data
Z-Wave frequency | 868.42MHz (EU) |
---|---|
Operation voltage | 220-240V, 50/60Hz |
Maximum load | 16A |
Power consumption | <2W |
Ambient temperature | 0°C to 40°C (during operation) |
Temperature range | 0°C to 40°C |
Hysteresis | 0.5°C to 2°C (default 0.5°C) |
Floor sensor | NTC R25=10K±1%@25°C, B25/50=3950K±1%, (3m included) |
Floor sensors supported | NTC R25=10K±1%@25°C, B25/50=3950K±1% (factory |
setting)
NTC R25=15K±1%@25°C, B25/50=3950K±1%
NTC R25=50K±1%@25°C, B25/50=3950K±1%
NTC R25=100K±1%@25°C, B25/50=3950K±1%
Control modes| 1. Away 2. Auto 3. Manual 4. Drying 5. Off
Control types| Room sensor (factory default)
Floor sensor
Room + floor sensor
This parameter can also be configured through advanced config parameter 10
IP rating| IP21
Relative humidity| 8% to 80%
Standard| 60730-1:2016;A1, IEC 60730-2-9:2019;A1
IEC 61000-3-2:2019, 61000-3-3:2013+A1:2019,
60730-1:2016+A1:2019,
60730-2-19:2019+A1:2019+A2:2020,
50663:2017;ETSI
301 489-1V2.2.3,ETSI
301 489-3V2.1.1 ETSI
300 220-1 v3.1.1., ETSI
300 220-2 V3.2.1
RED:2014/53/EU
Certificate| Z-Wave plus, CE, RED
Installation
a.Installation must be done by a qualified electrician.
b.The power supply must be turned off during installation.
(1) Wiring diagram
(2) Mounting
a.Remove the display unit and front cover by using a small screwdriver.
b.Insert the wires to the correct terminals as presented in the wiring diagram
above. The suggested wire-stripping length is 8-10mm.
c.Fix the thermostat into the connection box by tightening the screws. Make
sure that the thermostat is fixed without deformation. Suggested torque is
0.2-0.4Nm (2.0-4.1kgf.cm).
Symbol overview
Settings Menu
Select TIME/DATE on Home Interface to enter into TIME/DATE SET interface as
follow:
Enter settings menu (needs to be added)
- Under Home Interface, meanwhile, the device is at OFF mode (Off icon), press and hold up and down buttons at the same time for over 5 seconds to enter Settings Menu.
- Short press moves up and down button to select a settings item, then short press button F to enter selected item.
- Settings menu include Preview menu, Z-Wave settings, Schedule, Monitor settings, Time/Date settings, Other settings
Time Setting
Select TIME/DATE on Home Interface to enter into TIME/DATE SET interface as
follow:
Short press button to select the item you would like to modify, then short press up and down buttons to modify the value of the selected item, then short press button F to save and quit, the short pressing button only quits without saving.
2. Preview interface
On Home Interface, the user can enter into PREVIEW interface, the interface
will display some basic configurations, energy consumption, date, floor
temperature, etc.
Control Mode
Short press button on Home Interface to switch operation modes: the icons of Away, Auto, Manual, Drying, Off modes will be displayed alternatively for 3 seconds and last displayed mode will be selected, or just short press F button to select the desired mode when the modes’ icon displayed alternatively. Press and hold the button on the Home interface for over 3 seconds to select Away mode directly, then press and hold the button for 3 seconds to quit Away mode.
1. Away Mode : the device will control the heating system according to
the set temperature within the set period.
Users can set time to leave home and time to go home according to their
requirements of, and set how the
the device will control the temperature during this period.
1.1. If away mode has already been activated, the end time for away mode is
valid, the device will execute Away Mode
Temperature Schedule before the end time.
1.2. If away mode has already been activated, the values of the end time for
away mode are set as 0, the device will always
execute the current set temperature with no time limitation. The device will
consider the mode as anti-freeze mode, the
recommended temperature setting is 4-10°C.
2. Auto Mode: the device will control the heating system according to
the configured time schedule or Z-Wave protocol
Energy_Save_Heating Setpoint.
2.1. When configuration parameter 8 value is set as 1, the device will control
the temperature of energy save mode according to the temperature set by
Command Class Energy_Save_Heating Setpoint or set by using the move up and
down buttons, the following mentioned schedule will be invalid.
2.2. When configuration parameter 8 value set as 0, the temperature set by
Command Class Energy_Save_HeatingSetpoint and set by using the move up and
move down buttons will both be invalid, Energy Save Mode will control the
temperature according to the following user schedule.
For instance, if the user would like to keep the room temperature at 18C
during 18:00-23:00 on every Monday, and keep the room temperature at 20C after
22:30 on every Monday, then the user can set the schedule by himself.
Schedule setting method 1 : user can enter into the schedule on Z-Wave Set Interface, the schedule interface is as follows:
Short press button to select “Auto F Schedule”, then short press button Schedule weekly setting interface.
Schedule setting method 2 : on Home Interface, meanwhile the device is
under Auto Mode, short press button to enter into Auto Mode Schedule weekly
setting interface quickly:
On Auto Mode Schedule weekly setting interface, use buttons and F to enter
into schedule setting of a certain week as
follows:
On Auto Day Schedule interface, short press button to select the time or
temperature that you would like to modify, then short press move up and down
buttons to modify the value, then short press button F to save and quit,
the short pressing button only quits without saving.
For each schedule, the latter time should be later than the former time, otherwise saving will fail with the error remind “Time setting error!!!”. The default time schedules are as follows:
Monday-Friday | 7:30,24C-12:00,20C | Saturday-Sunday | 7:30,24C-12:00,20C |
---|---|---|---|
18:00,16C-22:30,18C | 18:00,18C-22:30,18C |
3. Manual Mode : the device will control the heating system according to
the current set temperature. The temperature can be
set by a move up and move down button on the Home interface, or configured by
Z-Wave gateway.
4. Drying Mode : The device will judge the set temperature for heating
within a short period of time.
I.e.: in order to dry the water in the bathroom in a short time, the device
could be set to quickly heat to dry the floor. Enter the configuration
interface is as follow:
Duration: set how long the dry mode should last
After Mode: set the mode after the drying mode ends
Remain: shows the remaining time of the drying mode
For configuration method and modification, please refer to Automatic Mode (Energy Save Mode) Schedule:
5. Off Mode: this mode only enables the device to turn on the heating
system when the anti-freezing mode is enabled and the device meets all
required conditions, otherwise, the device will not work, meanwhile, the
standby interface will only show
room temperature.
Monitor Set|
|
The function of the monitor set is a real-time monitor of over current, overheat, and freezing. On Home Interface, short press MONITOR SET to enter into monitor set interface as follows:
Short press button to select the item would like to modify, then short press moves up and down buttons to modify the value of the selected item, then short press F button to save and quit, the short pressing button only quits without saving.
---|---|---
Over-current Alarm| |
If the current is over the set value, the relay will be forced off by the device, and the state will be reported to the gateway. The over-current alarm function can be disabled, which can be set directly through the device. Or can be configured through Advance Config parameter 2 by setting the value as 0 to disable the function, please refer to the part “Advance Config”.
Over-heat Alarm| |
If room temperature or floor temperature is over the set value, the relay will be forced off by the device, and an overheat alarm will be reported to the associated devices, meanwhile, the buzzer or vibrator will beep 3 times every 10 seconds. The overheat alarm function can be disabled, which can be set directly through the device.
Or can be configured through Advance Config parameter 6 by setting the value as 0 to disable the function, please refer to the part “Advance Config”. Overheat alarm interface is as follow:
Note : to cancel over the current alarm or overheat the alarm, just press and hold the button for over 3 seconds or reset the power of the device. After canceling manually, the relay will show the heating forbidden icon within 120 seconds, but other operations are allowed.
Hysteresis| |
To prevent the undulation of sensor temperature when the sensor temperature is approaching the set temperature, which will cause that the controller may keep switching on/off the relay. Here hysteresis enables the controller to control the relay only when the sensor temperature is a bit lower than the set temperature, this value can be set. This hysteresis is only valid when the control type is a single sensor, please refer to the part Control Type.
For instance, when hysteresis is set as 0.5 degrees, then only when the current sensor temperature is 0.5 degrees lower than the set temperature, will the controller heat, if the sensor temperature >= set temperature, the controller will not heat.
Key Vibration Set| |
Set the level of the vibration sensor under the buttons or buzzer level. OFF: vibration or buzzer off Low Level, High Level: low vibration or buzzer level, high vibration or buzzer level. The level can also be configured through Advance Config parameter 03.
Display Brightness Set| |
The OLED displays brightness when operating the device. High Level, Mid Level,
Low Level.
This parameter can also be configured through the Advance Config parameter
[22].
Display Temperature Set| |
This parameter defines which sensor temperature will be displayed on the Home
page.
Floor Temp: floor temperature (external sensor). Home Temp: indoor air
temperature.
This parameter can also be configured through the Advance Config parameter
[23].
Other Set| |
Select OTHER SET on Home Interface to enter into another SET interface as
follow:
Short press button to select the item you would like to modify, then short
press moves up and down buttons to modify the value of the selected item, then
short press button F to save and quit, the short pressing button only quits
without saving.
Temperature Compensation| |
The displayed temperature may have big tolerance caused by the sensor or other
factors, so it is necessary to do temp compensation to the room sensor and
floor sensor. The compensation range is -5 ~ +5°C, stepping is 0.5°C.
This parameter can also be configured through Advance Config parameters [11]
and [12].
Re-power Status| |
Device state after reset power of the device.
If set as “last status”, the device will go to the status before power failure
after power on again.
If set as “default”, the device will go to default mode after power on again.
This parameter can also be configured through the Advance Config parameter
[4].
Internal Over Heat Protection| |
To ensure the safety of the device, if the internal temperature of the device (not displayed on the interface) is over a certain value during the heating process, the device will execute a short temporary action to turn off the relay, and the icon will appear on the interface, after the temperature decreases to a certain value, the device will recover to work.
Z-Wave Set Introduction
1. Z-Wave Network Management
Select ZWAVE INFO on Home Interface to enter into Z-Wave network management
interface as follow:
Adding to a Z -Wave Network ( Inclusion)
Method 1 : Select “Add”, then short press button F, the device will send
out inclusion request, “Status” will show “Inclusion…”. If
there is no response from a gateway within 30 seconds, or inclusion failed,
“Status” will show “Fail”. If included successfully,
“Status” will show “Inclusion OK” and device ID.
Method 2 : Operate the gateway into inclusion mode, make sure the device
is already removed from the previous network, reset
power of the device, the device will be included in the gateway automatically.
Removing from a Z-Wave Network (Exclusion)
Select “Remove”, then short press button, the device will send out exclusion
request, “Status” will show “Exclusion…”. If
there is no response from a gateway within 30 seconds, or exclusion failed,
“Status” will show “Fail”. If excluded successfully,
“Status” will show “Exclusion OK” and device ID will be shown as 0.
Factory Reset (Reset)
Factory resetting will reset all Advance Config parameters to the default
value, and the device will be removed from the Z-Wave
network.
Select “Reset”, then short press button F , the device will start reset,
“Status” will show “Reset…”. If there is no response from
a gateway within 6 seconds, or exclusion failed, “Status” will show “Fail”. If
reset successfully, “Status” will show “Reset OK”.
Note 1: if the device is excluded or reset successfully, the Auto Mode
Schedule will be reset to the default value.
Note 2: the sent frame of inclusion and exclusion is the INFO frame.
2. Basic set command class
Set the device operation mode as Comfort Mode (Manual Mode) by sending command
class basic set = 0XFF. Set the device
operation mode as OFF mode by sending command class basic set = 0x00
Z-Wave Technical Specifications
1. Supported Notification Report and Sensor Type
Notification Type
| Triggering Event|
Description
---|---|---
POWER_MANAGEMENT| POWER_MANAGEMENT_OVERCURRENT_DETECTED| Over Current Alarm
Heat Alarm| Overheat detected| Over Heat Alarm
SENSOR MULTILEVEL Type support| Scale
---|---
Air temperature| Celsius (℃)
2. Technical Specifications
Item
|
Definition
---|---
SDK| 6.82.00
Explorer Frame Support| Yes
Device Type| Thermostat(HVAC)
Generic Device Class| GENERIC_TYPE_THERMOSTAT
Specific Device Class| SPECIFIC_TYPE_THERMOSTAT_HEATING
Role Type| Always On Slave (AOS))
Routing| Yes
Thermostat Related Specifications
Command
|
Support
---|---
ThermostatMode| ThermostatMode_OFF(off) ThermostatMode_HEAT(UI displays
Manual) ThermostatMode_DRY ThermostatMode_EnergyHeat(UI displays Auto)
ThermostatMode_Away(UI displays Away)
ThermostatSetPoint| ThermostatSetPointType_Heating(set manual temperature) ThermostatSetPointType_Energy_Save_Heating(set auto temperature) ThermostatSetPointType_DRY
ThermostatSetPointType_Away_Heating(set away temperature)
3. Supported Command Class
Root Device
Suppourt Command class| |
Support S2/s0
---|---|---
COMMAND_CLASS_ZWAVEPLUS_INFO| V2|
COMMAND_CLASS_SECURITY| V1|
COMMAND_CLASS_SECURITY_2| V1|
COMMAND_CLASS_TRANSPORT_SERVICE| V2|
COMMAND_CLASS_SUPERVISION| V1|
COMMAND_CLASS_THERMOSTAT_MODE| V3| YES
COMMAND_CLASS_THERMOSTAT_OPERATING_STATE| V1| YES
COMMAND_CLASS_THERMOSTAT_SETPOINT| V2| YES
COMMAND_CLASS_ASSOCIATION| V2| YES
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION| V3| YES
COMMAND_CLASS_ASSOCIATION_GRP_INFO| V1| YES
COMMAND_CLASS_VERSION| V3| YES
COMMAND_CLASS_MANUFACTURER_SPECIFIC| V2| YES
COMMAND_CLASS_DEVICE_RESET_LOCALLY| V1| YES
COMMAND_CLASS_POWERLEVEL| V1| YES
COMMAND_CLASS_TIME_PARAMETERS| V1| YES
COMMAND_CLASS_CONFIGURATION| V1| YES
COMMAND_CLASS_NOTIFICATION| V8| YES
COMMAND_CLASS_METER| V3| YES
COMMAND_CLASS_MULTI_CHANNEL| V4| YES
COMMAND_CLASS_FIRMWARE_UPDATE_MD| V4| YES
Controlled command class
| |
Support S2/s0
---|---|---
COMMAND_CLASS_THERMOSTAT_MODE| V3| YES
COMMAND_CLASS_THERMOSTAT_SETPOINT| V2| YES
Note : the EndPoint01 mirrors equivalent effect root endpoint.
EndPoint1 command list:
Support command class | Support S2/s0 | |
---|---|---|
COMMAND_CLASS_ZWAVEPLUS_INFO | V2 | |
COMMAND_CLASS_SECURITY | V1 | |
COMMAND_CLASS_SECURITY_2 | V1 | |
COMMAND_CLASS_SUPERVISION | V1 | |
COMMAND_CLASS_SENSOR_MULTILEVEL | V5 | YES |
COMMAND_CLASS_ASSOCIATION | V2 | YES |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION | V3 | YES |
OMMAND_CLASS_ASSOCIATION_GRP_INFO | V1 | YES |
COMMAND_CLASS_THERMOSTAT_MODE | V3 | YES |
COMMAND_CLASS_THERMOSTAT_OPERATING_STATE | V1 | YES |
COMMAND_CLASS_THERMOSTAT_SETPOINT | V2 | YES |
EndPoint2 (floor temperature sensor) command list:
Support command class | Support S2/S0 | |
---|---|---|
COMMAND_CLASS_ZWAVEPLUS_INFO | V2 | |
COMMAND_CLASS_SECURITY | V1 | |
COMMAND_CLASS_SECURITY_2 | V1 | |
COMMAND_CLASS_SUPERVISION | V1 | |
COMMAND_CLASS_SENSOR_MULTILEVEL | V5 | YES |
COMMAND_CLASS_ASSOCIATION | V2 | YES |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION | V3 | YES |
COMMAND_CLASS_ASSOCIATION_GRP_INFO | V1 | YES |
5. Association
Root device
Group ID
| NAME| Profile| Max nodes|
Description
---|---|---|---|---
1| Lifeline| AGI_LIFE_LINE(0x0001)| 5| 1. Send Command Class
DEVICE_RESET_LOCALLY_NOTIFICATION to associated devices of this group when the
factory reset the device.
2. Send Command Class THERMOSTAT_SETPOINT_REPORT, THERMOSTAT_MODE_REPORT,
THERMOSTAT_OPERATING_STATE_REPORT to associated devices of this group When
operation mode and temperature change.
3. Send Command Class NOTIFICATION_REPORT to associated devices of this group
when over-current, overheat detected
4. Send Command Class METER_REPORT to associated devices of this group to
report metering parameters.
2| Heat Set| AGICONTROL KEY01 (0x2001)| 5| Transfer Command Class
THERMOSTAT_SETPOINT_SET THERMOSTAT_MODE_SET to control other temperature
control devices when operation changes
EndPoint01 :
Group ID| NAME| Profile| Max nodes|
Description
---|---|---|---|---
1| Lifeline| AGI_LIFE_LINE (0x0001)| 0| Lifeline(0x0001)
Note : the EndPoint01 has an equivalent effect of the root function. EndPoint02
Group ID| NAME| Profile| Max nodes|
Description
---|---|---|---|---
1| Lifeline| AGI_LIFE_LINE(0x0001)| 0| Lifeline(0x0001)
6. Advance Config Parameters
Parameter
| Size| Description| Default Value|
Parent Menu
---|---|---|---|---
0x02(2)| 1|
Over-current detection max. value, unit is A. When the detected current is over this value, the device will turn off the relay and send NOTIFICATION CC. 0, disable overcurrent detection 5-16, over current detection max. value
| 16| Monitor Set
0x03(03)| 1| Vibration level and buzzer level triggered by pressing buttons 0,
disable vibration and buzzer
1, Low Level
2, High Level| 1| Other Set
0x04(4)| 1| Whether to recover to settings before power failure or power reset
0, use default settings 1, recover to settings before power failure, or power
reset| 1| Other Set
0x06(6)| 1|
High-temperature detection max. value, unit is ℃ when either temperature sensor is higher than this value, the device will turn off the relay and send NOTIFICATION CC. 0, disable this function 20-60, the high-temperature value
| 45| Monitor Set
0x07(7)| 1|
Temperature control hysteresis value setting, setting range 0.5℃- 2℃ 5-20, unit is 0.1℃
| 5| Monitor Set
0x08(8)| 1| Auto mode (Energy save mode) temperature schedule 0, use schedule
set by the user 1, use Energy_Save_Heating temperature set by
THERMOSTAT_SETPOINT_SET| ****
0
| ****
None
0x09(9)| 1| Select floor temperature sensor type
1, NTC/10KB(25/50°C)=3950
2, NTC/15KB(25/50°C)=3950
3, NTC/50KB(25/50°C)=3950
4, NTC/100KB(25/50°C)=3950| 1| Other Set
0x0A(10)
| ****
1
| Temperature control reference selection 1, room sensor2, floor sensor 3, room+floor sensor| ****
1
| ****
Other Set
0x0B(11)| 1| ROOM SENSOR temperature compensation setting -10~10, unit is
0.5℃| 0| Other Set
0x0C(12)| 1| FLOOR SENSOR temperature compensation setting -10~10, unit is
0.5℃| 0| Other Set
0x0D(13)| 1| Set how long the drying mode lasts 5~100, the unit is minute| 30|
Dry Mode Schedule
** 0x0E(14)| 1| Set the mode a fter the drying mode ends 0x00 = OFF 0x01 =
Manual mode (comfort mode) 0x02 = Auto mode (energy save mode) 0x03 = Away
mode| 2| Dry Mode Schedule
0x10(16)| 1| When to report temperature relative change threshold value
actively, the unit is 0.1℃ 0, disabled let report
2- 10, rep or t when the threshold value is 2- 10| 2| None
0x11(17)| 1| Time interval value for a periodic report of
temperature, humidity, unit is S 0, disable to report 30~28800, report when
time interval value is 30~28800| 300 (5mins)| None
0x12(18)| 1| When to report power change absolute threshold, the
unit is W 0, disable to report 1~100, report when the absolute threshold is
1~100| 5| None
0x13(19)| 1| When to report current change absolute threshold, the
unit is 0.1A 0, disable to report 1~10, report when the absolute threshold is
1~10| 10| None
0x14(20)| 1| When to report voltage change absolute threshold, the
unit is 1 V 0, disable to report 1~10, report when the absolute threshold is
1~10| 2| **
None
0x15(21)| 4| Time interval value for periodic active report of
Meter 60-2678400 (31 days), unit is S| 600 (10mins)| None
0x16(22)| 1| The OLED displays brightness when operating the
device. 0, low level
1, mid-level
2, high level| ****
1
| ****
Other Set
0x17(23)| 1| This parameter defines which sensor temperature will
be displayed on the Home page.
0x00: indoor air temperature
0x01: external temperature (floor temperature)| ****
0
| ****
Other Set
0x18(24)| 1| The time zone that the time parameters command adopts is UTC, the time zone needs to be set: +12 ~ -12| 0| Other Set