DMP 711S Zone Expansion Module Installation Guide
- June 6, 2024
- DMP
Table of Contents
INSTALLATION GUIDE
711S
Zone Expansion Module
GET STARTED
The 711S is a flying lead style, single-zone, addressable expansion module
that allows you to increase the number of reporting zones available on DMP
panels. Refer to the panel installation guide for more information about zone
expansion modules and the maximum number allowed per panel. The modules
connect to the panel 4-wire Keypad Bus or LX-BusTM and are set to an address
that determines the reporting zone number. The 711S provides one Type-A Class
B zone.
What’s Included
- 711S Expansion Module
- 1k Ohm Resistor
Compatibility
- XT30/XT50 and XR150/XR550 Series Panels
INSTALLATION
Program the Panel
Setting Address Switches
The 711S Zone Expander uses two rotary switches identified as TENS and ONES
to set the module address. Use a small screwdriver to set the address
accordingly for Keypad Bus or LX-bus. For example, for address 502 on an XR550
Series panel set the TENS to switch to zero and the ONES switch to two as
shown in the figure above.
Keypad Bus Zone Numbers
The 711S module uses the first zone number only. The last three-zone
numbers cannot be used for other devices. For example, turn the 711S switches
to address 02 (TENS = 0, ONES = 2) to set the module zone number to zone 21.
Zones 22, 23, and 24 cannot be used. Refer to Table 1 for Keypad Bus zone
numbers and the panels where they operate.
| SWITCHES| ZONE NUMBER
---|---|---
KEYPAD ADDRESS| TENS| ONES| XT30/50| XR150| XR550
1| 0| 1| 11| 11| 11
2| 0| 2| 21| 21| 21
3| 0| 3| 31| 31| 31
4| 0| 4| 41| 41| 41
5| 0| 5| 51| 51| 51
6| 0| 6| 61| 61| 61
7| 0| 7| 71| 71| 71
8| 0| 8| 81| 81| 81
9| 0| 9| N/A| N/A| 91
10| 1| 0| N/A| N/A| 101
11| 1| 1| N/A| N/A| 111
12| 1| 2| N/A| N/A| 121
13| 1| 3| N/A| N/A| 131
14| 1| 4| N/A| N/A| 141
15| 1| 5| N/A| N/A| 151
16| 1| 6| N/A| N/A| 161
Table 1: Keypad Bus Zone Numbers
LX-Bus Zone Numbers
Refer to Table 2 for a partial list of XR550 Series panel LX-Bus zone numbers.
XR150 Series panels only use LX500. For LX-Bus addresses set the switches to
match the last two digits of the address.
| | SWITCHES
---|---|---
LX-BUS ADDRESS| LX-BUS NUMBER| TENS| ONES| ZONE NUMBER
501| 1 (LX500)| 0| 1| 501
506| 1 (LX500)| 0| 6| 506
623| 2 (LX600)| 2| 3| 623
654| 2 (LX600)| 5| 4| 654
742| 3 (LX700)| 4| 2| 742
768| 3 (LX700)| 6| 8| 768
833| 4 (LX800)| 3| 3| 833
877| 4 (LX800)| 7| 7| 877
919| 5 (LX900)| 1| 9| 919
994| 5 (LX900)| 9| 4| 994
Install the Module
The 711S addressable zone expansion module is for use in smaller applications,
such as installing in a pull station back-box or even in a recessed contact
hole behind the contact.
Wire the Module
Connect the Red, Yellow, Green, and Black wires from the panel Keypad Bus or
LX-Bus™ to the matching wires on the zone expander.
Caution: Do not use looped wire under terminals. Break wire run to
provide supervision of connections Wiring Specifications for Keypad and LX-Bus
DMP recommends using 18 or 22 gauge unshielded wire for all keypad and LX-Bus
circuits. Do Not use twisted pair or shielded wire for LX-Bus and Keypad Bus
data circuits. To maintain auxiliary power integrity when using
22-gauge wire do not exceed 500 feet. When using 18-gauge wire do not exceed
1,000 feet. Install an additional power supply to increase the wire length or
add devices.
Maximum distance for anyone circuit (length of wire) is 2,500 feet regardless
of the wire gauge. This distance can be in the form of one long wire run or
multiple branches with all wiring totaling no more than 2,500 feet. As the
wire distance from the panel increases, DC voltage on the wire decreases.
Maximum number of devices per 2,500 feet circuit is 40.
Maximum voltage drop between the panel (or auxiliary power supply) and any
device is 2.0 VDC. If the voltage at any device is less than the required
level, add an auxiliary power supply at the end of the circuit. When voltage
is too low, the devices cannot operate properly. Refer to the panel
installation guide and LX-Bus/Keypad Bus Wiring Application Note (LT-2031).
Keypad Bus or LX-Bus Wiring from Panel
All wiring is Power Limited and Supervised.
See Wire the Module.
Protection Zone Supervised 5 V, Class B, Style A
Max Impedance 100 Ω
Ground Fault Detected < 1200 Ω
Normal Operating Range 650 Ω to 1200 Ω
Program the Zones
You can program the 711S zone with any panel Burglary or Fire zone type or as
an Arming zone type when used with key switches.
Zone Expander Data LED
The 711S LED flashes each time the module responds to a poll from the panel.
If there is a problem with the panel, panel programming, or the Green data
wire between the panel and the zone expander module, the LED stops flashing.
COMPLIANCE INFORMATION
UL
To comply with ANSI/UL 365 Police-Connected Burglary System or ANSI/UL 609
Local Burglary Alarm Systems, the module must be mounted in a listed enclosure
with a tamper installed.
The keypad and LX-Bus are rated Class B, Style 3.5.
ULC Commercial Burglary (XR150/XR550 Series panels)
Place the 711S and other zone expander modules in a listed enclosure and
connect a DMP Model 307 Clip-on Tamper Switch to the enclosure programmed as a
24-Hour zone.
The 711S zone can only be used in Low-Risk applications. Medium or High-Risk
applications must use panel zone inputs.
SPECIFICATIONS
Operating Voltage | 8.8 to 15.0 VDC |
---|
Operating Current
Standby| 4.2 mA
Alarm| 4.7 mA
Zone Voltage| 5 VDC, max 2 mA
EOL Value| 1k Ohm
Dimensions| 1.25 W x 2.75 H in.
CERTIFICATIONS
▶ Commercial Burglar and Fire Accessory Zone Expander Signaling Device
▶ New York City (FDNY COA #6167)
Underwriters Laboratory (UL) Listed
ANSI/UL 365 | Police Station Connect Burglar Alarm Systems |
---|---|
ANSI/UL 609 | Local Burglar Alarm Units & Systems |
ANSI/UL 864 | Fire Protective Signaling Systems |
ANSI/UL 985 | Household Fire Warning System Units |
ANSI/UL 1023 | Household Burglar Alarm System Units |
ANSI/UL 1076 | Proprietary Burglar Alarm Units & Systems |
ANSI/UL 1610 | Central Station Burglar Alarm Units |
ANSI/UL 1635 | Digital Alarm Communication System Units |
ULC Subject-C1023 | Household Burglar |
ULC/ORD-C1076 | Proprietary Burglar |
ULC S304 | Central Station Burglar |
ULC S545 | Household Fire |
Designed, engineered, and manufactured in Springfield, MO using the U.S. and
global components.
LT-1875 1.01 21344
© 2021
INTRUSION · FIRE · ACCESS · NETWORKS
2500 North Partnership Boulevard Springfield, Missouri 65803-8877
800.641.4282 | DMP.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>