KPHTC411M
Air-to-Water Heat Pump Monobloc (41,000 Btu/h)
Performance:
Cooling Capacity (Btu/h)
(Leaving Water Temp. 64.4°F)
(Outdoor Temp. 95°F DB/75.2°F WB)| 41,000
---|---
Heating Capacity (Btu/h)
(Leaving Water Temp. 95°F)
(Outdoor Temp. 44.6°F DB/42.8°F WB)| 41,000
EER Cooling (Btu/Wh)
(Leaving Water Temp. 64.4°F)
(Outdoor Temp. 95°F DB/75.2°F WB)| 16.21
COP Heating (W/W)
(Leaving Water Temp. 95°F)
(Outdoor Temp. 44.6°F DB/42.8°F WB)| 4.90
COP @ A5W110
(Leaving Water Temp. 110°F)
(Outdoor Temp. 5°F)| 2.5
Performance values indicated above are in accordance with EN14511.
Water Operating Range:
Cooling Mode Leaving Water Temp (°F) | 41 ~ 80.6 |
---|---|
Heating Mode Leaving Water Temp (°F) | 59 ~ 149 |
Refrigerant Data:
Refrigerant Type | R32 |
---|---|
GWP (Global Warming Potential) | 675 |
Refrigerant Control / Oil | Electronic Expansion Valve/FW68D |
Refrigerant Charge (lbs.) | 4.41 |
Compressor Type | Hermetic Sealed Scroll |
Heat Exchanger Type / Qty | Fin & Tube / 2 |
Fan Type / Motor | Propeller / BLDC |
Net Dimensions (WxHxD, in.) | 48-51/64 x 54-21/64 x 12-63/64 |
Shipping Dimensions (WxHxD, in.) | 53-45/64 x 60-7/64 x 17-41/64 |
Net / Shipping Weight (lbs.) | 262.6 / 295.6 |
Sound Power dB(A)3
(Daytime Max/Rated/Low Noise)| 65 / 60 / 56
Sound Pressure dB(A)4
(Daytime Max/Rated/Low Noise)| 57 / 52 / 48
Electrical:
Power Supply (V/Hz/Ø)1,2 | 220-240 / 60 / 1 |
---|---|
Peak Control Running Current(A) | 23.0 |
Rated Running Current (A)
Cooling| 11.2
Heating| 10.9
Circuit breaker (A)5| 40
Rated running currents are based on the following conditions:
- Cooling: Outdoor Temp. 44.6°F DB/42.8°F WB and Leaving Water Temp. 95°F
- Heating: Outdoor Temp. 95°F DB/75.2°F WB and Leaving Water Temp. 64.4°F
Water Data:
Water Pump Type | Canned for hot water circulation |
---|---|
Water Pump Motor | BLDC |
Water Pump
Power input (Min./Rated) (W)| 3.5 / 140
Water Flow Rate (Min./Rated) (GPM)| 0 / 12.15
Piping Connections
Inlet/ Outlet (in.)| 1 Male Pipe Thread (tapered)
Strainer
Material/Mesh Size/Max. particle size| Stainless Steel / 30 / 1-3/16 (in.)
Relief Valve Pressure (PSI)| 43.5
Water Pressure sensor
Measuring range (Min.~Max.) PSI(G)| 0 ~ 290
Flow Sensor
Measuring range (Min.~Max.) (GPM)| 1.3 ~ 21.1
Flow Trigger Point (GPM)| 3.96
Devices for Water Circuit:
- Relief valve / Flow Sensor
- Drain hose
- Pressure Sensor / Air vent
Accessories :
- Second Circuit Thermistor – PRSTAT5K10
- Domestic Hot Water Sensor – PHRSTA0
- PI-485 Gateway – PP485A00T
- Wired Remote Control Cable Assembly – PZCWRC1
- AC Smart 5 – PACS5A000
- ACP 5 – PACP5A000
- Simple Dry Contact – PDRYCB100
- Dry Contact for Third Party Thermostat- PDRYCB320
- Wi-Fi Module – PWFMDD200
- PWYREW000 – Extension Cable for Wi-Fi Modem
- PENKTH000 – Meter Interface Module
- PQRSTA0 – Remote Room Air Temperature Sensor
For a complete list of available accessories, contact your LG representative.
Notes:
-
Must follow installation instructions in the applicable installation manual.
1. Power wiring size must comply with the applicable local and national code.
2. Acceptable operating voltage range: 198V – 264V.
3. Sound power level is measured in accordance with ISO 9614. -
Daytime Max: This mode is measured based on max. fan RPM and max. compressor Hz. that can be reached under outdoor air temperature of 35.6°F.
-
Rated: This mode is measured on the rated condition in the semi-anechoic rooms. Therefore, these values may vary depending on operation conditions.
-
Low Noise: This mode lowers noise by limiting the compressor Hz. and fan RPM, and thus the performance may be limited.
4. Sound pressure level is converted value at 1m distance from sound power level based on tonality penalty of 0dB and installation in free-field.
5. All installation sites must be equipped with an Earth Leakage Circuit Breaker (ELCB).
Note
- Unit must be installed in compliance with the installation manual in the product box.
- Unit must be grounded in accordance with the local regulations or applicable national codes.
For continual product development, LG reserves the right to change
specifications without notice.