Wired digital thermostat – non-programmable
Model: HTRS230(30)
User manual
Ver. 1
Date of issue: 24 VI 2020
Power supply: 230V
Introduction
The HTRS230V(30) from SAWS Controls is a digital, wired and surface-mounted
(or on a flush-box) nonprogrammable room thermostat dedicated for surface
heating/cooling control, characterized by high thermal inertia. It is
connected to the wiring center. The thermostat does not have the function of
creating schedules – it lowers the set temperature via the wiring center after
receiving the NSB signal from the weekly thermostat. Thanks to the built-in
algorithms, it offers much better temperature control accuracy than
traditional mechanical thermostats. The thermostat is characterized by silent
operation. The controller is characterized by silent operation.
Product compliance
The product complies with the following EU directives: 2014/30/EU,
2014/35/EU, 2011/65/EU. Full information is available at
www.saluslegal.com
Note!
This document is a quick guide to the installation and operation of the
product and indicates its main features and functions. Detailed information
are in the full manual, which is available at www.salus controls.eu
and which must be used for proper
installation and operation of the product.
Safety information:
Use in accordance with national and EU regulations. Use the device as
intended and keep it dry. Product for indoor use only. Please read the entire
manual before starting the installation and using the product.
Installation:
Installation must be carried out by a qualified person, with appropriate
electrical authorizations, in accordance with national and EU standards and
regulations. The manufacturer shall not be liable for failure to comply with
the manual.
NOTE: There may be additional protection requirements for the entire
installation. The installer shall be responsible for compliance with such
requirements.
Package content
Proper thermostat location
The ideal position to thermostat mounting is about 1,5m under floor level far from heating or cooling sources. In addition, the thermostat should not be installed behind curtains or other obstacles or in places with high humidity, as this will prevent accurate measurements of room temperature. The thermostat must not be exposed to sunlight. Do not place the thermostat on an outer wall.
Connection description
**** Note: The thermostat is compatible with the following Salus wiring center models: KL06 230V, KL08NSB 230V, KL04NSB 230V or directly to the actuator.
Symbols explanation
Terminal | Description |
---|---|
L, N | Power supply (230V AC) |
NSB | Night temperature reduction (230V output) |
SL | 230 V AC output signal 230V AC |
CO | Switching jumper between heating and cooling (input 230V AC) |
Note : The following designations are used interchangeably for products:
→ = SL
= NSB
Montage
Make sure that the thermostat is not connected to the 230V AC. Then open the front housing using a screwdriver as shown above.
Connect the thermostat properly. Please refer to the “Connection Description” section. Mount the thermostat using the designed screw holes.
Slide the thermostat on the back cover. The thermostat is configured for operation. Use buttons to set the temperature setpoint.
Button functions
∧| Increase /or decrease setpoint temperature setpoint
or value
---|---
∨
<| Mode selection
>
| Short press to confirm the selection
Press and hold – enter/exit the menu
LCD icon description
1. Heating mode
2. Cooling mode
3. Active work mode
4. Comfort temperature mode
5. Economic temperature mode| 6. AUTO mode
7. Frost protection mode
8. Temperature unit
9. Current/set temperature
10. Manual mode/temp. override
---|---
Manual mode – temperature setpoints
3 temperature levels are available. In manual mode, only one temperature level is maintained for the entire day. The icon in the frame indicates which mode is currently active. A different temperature can be set for each level.
– Comfort temperature mode
– Economic temperature mode
– Frost protection mode is Usually used during the period of long absence, or
during the holidays (only available in mode). HEATING
Press any button to highlight the screen, then follow the steps below:
Temperature setpoint
Press any button to highlight the screen, then follow the steps below:
AUTO mode – NSB function
The NSB (Night Setback) function enables automatic reduction of the
temperature setpoint on the HTRS230(30) SLAVE thermostat, via the HTRP230(50)
programmable MASTER thermostat connected to the wiring center (or another
external clock). The temperature change takes place between the comfort
temperature mode and economic temperature mode.
To activate the AUTO mode, select the icon A. Together with the icon, the
thermostat shows the active temperature mode on the display: or .
Press any button to highlight the screen, then follow the steps below:
Note: For the proper NSB function work, an appropriate cable connection is required. The connection description is on the previous page.
Calibration of displayed temperature – “offset” function
The thermostat allows to correct the displayed temperature by ±3.0°C.
Follow the steps below:
Press any button to highlight the screen, then follow the steps below:
Note: Calibration of the temperature can also be set in the installer parameters (parameter d02).
Heating / Cooling mode
Manual change:
Modes are indicated by symbols. Press and hold the button to enter the menu,
then use> the button to select the Heating / Cooling mode change setting.
Confirm changes using the button. Now use ∧ or ∨ buttons to set the heating or
cooling mode. Confirm by button.
Automatic change (via CO terminal):
The heating/cooling mode can be changed automatically via the CO terminal in
the thermostat. If a 230 V AC power supply is connected to the CO terminal –
then the thermostat automatically switches to cooling mode. If you want to use
this function, then you have to change the value of the d18 parameter to “1”.
Cooling blocking:
When D 19 thermostat parameter is set to “1”, then cooling is blocked for a
single room. When the cooling function is blocked, no message is displayed.
Installer mode
Press any button to highlight the screen, then follow the steps below:
Installer parameters
| Function| Parameter Values| Description| Default Values
---|---|---|---|---
601| Heating Control| 0| According
to the PWM algorithm
| 0
1| Hysteresis: 0.5 °C
(± 0.25 °C)
2| Hysteresis: 1.0 °C
(±0.5 °C)
d02| Displayed temperature correction| from
-3.0°C
to +3.0°C| if the thermostat indicates an incorrect temperature, then it can
be corrected ±3.0°C| 0.0°C
d05| Cooling Control| 1| Hysteresis: 0.5 ct
(± 0.25 °C)| 2
2| Hysteresis: 1.0 °C
(±0.5 °C)
d07| Valve Protection| 0| Disabled| 1
1| Enabled
d08| Frost protection setpoint| 5.0 —
17.0°C| The frost protection temperature is maintained for example during
active holiday mode.| 5.0°C
d12| Heating setpoint limits| 5.0 —
35.0°C| Maximum temperature which can be set for heating| 35.0°C
---|---|---|---|---
d13| Cooling setpoint limits| 5.0 — °C
40.0
| The minimum temperature which can be set for cooling| 5.0°C
d18| Heat/Cool Mode Selection| 0| Manual by buttons use| 0
1| Automatic by the CO terminal
d19| Cooling Blocking function| 0| Cooling allowed| 0
1| Cooling disabled
d20| Actuators loading selection for different temperature compensation|
0 — 5| Numbers 1 to 5 are the numbers of actuators con-netted to the
thermostat.| 0
Factory reset
If you made a mistake, want to change the thermostat parameters or return to
factory settings, follow the steps below.
**** Note: This action will permanently delete all current settings.
Press any button to highlight the screen, then follow the steps below:
IMPORTER:
QL CONTROLS Sp. z o.o. Sp. k.
ul. Rolna 4, 43-262 Kobielice
PRODUCER:
Salus Limited
6/F, Building 20E, Phase 3, Hong Kong Science
Park, 20 Science Park East Avenue, Shatin,
New Territories, Hong Kong
www.salus-controls.eu
SALUS Controls is a member of the Computime Group.
In accordance with the product development policy, SALUS Controls plc reserves
the right to change specifications, design, and materials used in production,
presented in this manual, without prior notice.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>