The AT10 contact thermostat / AT10F capillary thermostat is a mechanical thermostat, which can be very easily installed – to the surface of the pipe or by placing the capillary in a sleeve, e.g. of a hot water tank. It allows controlling the temperature of hot water (DHW) or central heating. It can be used to switch connected devices on or off in relation to the measured temperature. These can include pumps, switching valves, or boilers.
Product compliance
The product is compliant with the following directives: Low Voltage Directive LVD 2014/35/EU, RoHS Directive 2011/65/EU. Full information is available at www.saluslegal.com
****Safety information:
Use in accordance with national and EU regulations. Use the device as intended and do not allow it to get wet. Product for indoor use only. Installation must be carried out by a qualified person, in accordance with national and EU regulations.
Description of electrical connections
Terminal | Description |
---|---|
C | Common contact |
1 | NO — normally open contact |
2 | NC — normally closed contact |
Ground |
Installation
Remove the knob (1) and loosen the large plastic screw (2). Remove the housing
cover. Connect the cable contacts as presented in the diagram:
1. Underfloor heating protection against
overheating in case of exceeding the temperature setpoint – C-1 terminals are
opened
2. Filling the hot water (DHW) tank if the temperature in the tank drops below the set value – C-1 terminals are closed
Montage
AT10: For installation, press the thermostat firmly to the heat pipe and
fix it with the supplied elastic band so that the thermostat is in direct
contact with the pipe (remove any insulation at the installation spot before
fixing the sensor). The excess elastic band can be trimmed.
AT10F: Fix the thermostat to a flat surface using screws. Then place the
measuring element (capillary) in the measuring sleeve, e.g. located in the hot
water tank.
Changing temperature setpoint
To set the temperature, pull the knob towards you to release it. Then turn the knob to the position which indicates the required temperature. To keep this setting, press the knob lightly in the inward direction until a click is heard.
Technical information
Power supply | 230VAC |
---|---|
Max. load | 16 (4) A |
Output signal | terminals 1/C/2 (NO/COM/NC) |
Temperature adjustment range | 30 — 90 °C |
Dimension [mm) | 105 x 50 x 45 |
AT1OF: length of the capillary: 1200, 0 of the capillary: 7
SALUS CONTROLS DISTRIBUTOR:
QL CONTROLS Sp. z o.o., Sp. k.
ul. Rona 4,
43-262 Kobielice, Poland
Importer:
SALUS Controls Plc
Units 8-10 Northfield Business Park
Forge Way, Parkgate, Rotherham
S60 1SD, United Kingdom
www.salus-controls.eu
SALUS Controls is a member of the Computime Group.
In accordance with the product development policy,
SALUS Controls plc reserves the right to change specifications, design,
and materials used in production, presented in this manual, without prior
notice.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>