SALUS Wiring Centre 6-Zones KL06 24V User Manual

June 6, 2024
SALUS

SALUS logo

SALUS Wiring Centre 6-Zones KL06 24V

SALUS Wiring Centre 6-Zones KL06 24V

Introduction

Wired KL06 24V wiring centre allows easy and quick connection of thermostats and actuators. It has a serial connector for additional modules (sold separately):
• PL06 Pump or boiler control module
• PL07 Pump and boiler control module
The KL06 24V wiring centre is adapted to work with NC type actuators (normally closed) and maximum 6 thermostats.

Product Compliance

This product complies with the essential requirements and other relevant provisions of the following EU Directives: EMC 2014/30/EU, Low Voltage Directive LVD 2014/35/EU, RoHS directive 2011/65/EU. The full text of the EU Declaration of Conformity is available at the following internet address: www.saluslegal.com

Safety information

Use in accordance to national and EU regulations. Use the device as intended, keeping it in dry condition. Product for indoor use only. Installation must be carried out by a qualified person in accordance to national and EU regulations. Before any of operation releated to power supply (connecting wires, installing the device, etc.), make sure that KL06 is not connected to any power source. Installation must be carried out by a qualified person. Incorrect connection of the wires may cause damage to the wiring centre. The KL06 can not be used in conditions of water vapor condensation neither exposed to water.

Technical Information

Power Supply 24 V AC 50 Hz
Max load 2 (1) A
Outputs Terminals for actuator (24 V)
Dimmensions [mm] 300 x 86 x 63

Wiring centre description

description 1

1. Cartridge fuse 5 x 20 mm 2 A
2. Power Supply
3. Diodes
4. NSB (Night Set Back reduction) function
5. Thermostats connection
6. Actuators connection
7A. PL06 – pump (or boiler) control module
7B. PL07 – pump and boiler control module
8. Serial connector for PL06 and PL07 modules

Fuse

Note : Replace the fuse only when the wiring centre is disconnected from power supply 24V~.

Main fuse is located under the housing cover next to power supply terminals and secures the wiring centre and the devices connected to it. Use cartridge fuses (5×20 mm) with nominal max current 2 A. To replace fuse remove the fuse holder with a flat screwdriver and pull out the fuse.

Power Supply

Power supply for wiring centre is 24V 50Hz.description
2

LED diodes

  • green LED diode indicates power supply connection 230 V.
  • orange LED diode indicates NSB function being activated.

NSB (Night Set Back reduction) function

NSB function is activated in non-programmable Salus thermostats of the Expert NSB, HTR, BTR series via external signal. NSB 24 V signal (night-time temperature reduction) is sent via an external timer or programmable thermostat connected to the KL06 wiring centre. Non-programmable thermostats are receiving NSB signal and reducing setpoint temperature (by switching to eco mode). All thermostats have to be connected using a 4-wire cable (min. 4 x 0,75 mm², max. 4 x 1,5 mm² ).

Thermostats connection

  • Connecting HTR series thermostat with NSB functiondescription 3
  • Connecting RT10 24V thermostat with NSB function.description 4

Connecting ON/OFF battery-powered thermostat with voltage-free COM / NO output contacts (np. 091FL, RT310, RT510).description 5

Actuators connection

Wires of thermoelectric actuators should be plugged into self-locking connectors in appropriate zones. 4 actuators can be connected directly to one zone.description 6

7 A. PL06 – pump (or boiler) control module

PL06 module is used to control the pump (or boiler) using volt-free NC/COM/NO contacts. When any of thermostats connected to the KL06 24 V reports heat demand, COM/NO contacts are closing. COM/NO contacts are opening, when thermostats connected to the wiring centre will stop sending signal for heating.

Jumpers 0-15
These are used to set in minutes the delay time (overrun time). Default setting is „0”. 0-15 values specify the time in minutes. E.g. when jumper is set to value „0”, COM/NO output will turn off as soon as the thermostats stop calling for heat. If jumper will be set to the value „10”, the module will turn off 10 min after the thermostats stop calling for heat.

Jumpers P,1,2,3,4,5,6
They are used to select the zone which turns on the module. Default setting is „P”.
P – all zones start the module
1, 2, 3, 4, 5, 6 – select the specific zone which turns on the module.

PUMP CONTROLdescription 7

BOILER CONTROLdescription 8

  • Power Supply from the KL06 wiring centre
  • Max load 5 (2) A
  • Outputs NO/COM/NC relay
  • Dimensions [mm] 60 x 80 x 20

7 B. PL07 – pump and boiler control module

PL07 module is used to control the pump and the boiler using volt-free COM/NO contacts. When any of thermostats connected to the KL06 230V reports heat demand, COM/NO contacts are closing. COM/NO contacts are opening, when thermostats connected to the wiring centre will stop sending signal for heating.

ON-OFF Delay jumper
Is used to activate the delay output for the pump and boiler. Default is „ON”.

ON-OFF Overrun jumper
Is used to activate the delay output for the pump when heating is satisfied. Default is „ON”.

  • „ON” position turns OFF the pump output with a delay of 3 minutes when all thermostats stop calling for heat.
  • „OFF” position immediately turns OFF the pump output when all thermostats stop calling for heat.

PUMP AND BOILER CONTROLdescription 9

Power Supply from the KL06 wiring centre
Max load 5 (2) A
Outputs 2 x NO/COM relay
Dimensions [mm] 70 x 80 x 20

Serial connector for PL06 and PL07 modules

It provides communication between the KL06 wiring centre and the PL06/PL07 modules. KL06 wiring centre + PL06/PL07 module increases functionality and additionally makes possible to control pump and/or boiler. PL06/PL07 module is powered from the wiring centre.description 10

INSTALLATION

installation 1 installation
2

INSTALLATION OF THE ADDITIONAL MODULE PL06 OR PL07 ON THE EXAMPLE OF PL06 MODULEinstallation 3

Documents / Resources

| SALUS Wiring Centre 6-Zones KL06 24V [pdf] User Manual
SALUS, Wiring Centre, 6-Zones, KL06 24V
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals