Technical Specifications

Operation frequency 2.4 GHz – 2.483 GHz
Transmission power 4 dBm
Range (Typical indoor) 10~30m
Protocol 5.0 SIG Mesh
Stand-by power <1W
Operating voltage 220~240VAC  50/60Hz
DALI Channel 1 30mA, Max. 15 LED drivers
DALI Channel 2 50mA, Max. 25 LED drivers
Sensor principle PIR detection
Detection range (Max.)* Installation height: 6m
HBHC25 Detection Range (Ø) :9m
Detection range (Max.)* Installation height: 6m
HBHC25/R Detection Range(Ø) :10m
Detection range (Max.)* Installation height:15m (forklift)

12m (person)
 HBHC25/H| Detection range (Ø):24m
Detection range (Max.)*| Installation height:15m (forklift)
12m (person)
 HBHC25/RH| Detection range (Ø):40m
Detection angle| 360°
Operation temperature| Ta:-20°C~+50°C
IP rating| IP20
EMC standard (EMC)| EN55015, EN61000, EN61547
Safety standard (LVD)| EN60669-1/-2-1
AS/NZS60669-1/-2-1
RED| EN300328, EN301489-1/-17
Certification| CB, CE, EMC, RED, RCM

Download the App

Free App for set-up and commissioning

https://apps.apple.com/cn/app/koolmesh/id1570378349
https://apps.apple.com/cn/app/koolmesh/id1483721878
www.hytronik.com
Web app/platform: iot.koolmesh.com

Installation

Mechanical Structure & Dimensions

  1. Ceiling (drill hole φ66~68mm)
  2. Carefully prise off the cable clamps.
  3. Make connections to the pluggable terminal blocks.
  4. Insert plug connectors and secure using the provided cable clamps, then clip terminal covers to the base.
  5. Fit detection blind (if required) and desired lens.
  6. Clip fascia to the body.
  7. Bend back springs and insert them into the ceiling.

Wire Preparation

Pluggable screw terminal. It is recommended to make connections to the terminal before fitting to the sensor.
Wiring Diagram

Dimming Interface Operation Notes

Switch-Dim
The provided Switch-Dim interface allows for a simple dimming method using commercially available non-latching (momentary) wall switches. Detailed Push switch configurations can be set on the Koolmesh app.

Switch Function Action Descriptions
Push switch Short press (<1 second)
* Short press has to be longer Man 0.1 s. or it will be invalid. – Turn on/off – Recall a scene

– Turn on only – Exit manual mode
– Turn off only – Do nothing
Double push| – Turn on only – Exit manual mode
– Turn off only – Do nothing
– Recall a scene
Long press (1 second)
– Colour tuning| – Dimming
– Do nothing
Simulate sensor| /| – Upgrade a normal on/off motion sensor to a Bluetooth controlled motion sensor

Detection Pattern & Optional Accessories

1. HBHC25 (Low-bay)
HBHC25: Low-bay flat lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-6m)

Mount height Tangential (A) Radial (B)
2.5m max 50m2(Ø = 8m) max 13m2 (Ø = 4m)
3m max 64m2(Ø = 9m) max 13m2 (Ø = 4m)
4m max 38m2(Ø = 7m) max 13m2(Ø = 4m)
5m max 38m2(Ø = 7m) max 13m2(Ø = 4m)
6m max 38m2(Ø = 7m) max 13m2(Ø = 4m)

2. HBHC25/R (Reinforced Low-bay)
HBHC25/R: Low-bay convex lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-6m)

Mount height Tangential (A) Radial (B)
2.5m max 79m2(Ø = 10rn) max 20m2 (Ø = 5m)
3m max 79m2 (Ø = 101-n) max 20m2 (Ø = 5m)
4m max 64m2 (Ø = 9m) max 20m2 (Ø = 5m)
5m max 50m2 (Ø = 8m) max 20m2 (Ø = 5m)
6m max 50m2 (Ø = 8m) max 20m2 (Ø = 5m)

3. HBHC25/H (High-bay)
HBHC25/H: High-bay lens detection pattern for forklift @ Ta = 20ºC
(Recommended ceiling mount installation height 10m-15m)

Mount height Tangential (A) Radial (B)
10m max 380m2 (Ø = 22m) max 201m2(Ø = 16m)
11rn max 452m2 (Ø = 24m) max 201m2 (Ø = 16m)
12m max 452m2 (Ø = 24m) max 201 m2 (Ø = 16m)
13m max 452m2 (Ø = 24m) max 177m2 (Ø = 15m)
14m max 452m2 (Ø = 24m) max 133m2 (Ø = 13m)
15m max 452m2 (Ø = 24m) max 113m2 Ø= 12m)

HBHC25/H: High-bay lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-12m)

Mount height Tangential (A) Radial (B)
2.5m max 50m2 (Ø = 8m) max 7m2 (Ø = 3m)
6m max 104m2 (Ø = 11.5m) max 7m2 (Ø = 3m)
8m max 154m2 (Ø= 14m) max 7m2 (Ø = 3m)
10m max 227m2 (Ø = 17m) max 7m2 (Ø = 3m)
11m max 269m2 (Ø= 18.5m) max 7m2 (Ø= 3m)
12m max 314m2 (Ø = 20m) max 7m2 (Ø = 3m)

4. HBHC25/RH (Reinforced High-bay with 3-Pyro)
HBHC25/RH: Reinforced high-bay lens detection pattern for forklift @ Ta = 20ºC
(Recommended ceiling mount installation height 10m-15m)

Mount height Tangential (A) Radial (B)
10m max 346m2 (Ø = 21m) max 177m2 (Ø = 15m)
11 m max 660m2 (Ø= 29m) max 177m2 (Ø = 15m)
12m max 907m2 (Ø = 34m) max 154m2 (Ø = 14m)
13m max 962m2 (Ø = 35m) max 154m2 (Ø = 14m)
14m max 1075m2 (Ø = 37m) max 113m2 (Ø = 12m)
15m max 1256m2 (Ø = 40m) max 113m2 (Ø = 12m)

HBHC25/RH: Reinforced high-bay lens detection pattern for single person @ Ta = 20OC
(Recommended ceiling mount installation height 2.5m-12m)

Mount height Tangential (A) Radial (B)
2.5m max 38m2 (Ø = 7m) max 7m2 (Ø = 3m)
6m max 154m2 (Ø = 14m) max 7m2 (Ø = 3m)
8m max 314m2 (Ø= 20m) max 7m2 (Ø = 3m)
lOrn max 531 m2 (Ø = 26m) max 13m2 (Ø = 4m)
11rn max 615m2 (Ø = 28m) max 13m2 (Ø = 4m)
12m max 707m2 (Ø = 30m) max 13m2 (Ø = 4m)

Additional Information / Documents

  1. To learn more about detailed product features/functions, please refer to www.hytronik.com/download ->knowledge ->Introduction of App Scenes and Product Functions
  2. Regarding precautions for Bluetooth product installation and operation, please kindly refer to www.hytronik.com ->download/knowledge ->Bluetooth Products – Precautions for Product Installation and Operation
  3. Datasheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/bluetooth technology ->Bluetooth Sensors
  4. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy.

Subject to change without notice.
HBHC25-20200302-A0

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals